6ES5 700-3LA12
Siemens 6ES5 700-3LA12 CR 700-3 central rack
The 6ES5 700-3LA12 is the CR 700-3 rack for a CC 3 central controller in a SIMATIC S5-115U system. This SIMATIC S5 mounting rack connects the power supply, CPU and I/O cards through a common backplane. It is designed for a 19-inch cabinet. The Siemens manual gives chassis dimensions of 483 × 303 × 47 mm (W × H × D) and a weight of 5 kg.
S5-115U slot layout
The PS slot takes a PS 951 power supply and the CPU slot takes the processor. The CPU 944 and CPU 945 are examples from the S5-115U processor range listed for the CR 700-3. The rack has numbered positions 0–6 and a dedicated IM slot. Siemens specifies up to 11 I/O modules with a suitable adapter and module layout.
Slots 3–5 are the main positions for block-type digital inputs, digital outputs, combined I/O and analogue modules. Figure 3-7 specifies an IM 306 to address block-type analogue modules in slots 4 and 5. Check the permitted position for each compact module by its complete order number. Slot 6 does not process hardware interrupts.
For centralised expansion, the IM 305 or IM 306 uses the dedicated IM slot. For distributed links, the Siemens table lists interface modules such as the IM 304 and IM 308 in slot 6. The ER 701-0, ER 701-2 and ER 701-3 are separate expansion racks. The IM order numbers at both ends determine the supported link.
Slot, adapter and power requirements for communications processors and positioning modules depend on the exact card. For example, Siemens excludes a 3 A power supply when using a CP 524. Positions 0, 1, 2 and 6 can take two single-width cards in a suitable adapter casing. A fan assembly is required when two cards share one casing. The 6ES5 981-0HA11 is the 115/230 V AC fan option for a long rack.
S5-115H use. Siemens ST 50 also lists the same order number for central controllers using the CPU 942H. That layout allows up to nine I/O modules and uses an IM 304 or IM 324R to link the two central controllers. Use the S5-115H slot table for that configuration.
- Back up the STEP 5 program before removing the rack. Record the PS, CPU and IM order numbers, module positions and the left-right order in dual adapters.
- After safely isolating power, inspect the backplane pins and guides. Check the PS and CPU positions in particular for bent pins, loose connectors or signs of overheating.
- If the CPU stays in RUN but a block-type analogue card in slot 4 or 5 cannot be read, check the IM 306 and STEP 5 address before replacing the card.
- If the central cards respond but the entire expansion rack is missing, check the IM order numbers at both ends first. Then check the link cable and the expansion unit’s power source.
- If the fault appears as the rack warms up, identify casings holding two cards. Check the fan and filter, then compare the CP’s requirements with the PS 951 current rating.
- After replacement, keep actuator power circuits isolated while monitoring inputs in STEP 5. Verify that field signals match the original address list.
When buying used, confirm whether the offer includes the rack, CPU, power supply, adapters and fan. To offer a rack for sale, send label and backplane photos to otomasyonavm@gmail.com.
PDFs and Siemens references
S5-115U manual, Figure 3-7 (EN) · Technical data, p. 15-7 (EN) · ST 50 S5-115U, p. 3/62 (EN) · ST 50 S5-115H, p. 3/70 (EN).
Related topics
About Siemens S5 PLCs · CR 700-2 central rack · ER 701-3 expansion rack
Used Siemens · S5 racks · CPU 90U–115U · Siemens S5 · Used Siemens main page