6ES5 374-0AB11
6ES5 374-0AB11 Siemens SIMATIC S5 IP 252 DRS/SR Memory Submodule
The Siemens 6ES5 374-0AB11 is a DRS/SR memory submodule for the X3 socket on the SIMATIC S5 IP 252 closed-loop control module. It provides the expanded drive controller with self-tuning and the standard controller structure. Siemens’ detailed technical record specifies 2 × 32 KB EPROM, 8 KB EEPROM and 200 mA at 5 V. IP 252 installations include the S5-115U, the S5-135U with an R processor, and the S5-150U.
In service, the IP 252 uses the structures on this card to run a drive speed loop or a standard process loop. The module can take speed feedback through its X4 encoder input or X6 analog connection. The controller firmware and site-specific parameters occupy separate memory areas on the S5 memory submodule.
What does the DRS/SR version add?
The 0AB11 extends the DR/SR structures of the 6ES5 374-0AA11 with speed-loop self-tuning, connections between control loops, and arithmetic functions. Siemens specifies loop numbers 1 and 2 and a speed-controller sampling time of 4 ms or 8 ms for automatic commissioning.
The 6ES5 374-0BA11 is a separate IP 252 special version. The 6ES5 374-1KG11 is a different short-format Flash card. Siemens’ short 0AB11 data sheet uses the description 128 KB (8-bit) Flash EPROM. For the IP 252 firmware and parameter areas, use the EPROM and EEPROM breakdown in the detailed record and IP 252 manual.
How do you check the X3 socket and IP 240 expansion?
The memory card plugs into the 48-contact X3 socket on the front of the IP 252. The IP 252 fits the S5-115U mounting rack with an adapter casing. Siemens’ IP 252 application example uses a CR 700-2 rack and a CPU 942-7UA11. For an S5-135U central rack, check the manual for the hardware configuration with an R processor.
For additional encoder feedback via IP 240, Siemens specifies an S5-115U with a 7 A/15 A class power supply, an IP 252 6ES5 252-3AA13 at hardware release A04 or later, and the 0AB11 submodule. The software requirement is COM REG from release A05 or COM REG GRAPHIC. If a CPU 944 is fitted, the manual lists the 944-7UA12 or 944-7UA22 and later versions. Check both the power supply class and the slot layout for direct data exchange.
How are settings saved to EEPROM?
Set the controller structure, sampling time, structure switches and analog channel assignments with the IP 252 in STOP. Connect the PG to the IP 252’s X5 TTY interface using the appropriate S5 connection cable. Retentive settings entered in COM REG go into the IP 252’s RAM first, then to EEPROM.
Use SEND 21 to store changes in EEPROM. For cyclic transfers from the CPU, SEND 22 sends data without writing to EEPROM. On systems with a display, keep the communications processor settings and CP 526 display project separate from the IP 252 backup.
Editor’s note
When ordering a spare, record 374-0AB11 and the full IP 252 order number separately. On visually similar cards in the S5 special modules range, the suffix identifies the controller functions.
Before removing the card, save the COM REG project, the analog I/O mapping and the sampling time for each loop. Keep the SIMATIC S5 CPU program backup in a separate file.
Change the card with the IP 252 powered down. Set the IP 252 to STOP before restoring power, then verify the settings loaded from the replacement card.
If the IP 252 stays in STOP after the swap, check the seating and identification of the card in X3 first. The manual states that the IP 252 remains accessible from the PG if the card is missing or its identification is invalid.
Run self-tuning during controlled commissioning. The IP 252 suspends its other control loops while identifying and optimizing the selected loop. Record the existing Kp, Ti and limit settings first.
OtomasyonAVM resources and PDFs
IP 252 6ES5 252-3AA11 control module · IP 252 6ES5 252-3AA13 and manual links · SIMATIC S5 memory cards
OtomasyonAVM S5-115 PDF archive