6ES5 752-0LA12

Siemens 6ES5 752-0LA12 – 20 mA TTY Interface Module for CPU 945

6ES5 752-0LA12 is a 20 mA current-loop TTY module for the second serial interface of the S5-115U CPU 945 in the Siemens SIMATIC S5 family. This interface module provides transmit and receive circuits through a 25-pin female connector, at a maximum rate of 9,600 bit/s.

The module supports ASCII and 3964/3964R links within the CPU 945's industrial communication functions. The manual also describes its use as a programming-device interface. Its role in S5 communications is to provide the electrical TTY interface.

CPU 945 and related interface options

The Siemens ordering table lists this module among the CPU 945 options, alongside the 6ES5 945-7UA13 and 6ES5 945-7UA23 processors. It fits the CPU's replaceable interface-module receptacle.

6ES5 752-0LA52 is the 15-pin PG module; 6ES5 752-0LA62 is the SINEC L1 option. Match the complete order number, connector and operating mode.

Understanding the 20 mA TTY connection

TTY transfers data through the presence or absence of loop current. RS-232, RS-422 and TTY use different electrical interfaces. Assess the serial interface differences independently of connector shape. Here, 20 mA describes a serial communication loop, rather than a 4–20 mA analog measurement signal.

Identify which device supplies the current in each transmit/receive loop. The CPU 945 manual explains that the PLC power supply provides the 24 V needed to generate loop current, with connections established through jumpers in the cable connector.

Transmit and receive pins, and cabling

Figure 12.34 assigns 10: +TXD, 19: −TXD, 13: +RXD and 14: −RXD. Pins 12 and 16 provide +20 mA current sources. Check the S5 cables and connectors against this diagram. With a connection adapter, also verify how each contact reaches the other device.

The manual specifies a shielded four-wire cable with a braided screen and metal connector housing, and lists a maximum TTY cable length of 1,000 m. Confirm the actual cable and wiring arrangement for the installation. Jumpers 1 and 2 on the module change the logical polarity of transmit and receive data.

Parameters and communication checks

The communication mode, rate and character format in the PLC program must match the partner device. During troubleshooting, check the physical loop, transmit/receive direction and protocol settings separately. An electrical connection alone does not establish a successful ASCII or 3964R transaction.

Used-module selection and order numbers

For a used communication module, request a complete label photograph, connector details and the scope of a test involving data exchange in both directions. If buying it with a used PLC CPU, record the processor's complete order number too.

Keep 6ES5 752-0AA12 distinct from 6ES5 752-0LA12; a shared TTY description is not sufficient replacement approval. If the partner is a used HMI panel, verify its electrical interface, pin assignments and communication protocol separately.

Editor’s note

Read the label before judging the connector. A 25-pin connector does not establish an RS-232 interface. Older cabinets can contain similar-looking plugs with very different wiring. Establish the interface type first.

Before separating the old module and cable, photograph the jumpers and cable terminations. Record which side supplies loop current in the working setup. That gives you a dependable starting point when testing a replacement.

Do not condemn the CPU simply because communication has stopped. First check loop current and transmit/receive direction. Cable continuity alone is not a complete check when the current-supplying side has not been identified.

Matching the rate is only part of the job. Compare data bits, parity, stop bits and protocol on both devices. Record an existing setting before changing it so the original setup can be restored.

For a used module, do not settle for data travelling in only one direction. Test transmit and receive separately, then together. An occasional readable character is not proof of a stable link.

Leave a working link's polarity jumpers alone until you understand their purpose. Compare the existing settings with the partner device's requirements first. Preserve a known configuration while investigating the fault.

OtomasyonAVM resources and PDFs

Start with About Siemens S5 PLC, S5 interface modules and S5 communication modules.

The OtomasyonAVM Siemens S5 PDF archive collects our available documents. For this part's wiring and jumper settings, use §12.7.3, TTY Module, in the English CPU 945 manual linked below.

Related topics

+ 6ES5 752-0LA52: the CPU 945 PG interface option.

+ 6ES5 752-0LA62: the CPU 945 SINEC L1 option.

+ 6ES5 945-7UA13: CPU 945 processor.

+ S5 cables and connectors: physical connection components.

Browse SIMATIC S5

S5 interface modules · S5 communication modules · SIMATIC S5 systems · Used Siemens equipment

Siemens and external references

+ Siemens S5-115U CPU 945 Manual – 6ES5 998-3UF21, Edition 06, English: §12.7.3, pp. 12-108–12-112 for TTY connections; Figure 12.34 for pins; Figure 12.35 for jumpers; §12.7.6, p. 12-120 for specifications.

+ Siemens ST 50 – SIMATIC S5, 1998, archived copy of the English manufacturer catalogue: p. 3/24, CPU 945 and 6ES5 752-0LA12 ordering information.