6ES5 318-3UA11
Siemens 6ES5 318-3UA11 — IM 318-3 Expansion Interface Module
Siemens 6ES5 318-3UA11 is the IM 318-3 serial interface module for SIMATIC S5 expansion units. It exchanges remote I/O data with the central-side IM 308 — 6ES5 308-3UA12. Selectable rates are 31.25 / 62.5 / 187.5 / 375 kbit/s; the system supports distances of up to 3000 metres under the applicable cable and baud-rate conditions.
This S5 interface module fits EU 183U, EU 185U and EU 186U expansion units. An adapter casing is required for ER 701-2 and ER 701-3. Identify the exact mounting rack, such as ER 701-2LA12, and check the IM 306 equipment required in the relevant ER 701 arrangements.
Communication and addressing
Transmission uses an asynchronous, half-duplex serial party line. Siemens describes the floating electrical interface as similar to EIA RS-485. This does not by itself establish Modbus or PROFIBUS compatibility. Match the communications hardware to the installed IM 308/318 system.
The S2 switches select baud rate and address area. Supported areas are P, Q, IM3 and IM4; page addressing uses Qn, Qn+1, Qn+2 and Qn+3. The specified address capacity is 255 bytes in P and with page addressing, and 256 bytes in the other areas. Check digital input, digital output and suitable analog module addresses against the PLC program.
Supply, cable and termination
The IM 318 manual specifies a typical consumption of 0.3 A from the internal 5 V supply. PS 931-7LB12 and PS 931-7LB13 power supplies must not be used. Check the complete S5 power supply number before selecting equipment.
Use a shielded, twisted-pair connecting cable with 0.5–1.5 mm² stranded conductors. Each line originating at the IM 308 requires 120 Ω / 0.25 W termination at its end. Do not assume that 3000 m applies at every baud rate; check the permitted length for the selected cable and rate in the IM 308 system documentation.
Distinction from other IM 318 models
318-3UA11 is the expansion-rack-side model. The 6ES5 318-8MA12 used for ET 100U and the 6ES5 318-8MB11 used in an ET 200 arrangement are separate products. Match the complete order number and central-side interface when replacing a module.
Troubleshooting
The module has a green ON indicator, a red FAULT indicator and a RESET switch. During PLC troubleshooting, check supply, baud rate, address selection, cable and termination in sequence. Also inspect grounding, shield connections and potential sources of electromagnetic interference. An LED condition alone does not prove that the board has failed.
Editor’s note
Start by checking the matching IM 308. On an older Siemens S5 system, the removed board’s number may only tell half the story. Recording the central-side interface as well makes replacement selection much easier.
Before removal, photograph the S2 switch positions. There is little benefit in trying to reconstruct baud-rate and address settings from memory later. One clear photograph can save a long commissioning session.
Do not select the highest rate simply because the system is described as supporting three kilometres. Consider the cable, route and rate-specific limits together. Reliable operation of an existing line matters more than the highest available setting.
Back up the program and parameters before replacement, and record the RAM/EPROM memory arrangement. Before using RESET during testing, check its effect on the running application in the manual.
For a used module, ask which IM 308 and expansion rack were used for testing. Request clear photographs of the label, switches and front connector. A test exchanging actual input and output data is more informative than a power-up check alone.
OtomasyonAVM resources and PDFs
+ S5 interface modules · S5 mounting racks
Related topics
+ 6ES5 308-3UA12 — central-side IM 308
+ 6ES5 306-7LA11 — IM 306 rack interface
+ 6ES5 318-8MA12 — different model for ET 100U
+ 6ES5 318-8MB11 — different ET 200 arrangement
Browse SIMATIC S5
Siemens and external references
+ Siemens IM 318-3UA11 manual — English; section 3.3: settings, section 4.1: specifications
+ Siemens S5-135U/155U system manual — English; p. 2-5: IM 308/318 pairing and expansion arrangement