6ES5 314-3UA11

Siemens 6ES5 314-3UA11 – IM 314 Distributed Expansion Interface Module

6ES5 314-3UA11 is the IM 314 interface module connecting an expansion unit to the central controller in S5-115U, S5-135U and S5-155U systems. This Siemens SIMATIC S5 model is installed in the expansion rack and belongs to the S5 interface module range for distributed I/O connections.

An IM 304, 6ES5 304-3UB11, is installed at the central controller, with a 721-series cable providing the link. Using the specified S5 connecting cables, the total length from the controller to the last expansion unit must remain within 600 m per run. One IM 304 supports two runs, each with up to four expansion units.

Supply and principal specifications

The module uses the internal 5 V supply, drawing a maximum of 1.0 A. Maximum power loss is 5 W and approximate weight is 0.3 kg. Include this load in the S5 power supply calculation. Protection is IP20 and the operating range is 0 to +55 °C; also check the rack arrangement and cooling conditions.

Expansion units and supported module arrangements

The IM 304/IM 314 link is used with EU 183U, EU 185U, ER 701-2 and ER 701-3 arrangements. Digital inputs, digital outputs and analog modules require a suitable rack configuration. The EU 185U arrangement can also accommodate communication processors and intelligent modules under the relevant system requirements.

A terminator is required at the end

The last IM 314 on each run requires a 6ES5 760-1AA11 terminator. A missing terminator, broken cable or loss of expansion-unit power can cause a FAULT indication. Check the complete connection before deciding that the interface board has failed.

When selecting cables such as 6ES5 721-0BB60 and 6ES5 721-0BC00, review the complete code, connector condition and total run length together. The 600 m limit applies to the complete run, rather than to each individual cable section.

Adapter casing and jumper settings

Check the required 6ES5 491-0LA12 adapter casing for an S5-115U installation. ER 701-2 and ER 701-3 connections additionally require an IM 306. Set the IM 314 jumpers for the actual expansion rack.

Siemens’ manual notes that versions 04 and earlier have a different physical arrangement of J1, J2 and J3. Match both the hardware version and rack type before applying settings from a later drawing.

Addressing and model identification

The S1 switch selects the I/O address area. Addresses already used in the central unit must not be duplicated in the expansion unit. Record the existing SIMATIC S5 system’s address allocation and switch settings before replacement.

The IM 314R, 6ES5 314-3UR11, is a separate model for switched expansion connections in redundant systems. The IM 324R, 6ES5 324-3UR11, provides the central-controller coupling link. Keep these functions distinct when selecting a 314-3UA11.

Used-module inspection and functional testing

Inspect the label, version, jumpers and connectors when assessing a used interface module. Test actual I/O access using a suitable IM 304, cable and terminator. Include grounding and cable shielding in the inspection; applying power alone provides limited evidence of functionality.

Editor’s note

Start by identifying where the board belongs. The IM 304 works at the central controller, while this IM 314 works at the expansion unit. Similar front plates can be misleading, so check the label and role together.

A fault light deserves a few checks before a replacement. Is the terminator fitted, is the expansion rack powered, and are both cable ends sound? A missing connector can send a perfectly good board to the repair bench.

Photograph the old jumper settings. Then read the hardware version and compare it with the correct drawing. The physical jumper arrangement can change within the same order code, so take a moment before copying it.

Measure the run from beginning to end. If another rack has been added, include the original cable sections too. Short individual sections can still add up to a run beyond the permitted length.

Include actual inputs and outputs in the test. A cleared fault lamp is a useful start; correct reads and writes provide better evidence. Record the rack, cables and settings so the next maintenance visit starts with useful information.

OtomasyonAVM resources and PDFs

+ Shared SIMATIC S5 manuals and PDF archive

+ S5 interface modules and model pages

Related topics

+ IM 304 central-unit interface

+ IM 314 bus terminator

+ S5 cables and connectors

Browse SIMATIC S5

+ Back to S5 interface modules

+ SIMATIC S5 system pages

+ Siemens S5 PLC main page

+ Used Siemens products and models

Siemens and external references

+ Siemens S5-135U/155U, C79000-G8576-C199-07 – sections 7.3/7.4, connections, jumpers and specifications (English)

+ Siemens S5-115U, 6ES5 998-0UF23 – IM 304/IM 314 connections and adapter requirements (English)

+ Siemens 6ES5 314-3UA11 data sheet – 28 April 2018 (English, external archive)