Siemens 6ES5 777-0BC00 — SINEC L1 BT 777-0 Bus Terminal

Siemens 6ES5 777-0BC00 is a BT 777-0 bus terminal for connecting SIMATIC S5 stations to SINEC L1. This order number specifies a 2 m PLC connection cable and a bus segment distance of up to 2.5 km with suitable cable. In a S5 communication arrangement, it converts the SIMATIC S5 station’s 20 mA TTY signals to RS-485 bus signals.

SINEC L1 is an industrial communication system operating at 9,600 bit/s, with one master and up to 30 slaves. A CP 530-3LA12, or another CP 530 suitable for the controller, coordinates master communication; the CP 530-7LA11 is a block-type member of this family. The terminal provides the physical link between a station and the bus.

PLC connection and system compatibility

The station cable has a 15-pin D-sub connector; the bus connects through screw terminals. Select the Siemens S5 controller and interface together. Direct SINEC L1 slave connection on the S5-100U is documented for CPU 102 and higher; this capability does not extend to CPU 100.

Distinguishing cable length from segment distance

The 2 m specification describes the supplied cable between the terminal and PLC. The 2.5 km specification concerns the bus segment under the manufacturer’s cable conditions. Keep these separate when selecting S5 cables and PLC connection cables. The bus cable type and electrical characteristics form part of the distance assessment.

The SINEC L1 trunk uses four-core shielded cable. When a station is bypassed, the cable distance between the remaining operating terminals can increase. After maintenance, assess the resulting path rather than just the distance between neighbouring cabinets.

Bus terminal assignments

On the left-hand side, 1A/2A is the receive pair and 3A/4A the transmit pair. On the right-hand side, 1B/2B is the transmit pair and 3B/4B the receive pair. 0A and 0B are shield terminals. Follow the Siemens diagram inside the cover for pair assignment and polarity.

Check grounding and cabinet potential differences on long runs. Siemens limits the ground potential difference between adjacent stations to 5 V for the 777-0B.00 family. Include shielding and reference potentials when reviewing the S5 supply arrangement.

Power supply: an important S5-90U distinction

The BT 777 technical table specifies a 5 V supply and 0.3 A consumption. For external power, C is +5 V and D is 0 V. Select the power supply accordingly; do not apply 24 V to C/D.

For S5 controllers, the Siemens system manual requires an external 5 V DC supply for the 0BC00 on an S5-90U, specifying 5.0–5.3 V / 0.3 A for this connection. The terminal’s external supply must also switch off when the S5-90U loses power. On the S5-95U, the PG port supplies the BT 777. Establish the supply arrangement for the actual CPU.

Addressing and commissioning

The terminal does not receive channel addresses like a digital input module. With processors such as the CP 530-3LA11, check network configuration, station numbers and the polling list. Data exchange at the PLC CPU follows the relevant controller’s programming and send/receive mailbox arrangement.

During troubleshooting, check the physical cable first, then power and station settings. Changing the program before correcting a loose terminal or an incorrectly assigned pair can obscure the original fault.

Differences between related order numbers

The 6ES5 777-0BB00 has a 1 m station cable in the same 2.5 km class; the 0BC00 has a 2 m cable. The 6ES5 777-0BC01 data sheet additionally specifies break recognition. The 6ES5 777-1BC00 belongs to the 4 km segment class. Compare suffixes, supply requirements and line characteristics before replacement.

Editor’s Note

Treat the cable as part of a used PLC accessory. Inspect the D-sub pins, cable entry and any repairs before buying. A clean S5 accessory can still have an intermittent conductor fault hidden inside its cable.

For an S5-90U installation, settle the supply arrangement first. Missing external 5 V can make a working 0BC00 appear faulty. Check both normal operation and whether terminal power switches off when the PLC loses power.

Photograph and label the conductors before disconnecting them. Transmit and receive directions differ between the left and right sides; keep the cover diagram beside you. Randomly swapping conductors can destroy a useful record of the original installation.

Power on a bench alone does not establish correct operation. Test actual data exchange with suitable SINEC L1 stations and check for interruption when the cable is moved gently. Include a planned station power-off test to assess the remaining network path.

When replacing the 0BC00 with another suffix, compare more than the connector. Cable length, segment capability and CPU-specific power requirements must all suit the installation. On an older network, a clear record of labels and connections often saves more time than the first component swap.

OtomasyonAVM resources and PDFs

Browse our S5 communication modules and S5 cable connections pages for related hardware.

Shared PDF archive for S5 systems and communication — Check document scope and language when choosing a manual. The system and SINEC L1 documents used here are in English; exact manufacturer document links are below.

Related topics

+ CP 530-3LA12 communication processor

+ 6ES5 777-0BB00 — 1 m station cable

+ 6ES5 777-0BC01 — break recognition

+ 6ES5 777-1BC00 — 4 km segment class

Browse SIMATIC S5

+ S5 accessories

+ S5 communication modules

+ SIMATIC S5

+ Siemens second-hand equipment

Siemens and external references

+ Siemens 6ES5777-0BC00 Data Sheet — 27.09.2019, English

+ SINEC L1 / CP 530 Manual — GWA 4NEB 811 0545-02d, English

+ S5-90U/S5-95U System Manual — §14.1, English

+ S5-100U System Manual — Chapter 13, English

+ Siemens 6ES5777-0BC01 Data Sheet — comparison, English