6ES5 560-8AA11
Siemens 6ES5 560-8AA11 ICM 560 Individual Control Module
Siemens 6ES5 560-8AA11 is the ICM 560 individual control module in the SIMATIC S5 range. Siemens’ ICM 560 communications documentation allocates four input bytes and four output bytes. When selecting this S5 supporting component, check its complete identification against the existing plant configuration.
The ICM 560 operates on a distributed serial connection through the 6ES5 308-3UA12 IM 308. When checking data exchange with the SIMATIC S5 CPU, match command and feedback addresses to the electrical documentation. Do not interpret the four-byte communications area as a physical terminal count.
IM 308 connection and installation compatibility
Record the complete order number of the central interface module. For a different suffix, such as the 6ES5 308-3UB11, establish from its own documentation whether the existing connections and configuration can be retained. Do not select replacement communications hardware from the shared 308 designation alone.
Record the route, shield connections and termination of cables and connectors before dismantling. Check the power supply separately from the communications link. Inspect the route between the S5 rack and field devices for added cables, loose connections and previous repairs.
COM ET 100 configuration
Siemens’ COM ET 100 manual requires a separate form for each ICM, with the identifier “2AX” in the configuration field and the other configuration fields left blank. Define the I/O area and starting addresses for the project. During PLC programming maintenance, compare these records with the existing application.
The ICM connection configuration is read from the EPROM on the IM 308. Preserve the existing files and labels before changing S5 memory modules or their configuration contents. Replacing the ICM does not automatically correct the central interface’s configuration.
Understanding the four-byte address allocation
Example: If the project assigns input start address 128 and output start address 160, the allocated ranges are 128–131 for inputs and 160–163 for outputs. This illustrates address allocation only; verify the actual starting addresses and available area against the CPU and plant configuration.
Whatever PLC programming language is used, record the byte and bit associated with each command in the Ladder or FBD logic. Avoid trial writes until the function of the data bits is understood. Inspect their use in the existing program and the feedback returned by the device first.
Diagnostics and field checks
The IM 308 diagnostics arrangement uses the diagnostic byte associated with the ICM number. F0 concerns an inaccessible device or transmission fault. Record the result, then check the supply, connector and cable continuity in sequence. A communications error alone does not establish that the ICM is faulty.
Where the installation also contains digital input, digital output and combined I/O modules, distinguish the ICM data area from their addresses. Check analog module allocations for overlaps as well. These checks do not establish the ICM’s physical channel count or electrical signal range.
For an older Siemens S5 system, assess a used unit with a known suitable central interface and documented configuration. State its identification, physical condition, included connection parts and tested functions in the quotation. Do not borrow supply, output-current, channel-count or pin specifications from another board without matching 8AA11 documentation.
Editor’s note
Start with the identification label and plant records. Write down the ICM number and assigned addresses before removing the original unit. Recovering that information afterwards can turn a straightforward replacement into a longer investigation.
If the replacement does not communicate, compare the central IM 308 identification, configuration files and installed memory contents before blaming the device. Missing configuration can prevent an otherwise sound unit from working.
A four-byte allocation is not a terminal wiring diagram. A similar-looking connector is insufficient justification for using another S5 board’s cable. Trace the cable and identify its connections from the actual installation drawings.
Record whether the fault affects one device or several on the same link. Where several devices are affected, inspect the shared supply and cable route as well. Establish the fault pattern before replacing boards.
A useful acceptance test goes beyond an illuminated indicator. Check command transmission, expected feedback and connection stability. Record the central interface, addresses and test performed so the result can be understood later.
OtomasyonAVM resources and PDFs
+ 6ES5 560-8AA11 product and information page and Siemens S5 models.
+ OtomasyonAVM shared SIMATIC S5 PDF archive. The Siemens documents below explain the ICM connection and configuration context.
Related topics
+ 6ES5 308-3UA12, S5 interface modules and S5 connection cables.
+ PLC programming, S5 memory modules and about Siemens S5 PLC.
Browse SIMATIC S5
S5 supporting modules | S5 communications | Siemens S5 models | Siemens second-hand homepage
Siemens and external references
+ Siemens 308-3UA12 Expansion Unit Interface Module Manual, English. EWA 4NEB 812 6051-02b, Edition 04; ICM connection, data exchange and diagnostics in Section 4.3.
+ Siemens COM ET 100 Communications Software Manual, English. GWA 4NEB 812 6025-02; Section A.4.1 covers ICM 560 configuration.
Document scope: These references describe the ICM 560 system connection. The dedicated manual 6ES5 998-0KC11 referenced by the IM 308 manual was not retrieved; these documents are not presented as the electrical wiring sheet for the exact 8AA11 version.