6ES5 552-3UA21

Siemens 6ES5 552-3UA21 — CP 552 process diagnostic processor, 768 KB

Siemens 6ES5 552-3UA21 is a CP 552 process diagnostic processor with 768 KB of memory for Siemens S5. It compares actual process states from the SIMATIC S5 program with configured expected conditions and generates error messages. Within the range of S5 communications and supporting processors, its role is to assist with locating process faults.

It helps investigate an incomplete movement or a missing expected sensor signal. Diagnostic results depend on the configured data matching the running program and actual field wiring.

Monitored signals and COM 552 software

The CP 552 monitors binary inputs, outputs and flags. Match the addresses of digital inputs, digital outputs and combined I/O groups to the diagnostic operands. It does not directly monitor analog values, timers or counters. Faults involving analog modules require an appropriate additional investigation.

Diagnostic data prepared with COM 552 / DIAGNOSIS work together with standard function and handling blocks in the CPU. Whether the PLC programming project is examined in LAD or FBD/CSF, use the addresses of the running program. Review the corresponding diagnostic data whenever that program changes.

CPU compatibility, rack and power

The manufacturer manual describes use with S5-115U, S5-135U, S5-150U, S5-155U and EG 185. For S5-135U it specifies an R processor or CPU 928; CPU 921 is excluded. Check the exact number and revision of a controller such as the CPU 928A, together with its required blocks.

The CP 552-2 uses two boards. Its documented requirements include 5 V, maximum 3.2 A and approximately 40 mm front-panel width. Account for these when checking the S5 rack layout and power-supply capacity. For S5-115U, verify adapter-casing and cooling requirements against the installed system’s documentation.

Programmer connection and local display

The front IF1 port uses AS 511 over a serial TTY current loop. Use the appropriate S5 programming cable; connector appearance does not establish RS-232 compatibility. The VIDEO connection supports message display on a suitable local monochrome monitor.

When checking the interface arrangement, distinguish direct IF1 access from programmer access through the system bus. The manual separately describes bus access for S5-135U with a 923C coordinator and for EG 185. Do not extend this arrangement to every S5 installation.

SSNR, DIP switches and addressing

CPU communication uses two 1 KB pages in dual-port RAM. Set the interface number with DIP switch J56: the first page has an even SSNR and the second receives the next odd number. For example, selecting 6 assigns pages 6 and 7. Check that neither number is already assigned elsewhere in the system.

With the factory switch settings all OFF, the pages use 0 and 1. The documented J55 base address is F400H, and Siemens instructs users to retain that setting. Keep the physical slot number distinct from SSNR and compare the hardware setting with the CPU block parameters.

Memory use and fault assessment

The full 768 KB is not available for diagnostic definitions. The manual specifies approximately 695 KB for CP 552-2 setpoint data; symbols and message texts reduce the available space. Back up configuration files separately. Do not treat an S5 memory card alone as a complete diagnostic-system backup.

A lit STOP LED does not by itself establish a failed processor. Check synchronization, missing or incorrectly parameterized blocks and startup conditions. During PLC debugging, record CPU status, CP indicators and messages together. Do not assume a different processor such as the CP 525 is a direct replacement because of a similar suffix or front panel.

Editor’s note

When buying a used Siemens CP, check the complete number and completeness of the two-board assembly. Request clear photographs of the memory submodule, board connections and retainers. Assess an incomplete assembly separately from a complete unit.

Powering up and seeing LEDs is an initial check. The meaningful demonstration is CPU communication, use of the correct diagnostic data and recognition of a known process condition. Record which CPU and software were used.

Before removing the original unit, photograph J56, the assigned SSNR and every jumper position. A working replacement can fail to communicate with unsuitable factory settings. Transfer settings only after comparing them with the existing project.

Do not condemn the board solely because STOP is lit. Check the CPU blocks, parameters and synchronization first. If IF1 is inaccessible, verify the cable on a known-good setup as well.

Do not create a diagnostic test by randomly disconnecting a sensor on a running machine. Use a test bench or planned shutdown and a controlled scenario with a known result. Afterwards, verify normal connections and operation.

For legacy S5 maintenance, the project backup is as valuable as the processor. Keep the CP configuration, message texts and CPU program at matching revisions. Finding the same hardware number may not complete the repair if these files are missing.

OtomasyonAVM resources and PDFs

+ Siemens S5 PDF archive: system and module documents. The manufacturer’s COM 552 / CP 552 manual is linked under external references below.

+ 6ES5 552-3UA21 model page and used Siemens S5 models: the model and related system hardware.

Related topics

+ 6ES5 928-3UA21 CPU 928A and 6ES5 923-3UC11 coordinator: controller and system-access arrangements.

+ 6ES5 525-3UA21 CP 525 and S5 interface modules: compare distinct processor and interface roles.

+ S5 cable types and PLC debugging: connection and diagnostic work.

Browse SIMATIC S5

Siemens S5 · S5 communications modules · S5 expansion products · Second-hand Siemens products

Siemens and external references

+ Siemens COM 552 / CP 552 Manual — 6ES5 998-3SE22, Release 05, Volume 1, English. CP 552 Instructions: Chapters 1–3 cover functions, memory, interfaces and specifications; Chapter 6 covers SSNR and DIP settings.

+ Siemens S5-115U Manual — 6ES5 998-0UF23, English. Section 15.2.10 covers CP use and power-supply loading.

+ UL component record in the Siemens archive — E120869. Lists CP 552-3UA11 and CP 552-3UA21 order numbers.