Siemens 6ES5 513-3LA11 is a magnetic bubble memory module for SIMATIC S5-150K and S5-150S. Siemens catalogue ST 53 specifies 64 × 2¹⁰ words. With 16-bit words, this corresponds to 131,072 bytes or 128 KiB, commonly described as 128 KB in product listings. It belongs to the S5 memory equipment used for data storage in the Siemens S5 PLC family.

Magnetic bubble memory retains stored data when power is removed. The catalogue describes this module for storing data such as texts and process images in data block form. Within the Siemens S5 architecture, distinguish its role from the CPU's working memory; 128 KB of storage does not automatically provide the same amount of additional program working memory.

Capacity and distinction from 3LB11

513-3LA11 provides 64 K words / 128 KiB. The same catalogue separately lists 513-3LB11 at 128 K words / 256 KiB. Check the LA/LB letters when ordering. A capacity difference alone does not establish that the existing application can move to another board without changes.

Do not confuse the 513's storage function with other memory types such as 372-series EPROM, 373-series EPROM, 375-series EPROM, a 374-series RAM card or 374-series Flash EPROM. These are examples of different memory technologies and system applications, rather than direct replacement candidates for the 513.

Data transfer and application software

The module contains a microprocessor and buffer memory for data exchange alongside the magnetic bubble memory. Siemens specifies 10–90 ms to transfer a 128-byte data block. This is not the PLC scan time or the time required to transfer the complete memory contents.

The catalogue lists standard function block packages 6ES5 831-6BA11 for S5-150K and 6ES5 831-6CA11 for S5-150S. Before replacement, document the blocks, data blocks and read/write calls used in the PLC program. Working hardware cannot compensate for missing application blocks.

Supported systems and catalogue slot positions

ST 53 identifies this compact 513 version for S5-150K and S5-150S. Listed positions are ZG 150-3KB52: 143 or 151; ZG 150-3KB62: 81 or 91; ZG 150S: 145 or 193; and ZEG 150S: 135. These are catalogue slot numbers, not data or I/O addresses.

The catalogue permits only one 513 memory module per programmable controller. When arranging S5 additional modules and S5 communication modules, check the complete rack order number and existing configuration. Multiple-module or address information from a different 513-M manual must not be assigned automatically to 3LA11.

Supply current and weight

The Siemens ST 53 technical table lists 2.0 A consumption from the 5 V rail and an approximate weight of 0.55 kg for the 513 memory module. Include this load in the rack power budget. This information is not a wiring diagram for applying an external supply to arbitrary points on the board.

Addressing, programming connections and other storage arrangements

Use the documentation for the exact 3LA11 hardware and the existing STEP 5 project to establish addressing and transfer arrangements. S5 interface modules, the PG 511 programming interface and S5 cable connections serve separate functions. Connecting a programmer to the CPU does not establish that all data stored in the 513 has been backed up automatically.

The 6ES5 341-3AA11 external memory interface provides a different memory connection arrangement. The later CP 581 basic board with silicon disk and CP 581 hard disk storage module are also not mechanical or software equivalents of the 513. A migration must address data structures, application calls and system compatibility together.

Editor's note

Do not assume that this board's contents are simply another copy of the PLC program. Machine texts, process information or application-specific tables may be stored here. Establish which data blocks are written to the module and how they are read back before replacing it.

Where possible, obtain a backup from the working installation through reading first. Clearing the memory or running an unfamiliar write call as a test can destroy valuable data on healthy hardware. Use a separate spare or an area confirmed to be unused for controlled testing.

If reading fails, investigate more than the memory device. During PLC troubleshooting, check function blocks, call parameters, rack placement and supply conditions together. An application requesting the wrong data and hardware failing to read are different faults.

Take the catalogue's 2.0 A figure seriously. An ageing rack power supply, contact resistance or contaminated connectors can cause intermittent behaviour. Photograph the installation and jumper positions before removal; disconnect system power and follow ESD precautions during maintenance.

For a used purchase, obtain a clear view of the 513-3LA11 label. Record the LA/LB distinction, capacity and hardware version. An illuminated indicator alone is insufficient; seek successful reading, controlled writing and subsequent reading in a suitable test arrangement.

With used Siemens equipment, a functioning board and data appropriate to your machine are separate requirements. Agree on backups, test coverage and the state of the stored data in writing. Preserve the existing contents before changing hardware.

OtomasyonAVM resources and PDFs

Start with About Siemens S5 PLC, S5 memory cards, S5 additional modules and S5 interface modules.

This page uses the exact-order-number and technical tables in Siemens catalogue ST 53, 1985, listed below. Address and jumper details for different 513-M versions have not been assigned to this model.

Related topics

+ 6ES5 341-3AA11: external memory interface with a different role from the 513.

+ 6ES5 372-0AA51: EPROM memory submodule.

+ 6ES5 374-2AH21: RAM memory card using a different storage technology.

+ 6ES5 374-2FH21: Flash EPROM card; system compatibility requires separate assessment.

Browse related equipment

Siemens S5 PLC · S5 CPU family · Memory cards · Additional modules · Cables · Used Siemens equipment

Siemens and external references

+ Siemens SIMATIC S5, S5-130 and S5-150 – Catalogue ST 53, 1985: third-party archive copy of the manufacturer's catalogue. PDF page 120 / printed page 9/2 identifies the complete order number, word capacity and S5-150K/S compatibility. PDF page 39 / printed page 3/11 covers application, slots, transfer time and the single-module limit. PDF page 88 / printed page 8/2 lists 5 V rail consumption and weight.