6ES5 488-3LA11
Siemens 6ES5 488-3LA11 — S5-105R 220 V AC Digital I/O Module
The Siemens 6ES5 488-3LA11 is a combined digital module for SIMATIC S5-105R, providing five 220 V AC inputs and three 220 V AC, 0.5 A outputs. Within the SIMATIC S5 range, 6ES5 488-3LA11 combines AC field-signal acquisition and AC load control on one digital input/output module.
It belongs to the S5-105R arrangement associated with CPUs such as 6ES5 905-3RB11 and 6ES5 905-3RB21. When selecting Siemens S5 PLC equipment, verify the 105R chassis, CPU and field voltage together. The 220 V AC signal level differs from a 24 V DC sensor connection.
Inputs: voltage thresholds and delay
The five digital inputs have a nominal rating of 220 V AC. Siemens specifies 0–70 V AC for signal “0” and 170–264 V AC for signal “1”. Typical input current at “1” is 15 mA; typical turn-on and turn-off delays are 8 ms and 22 ms respectively. Do not rely on an intermediate voltage producing a defined logic state.
Outputs: current, load type and leakage
The three digital outputs use a 220 V AC, 50 Hz load supply, with a permitted range of 176–264 V AC. The specified operating current is 50 mA–0.5 A per output, and the maximum lamp load is 50 W. Check coil inrush current when selecting a contactor.
Load type matters when calculating current. A simple resistance calculation using Ohm's law does not establish the initial pickup current of an AC contactor coil. Use a suitable control device and load arrangement rather than connecting a motor power circuit directly to this output.
Siemens specifies a maximum off-state residual current of 5 mA and describes interruption when load current reaches zero. Assess the circuit accordingly rather than expecting dry-contact behaviour. If using an SSR or relay interface, check its input current, pickup and release behaviour, and response to residual current together.
Switching limits: the stated maxima are 10 Hz for resistive loads, 8 Hz for lamps and 2 Hz for inductive loads at rated load. These limits depend on load type; one frequency rating cannot be applied to every load.
Shared fuse and field connections
One fuse protects all three outputs. Select the fuse according to the manufacturer's specified type rather than deriving its rating from the 0.5 A channel limit alone. The purpose of the fuse and the module's output-current limit are different considerations when assessing fuse capacity.
The specified front connector for the five-input/three-output arrangement is 6ES5 766-0LA11. When checking cables and connectors, inspect the latch, loose connections and signs of heating. Siemens requires the load and input-signal voltages for each module to come from the same phase. Input and output circuits are galvanically isolated from the control system.
Installation and dimensions: S5-105R-A provides four I/O module positions and S5-105R-B provides eight. Check the chassis and slot arrangement accordingly. Module dimensions are 133 × 41 × 185 mm (height × width × depth), with a weight of approximately 0.3 kg.
Addressing and differences between variants
On the 105R, the module-position number forms part of the I/O address. Siemens' example I0.5 identifies input 5 of the module in position 0. If moving a module, compare program addresses with field connections; do not transfer the addressing method of another S5 family without checking the 105R documentation.
Within the same system, 488-3LA21 is the 115 V AC version and 488-3LA31 is the 24 V DC version. 487-3LA11 provides eight inputs and eight outputs at 24 V DC. Compare complete order codes, channel counts and voltages when assessing S5 expansion modules. These variants must not be treated as interchangeable with unchanged field wiring.
Editor's Note
Start by checking the 3LA11 suffix on the label. This board uses 220 V AC input signals; an input failing to respond to a 24 V PNP sensor does not establish a board fault. The 3LA21 and 3LA31 variants have different voltage ratings.
A voltage reading on an output that is commanded off does not, by itself, prove a shorted output. The manual permits up to 5 mA of residual current. Have a qualified person assess it with a suitable test load and reference rather than relying on an unloaded meter reading.
If all three outputs fail together, check the shared fuse and load supply. Establish why the fuse opened before replacing it. A faulty coil or damaged field cable can subject a replacement board to the same fault.
The 0.5 A maximum is only one part of load selection: Siemens starts the operating range at 50 mA. For a small LED indicator or electronic input, check minimum load, leakage current and release behaviour together.
For a used module, request individual tests of all five inputs and all three outputs. Include discoloured terminals, cracks and a loose connector latch in the assessment. Photograph slot positions and cable labels before removal, and isolate both PLC and field supplies before working on the connections.
OtomasyonAVM resources and PDF documentation
Use About Siemens S5 PLC for system distinctions and the Siemens S5 PDF archive for documentation. For this module, refer to sections 2.4, 4.3 and 5.5 of S5-105R Operating Instructions, GWA 4NEB 810 0220-02.
Related topics
S5 combined digital I/O modules · S5 digital inputs · S5 digital outputs · S5 cables and connectors
Navigation: 6ES5 488-3LA11 model page | SIMATIC S5 main page | Siemens S5 PLC models | Used Siemens equipment
Siemens documents and external references
Siemens S5-105R Operating Instructions — English PDF: printed pages 2.4–2.5 for wiring and addressing, 4.1 for troubleshooting, 5.7–5.8 for exact-code specifications, and 6.1 for the front connector.
Siemens S5-105R Betriebsanleitung — German PDF: comparison of the 488-3LA11, 3LA21 and 3LA31 versions.