6ES5 440-8MA22

Siemens 6ES5 440-8MA22 – 4-Channel 24 V DC / 2 A Digital Output Module

6ES5 440-8MA22 is a Siemens SIMATIC S5 module with 4 transistor outputs, a nominal load voltage of 24 V DC and a rating of 2 A per channel. This member of the S5 digital output range is non-isolated, with a permitted load supply range of 20–30 V DC. The combined current of all four outputs must not exceed 4 A.

Channel current and total loading

The permitted on-state current is 5 mA–2 A. A 2 A channel rating does not allow all four outputs to supply 8 A simultaneously. Keep the 4 A total limit when assessing the power supply, and include pickup current for control relays and other coil loads.

Common reference and field wiring

The outputs share an M reference and have no galvanic isolation. Arrange grounding and load returns according to the system drawing. Incorrect common wiring, loose terminals or voltage drop in field cables can resemble an output fault.

Short-circuit protection and red fault LED

The module provides electronic short-circuit protection. The manual states that the output switches on automatically when the short circuit has been removed. The red fault LED can indicate a short circuit or missing L+ load voltage; investigate both conditions before judging the card.

CPU error diagnostics

In the S5-100U manual’s English address notation, I X.0 reports faults such as an output-channel short circuit or missing load voltage. I X.1 reports a defective module, such as a shorted output transistor. X is the module’s byte address; “1” indicates a fault. These are diagnostic bits read through the digital input process image; they do not add two physical inputs to the card. Account for them in the input/output addressing arrangement.

These diagnostics cannot be read with CPU 100 version 8MA01. For example, X=5 gives I 5.0 and I 5.1 in the manual’s notation; verify the actual address from the installation. This explanation applies to S5-100U diagnostics. Check the relevant documentation for another CPU or station.

Switching and operating conditions

Maximum switching frequency is 100 Hz for resistive loads and 2 Hz for inductive loads. The lamp-load limit is 10 W, and maximum off-state residual current is 1 mA. Internal inductive turn-off voltage limitation is −15 V.

The S5-100U manual permits ambient temperatures of 0–60 °C for horizontal installation and 0–40 °C for vertical installation. Maximum unshielded cable length is 100 m, and approximate module weight is 200 g.

Bus unit and system compatibility

The module plugs into a suitable bus unit; 6ES5 700-8MA11 is a bus module from this family. Catalog ST 50 lists the card in the S5-90U, S5-95U and S5-100U range. For an S5-90U CPU or another SIMATIC S5 system, check CPU expansion requirements and the existing mechanical coding.

Differences from similar codes

The 6ES5 440-8MA12 is a four-output 0.5 A model. The 6ES5 441-8MA11 is a separate model with 8 outputs. Check channel count, protection and load ratings for the complete order number.

The 6ES5 451-8MA11 is a different, isolated output card. The 6ES5 453-8MA11 provides low-current 5–24 V DC outputs, while the 6ES5 452-8MR11 uses relay contacts. Compare load type and common-terminal arrangements before replacement.

Used-module inspection and replacement preparation

When testing a used output module, check all four channels in sequence with suitable loads. Monitor total current, L+ supply and fault indication together. Back up the program and memory unit before replacement.

Record the existing S5 system’s I/O addresses and wiring. For used Siemens modules, state label details, included bus/connection parts, physical condition and completed tests for the individual item.

Editor’s note

Check the total before calling this an 8 A card. Each channel is rated at 2 A, but the whole card is limited to 4 A. List the individual loads and add them up before assessing the supply and wiring.

Measure L+ when the red LED comes on. A 24 V reading without load may not tell the whole story. Check it under load before setting aside a sound card as faulty.

Allow for automatic recovery after a short circuit. This model can switch the output on again once the short has cleared. Isolate the circuit appropriately before working on the load and tracing the cause.

Check the CPU version if diagnostics are missing. CPU 100 8MA01 does not support this readout. Missing I X.0 and I X.1 information alone does not establish an output-card fault.

Make the final check on all four channels. Save the program, use suitable test loads and record each result. A short record makes the card’s condition much easier to assess later.

OtomasyonAVM resources and PDFs

+ Shared SIMATIC S5 manuals and PDF archive

+ S5 digital output modules and model pages

Related topics

+ 6ES5 440-8MA12 – 4-channel 0.5 A output module

+ 6ES5 441-8MA11 – 8-channel output module

+ 6ES5 700-8MA11 bus module

Browse SIMATIC S5

+ Back to S5 digital output modules

+ SIMATIC S5 system pages

+ Siemens S5 PLC main page

+ Used Siemens products and models

Siemens and external references

+ Siemens S5-100U manual – 440-8MA22 specifications and wiring, 14-27 (English)

+ Siemens S5-100U – diagnostic bits and CPU 100 8MA01 exception, 6-6 (English)

+ Siemens ST 50, 1998 – 440-8MA22, 4 A total and 50% loading, 2/31 (English)