6ES5 440-8MA12

Siemens 6ES5 440-8MA12 – 4-Channel 24 V DC / 0.5 A Digital Output Module

Siemens 6ES5 440-8MA12 is a SIMATIC S5 digital output module with four 24 V DC transistor outputs rated at 0.5 A each. It provides field outputs in S5-100U installations using CPU 100, CPU 102 or CPU 103. The outputs are not galvanically isolated, and the combined permissible load current is 2 A.

Within a SIMATIC S5 control system, the module switches suitable DC relay coils, small valves and indicator loads in response to program commands. It switches the positive side of the load; the return connects to M. When selecting Siemens automation spares, check the complete 8MA12 suffix and the load current rather than relying on the 440 family number alone.

Load supply and output ratings

The nominal load supply is 24 V DC, with an allowable range of 20–30 V DC including ripple. The specified current range is 5–500 mA per channel, with a maximum lamp load of 5 W. Off-state residual current can reach 0.5 mA; allow for this when connecting sensitive LED loads or electronic inputs.

Consider 6ES5 440-8MA22 separately where a higher current rating is required, or 6ES5 441-8MA11 when reviewing channel density. 6ES5 450-8MB11 and 6ES5 451-8MA11 are further output options with different electrical characteristics. Their wiring and protection requirements must be checked independently.

Maximum switching frequency is 100 Hz for resistive loads and 2 Hz for inductive loads. This module should therefore not be treated as a high-speed pulse output. When comparing the relay-output 6ES5 452-8MR11 with the transistor-output 6ES5 453-8MA11, review load voltage, current and switching polarity as separate selection criteria.

Terminal wiring and bus unit

Supply connections are terminal 1 = L+ and terminal 2 = M. The four loads connect to terminal pairs 3–4, 5–6, 7–8 and 9–10. The odd-numbered terminal is the switched output, and the adjacent even-numbered terminal provides the M return, allowing two-wire load connections. Check terminal functions before transferring wiring between similar-looking S5 digital input/output modules.

The module mounts on a suitable S5 bus unit with its terminal block. Inspect the installed 6ES5 700-8MA11, 6ES5 700-8MA21 or 6ES5 700-8MA22 arrangement, including screw/crimp termination, mechanical seating and contact condition. When servicing S5 compact-system modules, check the backplane connection and the field supply as separate parts of the circuit.

Addressing and fault feedback

In an S5-100U, the slot determines the digital output byte address. A module in slot 5 therefore uses Q 5.0–Q 5.3 in English STEP 5 notation. The additional .4–.7 front markings relate to ET 100U addressing; they do not indicate eight physical outputs. Combined modules such as 6ES5 482-8MA13 have their own addressing rules.

The red F LED can indicate a short circuit or missing load supply. In the S5-100U diagnostic input byte, I X.0 reports a short-circuit/fuse or load-supply fault, while I X.1 reports a module fault such as a shorted output transistor. X is the slot byte address and 1 means a fault is present. This software feedback is not supported by CPU 100 version 8MA01. These diagnostic bits are distinct from normal sensor inputs on a module such as 6ES5 431-8MA11.

System compatibility and operating conditions

The exact order number appears in both the S5-100U and S5-90U/S5-95U system manuals. For an S5-90U 6ES5 090-8MA01 or S5-95U 6ES5 095-8MA03 installation, follow the applicable CPU expansion and addressing rules. Permissible ambient temperature is 0–60 °C with horizontal mounting or 0–40 °C with vertical mounting. Approximate module weight is 200 g.

Editor’s Note

Start with a clear view of the 8MA12 label. Another 440 module may fit the same space while carrying a different rating. Before removing the old card, photograph its label, terminal layout and cable numbers together. Those few pictures can save a great deal of work later.

Do not accept a lit channel LED as proof that the output is healthy. Use a suitable test load and check all four channels separately, including current and switching behaviour relative to M. An unloaded voltage reading does not establish that a channel can carry its load.

If the F LED is on, measure the supply at terminals 1 and 2 under load before condemning the module. A loose terminal, broken M return or shorted valve coil can stop the machine just as effectively. Separate the field circuit from the card step by step.

Short-circuit protection can automatically restore an output once the short circuit disappears. Keep that in mind while disconnecting test wiring, and isolate loads that could cause movement. A larger fuse is not a remedy for a coil that exceeds the channel rating.

When buying used, inspect the mounting latch, backplane contacts and heat marks around the terminals. A faintly glowing LED load may also reflect the specified off-state residual current. Ask for evidence of all four channels operating under load with the stated CPU, rather than accepting a general claim that the card works.

OtomasyonAVM resources and PDFs

Browse the SIMATIC S5 overview and digital module group for system context. Use the OtomasyonAVM S5 PDF archive to locate manuals. The exact module specification appears on printed page 14-26 of the S5-100U manual and 15-24 of the S5-90U/S5-95U manual. Both documents are in English.

Related topics

+ 440-8MA22 output module · 441-8MA11 output module · 431-8MA11 digital input module · 700-8MA11 bus unit

Browse SIMATIC S5

+ S5 digital input/output modules · S5 compact-system modules · SIMATIC S5 · Siemens S5 PLC · Second-hand Siemens overview

Siemens and external references

+ Siemens S5-100U System Manual, EWA 4NEB 812 6120-02b, English — printed page 14-26: specifications; 3-14–3-15: wiring; 6-4: addressing; 6-6: diagnostics.

+ Siemens S5-90U/S5-95U System Manual, EWA 4NEB 812 6115-02b, English — printed page 15-23: fault feedback; 15-24: exact-order-number specifications.