6ES5 430-4UA12

Siemens 6ES5 430-4UA12 — 32-Channel 24 V DC Isolated Digital Input Module

Siemens 6ES5 430-4UA12 is a 32-channel, 24 V DC isolated digital input module in the SIMATIC S5 U peripheral range. It is used in suitable U-type hardware arrangements for S5-135U, S5-150U and S5-155U systems. All 32 inputs share one galvanically isolated group. This compact digital input module transfers machine status signals to the S5 system.

Typical signal sources include industrial sensors, inductive sensors, photoelectric sensors and limit switches. The manufacturer’s contact diagram applies positive 24 V to an input. For electronic sensors, assess the output circuit, common return and off-state leakage current together.

Input levels and timing

For positive input voltages, 0–7 V represents logic 0 and 13–33 V represents logic 1. Do not use the 7–13 V transition region as a defined logic level. Rated input current is 7 mA. Include wiring voltage drop when selecting the field power supply and sensor output.

Maximum input frequency is 100 Hz. The specified delay is typically 3 ms (1.4–5 ms), with a typical response time of 6 ms (4–10 ms). Include PLC scan timing when assessing short pulses. During supply troubleshooting, measure the S5 power supply side and the field circuit separately.

Front connector, field supply and enable circuit

The 42-pin front connection uses pin 1 for F+, pin 2 for F−, pin 3 for L+ and pin 21 for L−. Field supply is 24 V DC, permitted range 20–30 V DC. Check pin numbering, contact retention and connector locking when inspecting S5 cables and connectors and the rack.

Input terminals run through 4–11, 13–20, 25–32 and 34–41. On the 4UA12, fitting the X20 jumper activates the external F enable input. This is the factory setting, so the enable voltage must also be supplied. Check the jumper position against the machine’s wiring design.

For a U-type expansion arrangement, inspect the connection chain through the interface modules and expansion modules as well. Verify the replacement module’s rack arrangement, wiring and address setting against the existing machine project.

Addressing and fault isolation

The 32 inputs occupy four input bytes. For example, a starting byte of 16 in the PLC project gives input bits I16.0–I19.7; this is an addressing example. When checking PLC input operation, make sure the module’s address switch matches the program.

Green channel indicators help identify the physical input state. Compare the voltage from the relay contact, the channel indicator and the program bit in that order. Within a Siemens S5 installation, a common supply or enable fault needs different checks from a single faulty sensor.

Comparison with similar order numbers

Check 6ES5 430-4UA13, 6ES5 430-4UA14 and 6ES5 420-4UA12 individually when selecting a spare. Compare the complete suffix, isolation arrangement, enable connections and manufacturer’s revision notes before replacement. For a used module, request clear front/rear label photographs and a channel test record.

Editor’s note

Start with the complete label. Record the 4UA12 suffix, hardware version and X20 jumper position with clear photographs. Keep a record of the removed module’s settings before fitting a spare.

Check the common circuit before condemning the board. If several inputs misbehave together, measure the field supply, L− return and F+/F− voltage at the connector. A correct voltage at the power supply does not rule out a loose connection farther along the circuit.

Investigate a sudden all-ones pattern carefully. Compare the actual sensors, enable circuit and CPU QVZ information. Input bits alone are not enough to complete an S5 fault diagnosis.

Test all 32 channels on a used module. With a suitable current-limited test arrangement, apply 0/24 V to each input in turn and record both the green indicator and the corresponding PLC bit. One working channel does not establish the condition of the whole board.

Include the machine wiring in the final check. Sensor leakage, voltage drop on long runs and loose front contacts can produce misleading symptoms even after a bench test passes. Put the machine outputs into a safe state before the final connection and verify the recorded input addresses.

OtomasyonAVM resources and PDFs

+ About Siemens S5 PLC — systems and module selection

+ S5 digital input modules — model pages

+ Our general SIMATIC S5 PDF archive — existing manual and file index.

Related topics

S5 digital output modules · S5 analog modules · Relay and contact operation

Browse SIMATIC S5

S5 digital input modules · SIMATIC S5 · Siemens S5 PLC · Used Siemens equipment

Siemens and external references

+ Siemens U Periphery — 6ES5 998-0PC22, English: §5.2, printed pp. 35–36 / PDF pp. 238–239; exact 4UA12 specifications and wiring diagram.

+ Siemens PGC 302 edition II — C79000-G5376-C523-2, English: SIMATIC modules section, printed p. 15 / PDF p. 54; exact 430-4UA12 order number, input indicators and cable lengths.

+ Siemens 6ES5430-4UA12 product record — exact order number and compact U, 32-input, 24 V DC isolated module description.