6ES5 498-1AA61
6ES5 498-1AA61 Siemens SIMATIC S5 ±5 V Measuring Range Submodule
The Siemens 6ES5 498-1AA61 is a measuring range submodule for 460 and 465 series analogue input modules in SIMATIC S5 systems. With the host module set to the correct mode, it gives four input channels a nominal voltage range of −5 V to +5 V. Siemens lists it for 460-4 and 465-4 modules used in S5-135U/155U systems and for specified 460-7 and 465-7 modules in the S5-115U/H/F family.
The submodule acts as a voltage divider, bringing the signal at the analogue input down to the level required by the host measuring circuit. A 0–5 V signal uses the positive half of the range. With a 0–10 V source, the portion above 5 V exceeds the nominal measuring range. Set the PLC scaling to suit the actual transmitter signal.
Which channels does it configure on each host?
The 460-4UA11, 460-4UA12 and 460-4UA13 are eight-input modules. Their two range slots serve channels 0–3 and channels 4–7. If the first group measures ±5 V, fit the 1AA61 in the slot for channels 0–3. Check the other group’s range submodule and the shared operating mode separately.
For voltage or current measurement, the 465-4UA11, 465-4UA12 and 465-4UA13 have 16 inputs arranged in four groups of four. One 1AA61 sets the range for the group it is fitted to. In particular, with the non-isolated 465-4UA12, check the manual for the permissible potential difference between the signal source and module references.
The Siemens ST 50 catalogue also lists the 1AA61 as a range option for the 460-7LA13 for S5-115U/H/F and the 465-7LA13 for S5-115U/H. Use the wiring diagram and switch table for the full order number of the installed host.
How do you set the host for ±5 V?
In the 460-4UA13 range table, the 1AA61’s nominal ±5 V range appears under 500 mV/mA/Pt100 mode with gain ×1. The mode name refers to the host measuring circuit. With the 1AA61 voltage divider fitted, the nominal range at the terminals is ±5 V. The 465-4UA12 table also lists ±5 V under 500 mV/mA/Pt100 mode.
Wire the signal pair to M+ and M− as shown in the host diagram. The S5-115U documentation lists the 24-terminal screw front connector and the 46-terminal screw front connector as separate parts. Verify channel terminals, signal reference and field cable shield termination against the installed module’s wiring diagram.
The 460-4UA13 technical table gives an input resistance of 50 kΩ and a nominal measured range of ±2048 units for ±5 V. Extract the measurement from the input word using the selected data format, then scale the value to engineering units.
Which signals use the other 498 variants?
For voltage measurement, the 498-1AA21 is the ±1 V option and the 498-1AA31 is the ±10 V option. The 498-1AA11 serves mV or Pt100 measurement according to the host module and its settings.
For current inputs, Siemens lists the 498-1AA41 for nominal ±20 mA, the 498-1AA51 for two-wire 4–20 mA transmitters and the 498-1AA71 for four-wire 4–20 mA transmitters. Match the replacement to the signal type on the transmitter label and the wiring arrangement.
Editor’s note
Before replacement, photograph the 6ES5 498-1AA61 label, the full host order number and the channel group served by the submodule.
If the reading is half the expected value or off by a multiple, check the mode selector, gain setting where fitted, and PLC scaling together. Another channel group on the same module may use a different range.
If the reading is near zero or unstable, measure the transmitter output at M+ and M−. Then check the potential between the transmitter and module references against the host’s limit.
Use the host range table to interpret wire-break diagnostics. On the 460-4UA13, for example, Siemens lists detection for specific mV and Pt100 ranges. On a ±5 V channel, start by measuring the voltage.
After replacement, apply two known voltage points under controlled test conditions. Compare the raw input value and displayed engineering value separately to verify both the hardware range and software scaling.
OtomasyonAVM resources and PDFs
Siemens SIMATIC S5 PLC guide · SIMATIC S5 analogue input and output modules
OtomasyonAVM SIMATIC S5 PDF archive
Related topics
Compatible analogue input modules · Eight-input 460-4UA13 · Sixteen-input 465-4UA12
Other voltage ranges · ±1 V 498-1AA21 · ±10 V 498-1AA31
Browse SIMATIC S5
Used Siemens SIMATIC S5 equipment › SIMATIC S5 › S5 analogue modules
Siemens documentation and external references
Siemens SIMATIC S5-135U/155U system manual · Section 9.3, 460 range cards and gain table
Siemens SIMATIC S5 U Periphery manual · Chapter 5, range tables for earlier 460 and 465 modules
Siemens ST 50 SIMATIC S5 catalogue · S5-115U/H/F analogue modules and 498 range submodule ordering table