6ES5 955-3NC41
Siemens 6ES5 955-3NC41 S5 Rack Power Supply
The Siemens SIMATIC 6ES5 955-3NC41 is an isolated rack power supply for the S5-135U/155U central controller and selected EU 183 and EU 185 expansion units in the SIMATIC S5 family. It takes 24 V DC (18–33 V) and supplies the rack with 5.1 V DC at 18 A. The auxiliary outputs are rated at 15 V DC at 0.5 A and 24 V DC at 1 A.
In the cabinet, the unit converts the incoming 24 V DC feed into the supply rails used by the S5 rack. The 6ES5 955-3NF41 also takes 24 V DC and is rated at 40 A on its main rail. The 6ES5 955-3LC41 belongs to the 18 A class and takes 120/230 V AC. Check the input type first, then match the main output rating.
Which racks take the 3NC41?
Siemens manual C79000-B8576-C199-03 pairs this unit with the 6ES5 188-3UA31 central controller and the 6ES5 183-3UA22 EU 183 and 6ES5 185-3UA22 EU 185 expansion units. If a power fault affects only the S5 expansion hardware, check its supply separately from the central rack.
The later Siemens manual specifies the 6ES5 955-3NC42 for the 6ES5 188-3UA32 central controller. Both supplies are in the 18 A class. Siemens specifies 18–33 V DC for the 3NC41 and 19.2–33 V DC for the 3NC42. The 6ES5 188-3UA11 and 6ES5 188-3UA21 are listed with the 3LC41 and 3LF41, respectively. Read the full rack part number before ordering a replacement.
Input current and auxiliary outputs
The unit draws 9.5 A at 24 V DC and rated load. Siemens specifies a peak inrush current of 100 A for 100 µs. Take both values into account when checking the upstream PLC power supply.
The 5.1 V and 15 V rails are regulated. Siemens specifies ±0.5% rated voltage tolerance and overload current limiting for the 5.1 V rail. On the auxiliary 24 V output, X2 and the front output terminals share a combined 1 A limit. Use the machine schematic to trace those points and identify the field supply circuits around the S5 digital inputs and S5 digital outputs.
What do the front-panel indicators tell you?
The 5 V o.k., 15 V o.k. and 24 V o.k. indicators correspond to separate output rails. Voltage low refers to the external 24 V load-voltage monitor. If it comes on, trace the S5 wiring and connectors against the machine schematic to identify the supply it monitors.
If only a remote I/O group is down, record the expansion rack’s supply indicators separately from the status of the S5 interface modules. If several S5 analog modules lose their readings at once, check the shared rack supply before tracing individual channels.
Editor’s note
Read both nameplates. Confirm the 3NC41 suffix on the supply and look for 188-3UA31, 183-3UA22 or 185-3UA22 on the rack. The 6ES5 183-3UA13 is also an EU 183, and Siemens lists it with the AC-input 3LC41.
Check the input when the fault occurs. If the unit drops out on startup, monitor the incoming 24 V as it starts. An unloaded reading can miss a brief dip.
Read the front test sockets correctly. Siemens uses 3 V = 18 A as the scale for measuring current on the 5 V rail. Use a compatible S5 rack for bench testing. Siemens specifies a 0.5 A minimum load on the 5.1 V rail.
Record the fan indicators before resetting them. Note which fan LED is lit and whether Fan Alarm is active. If the warning returns, check the airflow path as well as the fans.
Check the backup arrangement before removal. Record any MB low indication and any external battery connection. Siemens describes battery backup for the central controller and EU 185. Identify the fitted S5 memory card and back up the STEP 5 project and the required machine data.
OtomasyonAVM resources and PDFs
Browse the S5 power supplies and S5 racks and chassis to compare part numbers. For a family overview, see About Siemens S5 PLCs.
The OtomasyonAVM S5 manual and PDF archive is the site’s S5 document index. For CPU 922 installations, the 6ES5 998-1UL13 S5-135U / CPU 922 manual set page describes the German documentation. For the 3NC41 specifications, see edition 03 of the Siemens system manual linked below.
Related topics
+ 6ES5 955-3NC42, 24 V DC input, 18 A class
+ 6ES5 955-3NF41 and 6ES5 955-3NF42, 24 V DC input, 40 A class
+ 6ES5 955-3LC41 and 6ES5 955-3LC42, AC input, 18 A class
Browse the S5 range
Used Siemens S5 PLCs · SIMATIC S5 · S5 power supplies
Selling this power supply? Email a nameplate photo, quantity, working or fault condition and asking price to otomasyonavm@gmail.com.
External references
+ Siemens SIMATIC S5-135U/155U System Manual, C79000-B8576-C199-03 (EN). See pages 4-57–4-59 for the specifications and page 4-21 for the rack compatibility table.
+ Siemens SIMATIC S5-135U/155U System Manual, C79000-G8576-C199-07 (EN PDF). Covers the 3NC42 and 188-3UA32 for comparison.