6ES7 153-2AB00-0XB0

6ES7 153-2AB00-0XB0 – Siemens ET 200M IM 153-2 FO

Series: SIMATIC ET 200M
Category: Fiber-optic PROFIBUS DP interface module

Purpose and position in the station

6ES7 153-2AB00-0XB0 is an IM 153-2 FO interface connecting a Siemens ET 200M station to fiber-optic PROFIBUS DP. It exchanges data between S7-300 modules and the supervising PLC. It is not a CPU that independently executes a user program.

Module capacity and basic specifications

The station accepts up to 8 compatible S7-300 modules. Select digital input, digital output and analog modules by their full order numbers and the station configuration. The rated supply is 24 V DC, with a permitted range of 20.4–28.8 V DC. Housing dimensions are 40 × 125 × 117 mm.

Applications using 4–20 mA or 0–10 V require a suitable analog module. The optical connection on the IM 153-2 FO is a network interface, not a measurement input for direct sensor wiring.

Fiber-optic communication and connections

PROFIBUS DP communication supports a maximum of 12 Mbit/s. Adjacent devices are linked by duplex fiber. Under Siemens’ specified cable and connection conditions, the distance is up to 50 m with plastic fiber or 300 m with PCF fiber. These limits apply to one link between adjacent devices. Check the cable, optical connectors and partner device together.

An optical connection does not make this a PROFINET device. When planning a replacement or network conversion, consider the protocol differences described under ET 200 PROFIBUS and PROFINET interfaces. Losing power to an intermediate device in an optical line can also interrupt access to downstream stations.

Differences between 2AB00 and later versions

Siemens’ ET 200M compatibility table does not show support for redundancy, DPV1, SYNC/FREEZE or isochronous operation in the 2AB00 column. Specifications for 6ES7 153-2AB01-0XB0 or 6ES7 153-2BB00-0XB0 must therefore not be applied to this module. Its supported input time-stamping function must also be distinguished from the 1 ms capability of later versions.

Commissioning and fault checks

Before replacement, back up the project and record the PROFIBUS address, module order and CPU / DP master configuration. Check that the STEP 7 hardware catalogue entry or GSD file matches the interface version. If communication fails, investigate the supply, optical connections, address and project-to-hardware match separately.

For power interruptions, assess neighbouring devices along the optical line as well as the interface itself. Size any uninterruptible power supply for the complete station load. Replacing I/O modules during operation requires the appropriate active backplane bus and configuration; a station assembled with ordinary bus connectors must not be assumed to provide the same capability.

Editor’s Note

Start replacement selection with the full 2AB00 order code and the existing optical connection. Choosing solely by the “IM 153-2” label can lead to a different physical interface or feature set. Review the original label, hardware version, station photograph and saved project together. A module fitting mechanically does not establish that it will run the existing application in the same way.

Manuals and PDF documents

See Siemens ET 200 manuals and PDF documents for connection, commissioning and version information. Technical references: Siemens ET 200M Operating Instructions, 12/2008, EWA-4NEB780600602-08, section 10.3 and appendix A.2; and the SIMATIC NET PROFIBUS Network Manual for optical network design. Use the 2AB00 column when interpreting the general manual’s feature tables.