6ES7 153-1AA03-0XB0

Siemens 6ES7 153-1AA03-0XB0 – ET 200M IM 153-1

The 6ES7 153-1AA03-0XB0 is an IM 153-1 DP ST interface module for ET 200M stations in the Siemens ET 200 family. It connects remote S7-300 I/O to the main PLC over PROFIBUS. The controller runs the machine program, while the IM 153-1 handles communication and I/O data exchange for the remote station.

Station capacity

The interface accepts up to 8 compatible S7-300 modules, with an address space of 128 input bytes and 128 output bytes. These figures describe I/O data capacity, not program memory or the number of physical channels.

When combining digital inputs, digital outputs and analog modules, check both their data requirements and backplane current consumption. For function and special-purpose modules, a mechanical fit alone does not establish support by the IM 153-1. The ET 200 overview explains the differences between station families.

Power supply and PROFIBUS connection

The supply rating is 24 V DC, with a permitted range of 20.4–28.8 V DC, maximum input current of 350 mA and typical power loss of 3 W. The 5 V DC backplane supply, rated up to 1 A, powers module electronics; field loads have separate supply requirements.

PROFIBUS DP uses RS 485 through a 9-pin D-sub socket. The maximum rate is 12 Mbit/s, with automatic baud-rate detection. Front switches select an address from 1 to 125. This model has no PROFINET or direct Ethernet connection.

STEP 7, GSD files and hardware revisions

Configuration is available through STEP 7, COM PROFIBUS or engineering tools using a suitable GSD file. Siemens identifies SIEM801D.GSD and, for DPV1, SI01801D.GSG. The configured interface, module sequence and parameters must match the installed hardware.

DPV1 mode is supported from hardware revision E05 of the 1AA03 model. The enhanced 64-byte diagnostic frame is listed from E02. Here, E denotes the module revision: identical order numbers do not guarantee identical functionality across all production revisions.

Differences from IM 153-2 and module replacement

The IM 153-1 does not support interface redundancy, input time stamping or CiR system expansion in RUN. Applications requiring these functions need a suitable IM 153-2 version and station arrangement. The different ET 200 communication interfaces have distinct capabilities.

However, I/O modules can be replaced during operation with suitable active bus modules and configuration. This does not mean removing the IM 153-1 itself under power, or adding new modules through CiR. Include the connection and bus modules and relevant ET 200 accessories when planning maintenance.

Fault checks and installation

ON indicates supply voltage, BF a PROFIBUS bus fault and SF a group error. Record whether each LED is steady or flashing, then read the station diagnostics. Check supply dips, the station address, cabling, termination and module-order mismatches before concluding that the interface has failed.

Dimensions are 40 × 125 × 117 mm, in width, height and depth order. The operating temperature range is 0 to +60 °C horizontally and 0 to +40 °C vertically. Assess the actual cabinet temperature together with the mounting orientation.

Editor's Note: Photograph the E revision as well as the full order number before selecting a spare. A unit earlier than E05 should not be treated as equivalent in a project that requires DPV1. For I/O replacement during operation, check the active bus arrangement and removal/insertion interrupt setting: the manual specifies different behaviour for E01 and E02 onward when this interrupt is disabled.

Manuals and technical references

For wiring, configuration and diagnostics, use the Siemens ET 200 manuals and PDF documents page. Technical references: Siemens 6ES7153-1AA03-0XB0 Data Sheet, 20 January 2021; ET 200M Operating Instructions, 04/2022, EWA-4NEB7806006-09, particularly the IM 153-1 features and compatibility section A.1.

Related topics

S7-300 CPU modules · HMI and operator panels · SCADA systems. When investigating an operator-panel communication alarm, compare the main PLC status with the remote I/O station diagnostics.

Navigation: Siemens automation · SIMATIC S7 · Siemens ET 200 · OtomasyonAVM home