6ES7 142-6BH00-0AB0

Siemens main menu › SIMATIC S7 family › ET 200 › Digital output modules

6ES7 142-6BH00-0AB0 — Siemens ET 200eco PN, 16 DO 24 V DC / 1.3 A Digital Output Device

6ES7 142-6BH00-0AB0 is an ET 200eco PN, 16 DO 24 V DC / 1.3 A digital output device in the Siemens SIMATIC product family. It controls field loads directly on the machine within ET 200 distributed I/O systems. Each of its eight M12 output sockets carries two channels, providing 16 outputs in total.

Five checks before selection

1. Series and network compatibility: Match the complete order number and device family when selecting ET 200 digital output modules. This model uses PROFINET IO and includes an integrated switch with two M12 network ports. When comparing PROFIBUS and PROFINET communication options, do not interpret the catalogue wording “SIMATIC DP” as indicating a PROFIBUS connection. Check the device name, IP settings and output addresses in the Siemens S7 control system project.

2. Channel and group current: Each channel supports up to 1.3 A, while the outputs in each eight-channel supply group have a combined limit of 3.9 A. The 4 A infeed limit specified for 1L+ and 2L+ is different from the total output current limit. When reviewing ET 200 power supply options, use the 24 V DC nominal rating and 20.4–28.8 V DC permissible range. Calculate power distribution to field loads for simultaneous operation and pickup currents; do not parallel outputs to increase current capacity.

3. M12 sockets and channel numbering: X1–X4 carry DQ0–DQ3 and DQ8–DQ11 in the 1L+ group; X5–X8 carry DQ4–DQ7 and DQ12–DQ15 in the 2L+ group. At each socket, pin 4 carries the first output and pin 2 the second. For example, X1 provides DQ0 and DQ8. Select M12 field connection components that bring out both channels. A cable carrying only one output pin cannot provide access to the second channel.

4. Diagnostics and stopping behaviour: Wire break and short circuit to M can be monitored per channel, while missing 1L+/2L+ supply is monitored per group. Enable these diagnostics in the project parameters; the 2015 manual lists them as disabled by default. CPU/master STOP behaviour can be set to shut down the outputs or retain the last value. Test the machine’s stopping sequence and use digital input feedback signals to verify the actual actuator state where required.

5. Installation and application limits: The housing measures 60 × 175 × 49 mm. Use suitable connections and seal unused sockets with protective caps to maintain IP67 protection. This is a standard digital output device and does not support PROFIsafe. For an application requiring ET 200 safety modules, matching output count and current rating alone does not establish suitability.

Editor’s note

Do not base the load calculation on socket count: Four 1 A loads operating simultaneously in one supply group draw 4 A, exceeding the 3.9 A group limit. Keeping each load below the 1.3 A channel rating is not enough. Record the channel number, M12 socket and supply group together in the wiring schedule.

PDF and technical documentation

Visit the Siemens ET 200 PDF and user manual library. For this model, consult the 6ES7142-6BH00-0AB0 datasheet and ET 200eco PN, 01/2015, A5E01250250-AH. Section 9.2.5, pages 135–139, covers the device; page 141 lists its parameters; page 47 shows the M12 wiring arrangement. Page numbers may differ between manual editions.

Related topics

Terminal bases • Connection modules • Digital inputs • Digital outputs • Power distribution • Additional modules

Otomasyon AVM • Siemens guide

Siemens main menu  |  SIMATIC S7 family  |  ET 200 module categories  |  ET 200 PDF archive