6ES7 142-6BF00-0AB0
Siemens 6ES7142-6BF00-0AB0 ET 200eco PN 8-Channel Digital Output Module
6ES7142-6BF00-0AB0 is an 8-channel, 24 V DC digital output field module in the SIMATIC ET 200eco PN family. Each output supports up to 1.3 A. Part of the Siemens industrial automation range, it connects suitable DC valves, relays and other loads directly on the machine under PROFINET control.
Within the Siemens ET 200 distributed I/O family, this model provides eight independent channels through four M12 output sockets. Each socket carries two separate outputs. In industrial automation applications, selecting cables and splitters by socket count alone can leave some of the available channels inaccessible.
Channel current and group current limits
The 1.3 A channel rating does not mean that all eight outputs can operate at that current simultaneously. In all mounting positions, each four-channel group has a combined limit of 3.9 A up to 55 °C and 2.6 A at 60 °C. For PLC-based control applications, add the simultaneous loads within each group; four 1 A loads in the same group, for example, exceed the 3.9 A limit.
Five checks before selection and commissioning
1. M12 output connections: On sockets X1–X4, pin 4 carries DQ0–DQ3 respectively, while pin 2 carries DQ4–DQ7. When reviewing ET 200 system architecture and connections, check that the selected Y splitter routes these channels correctly to separate actuators. The two output pins in a socket are not duplicate connections for the same signal.
2. Supply groups: DQ0, DQ1, DQ4 and DQ5 on X1 and X2 belong to 1L+; DQ2, DQ3, DQ6 and DQ7 on X3 and X4 belong to 2L+. Calculate group loads using this arrangement rather than consecutive channel numbers. If one group fails to operate, measure its supply at the module under load.
3. PROFINET connection: The module has two M12 D-coded network ports connected through an integrated switch for 100 Mbit/s PROFINET communication. In SIMATIC S7 control systems, compare the device name, network settings and configured hardware definition. Before replacing equipment in an installation using Siemens PLC and I/O products, save the working project and record the device description file in use.
4. Diagnostics and stop behavior: Load supply loss, short-circuit and wire-break detection with the output off depend on diagnostic parameter settings. Also check the configured output response to CPU STOP. A command displayed on HMI operator panels does not by itself confirm actuator movement; examine channel LEDs, enabled diagnostics and field feedback together.
5. Field protection: Achieving IP65/IP67 protection requires correctly fitted, suitable connectors and appropriate sealing caps on unused round sockets. Include cable types, splitter wiring and unused-port condition in the commissioning record. Inspect connection points regularly, particularly in areas exposed to washdown or moisture.
PDF manuals and connection information
Find documentation resources on the Siemens ET 200 PDF manuals page. The ET 200eco PN Operating Instructions, 08/2016 cover this model in Section 9.2.1, with the socket assignment in Table 9-4. Share the label photograph, cable and splitter details, and channel loads through Siemens product technical enquiries to provide the information needed for review.
Editor's note: A cable that uses only the pin 4 output leaves the second channel on pin 2 inaccessible. If half of the outputs appear not to work, check cable conductors and the Y splitter pin assignment before concluding that the module is faulty.
Related topics and Siemens navigation
Product families
Siemens main menu | Siemens PLC products | SIMATIC S7
ET 200 resources
ET 200 products | ET 200 system overview | ET 200 PDF manuals
Control and assistance
HMI operator panels | SCADA systems | Siemens product enquiries