6ES7 142-3BH00-0XA0

Siemens main menu › SIMATIC S7 family › ET 200 › Digital output modules

6ES7 142-3BH00-0XA0 — Siemens ET 200eco BM142, 16 DO 24 V DC / 0.5 A Digital Output Module

6ES7 142-3BH00-0XA0 is an ET 200eco BM142 basic module in the Siemens SIMATIC product family. It provides 16 digital outputs at 24 V DC, with a nominal rating of 0.5 A per channel. Within the ET 200 distributed I/O family, it controls machine-mounted solenoid valves, DC contactors and indicator lights. It belongs to the PROFIBUS DP version of ET 200eco.

Five checks before selection

1. Network and project compatibility: The device communicates over PROFIBUS DP at up to 12 Mbit/s. When comparing PROFIBUS and PROFINET options, do not treat ET 200eco PN devices as equivalent to this order number. Match the GSD configuration, PROFIBUS address and output addresses to the existing station in the Siemens S7 control system project. Similar-looking sockets do not establish network compatibility.

2. Nominal current and total load: Among ET 200 digital output modules, this model is selected by its 0.5 A per-channel nominal rating. The Siemens manual specifies a 4 A total output current limit in all mounting positions up to 55 °C. Calculate power distribution to field loads using the loads that will operate simultaneously. Operating all sixteen outputs at 0.5 A would exceed the total limit. Do not parallel outputs to increase current capacity.

3. Separate connection block: The BM142 requires a separately ordered connection block. Options include 6ES7194-3AA00-0AA0 ECOFAST and 6ES7194-3AA00-0BA0 M12 / 7/8-inch. Select ET 200 connection modules to suit the installed network and power cables. When reviewing terminal and connection block options, check which components accompany the basic module; the BM142 order number alone does not establish that a complete connection assembly is included.

4. Supply and M12 pin assignment: 1L+ supplies the electronics and 2L+ supplies the output loads; both use nominal 24 V DC. Check both circuits separately when arranging the ET 200 power supply system. Across the eight M12 output sockets, pin 4 carries channels 0–7 and pin 2 carries channels 8–15. For example, X1 carries channels 0 and 8. Pin 3 is 2M and pin 5 is PE; pin 1 is unused. Use a correctly wired cable or Y splitter to access both channels.

5. Diagnostics and field protection: Each channel has a green status LED, and the device has a red SF group fault indicator; individual red channel fault LEDs are not provided. Diagnostic information can be read over PROFIBUS. An illuminated output LED does not prove mechanical movement; monitor digital input feedback signals where required. To achieve IP65/IP67 protection, install the connection block and connectors correctly and seal unused sockets with suitable caps.

Editor’s note

For this module, “16 outputs × 0.5 A means 8 A available” is an incorrect assumption. Sixteen loads drawing 0.3 A each require 4.8 A; every channel is below its nominal rating, yet the 4 A total limit is exceeded. Assess the load schedule together with simultaneous operation, pickup current and cable current-carrying capacity.

PDF and technical documentation

Visit the Siemens ET 200 PDF and user manual library for the documentation guide. Use the 6ES7142-3BH00-0XA0 datasheet and section 8.7 of the ET 200eco manual, 08/2014. This module is covered on pages 83–86 of the English A5E00158716-AD edition and pages 71–74 of the Turkish A5E51988150-AD edition. Also compare the connection block selection with the manual’s article-number appendix.

Related topics

Terminal bases • Connection modules • Digital inputs • Digital outputs • Power distribution • Additional modules

Otomasyon AVM • Siemens guide

Siemens main menu  |  SIMATIC S7 family  |  ET 200 module categories  |  ET 200 PDF archive