6ES7 141-6BF00-0AB0

Siemens main menu › SIMATIC S7 › SIMATIC ET 200

Siemens 6ES7 141-6BF00-0AB0 — ET 200eco PN, 8 DI 24 V DC, 4 × M12

6ES7 141-6BF00-0AB0 is the ET 200eco PN, 8 DI 24 V DC, 4 × M12 digital input block in the Siemens ET 200 distributed I/O family. It transfers signals from proximity sensors, limit switches and suitable contacts to the controller over PROFINET IO. This model in the ET 200 digital input range provides eight inputs through four M12 sockets, with two separate input signals at each socket.

Order number: 6ES7141-6BF00-0AB0
Series: SIMATIC ET 200eco PN
Inputs: 8 DI, 24 V DC
Sensor connections: 4 × M12, dual channel assignment
Communication: PROFINET IO; integrated switch, 2 × D-coded M12 network connections
Sensor supply: Four supply outputs, maximum 100 mA each
Typical input delay: 3 ms
Protection rating: IP67 with correct installation and connections
Dimensions: 30 × 200 × 49 mm

Using the compact field block

Within the ET 200 system architecture, this device combines the network connection and inputs in one housing. It is not an electronics module fitted to an ET 200S terminal base or an ET 200pro CM IO connection module. When assessing ET 200 communication options, identify this reference as a PROFINET IO device. It can serve points where sensors are grouped on a machine; allow space for cable bends and access to the sockets when planning its location.

Five checks before selection or replacement

1. Four sockets, eight inputs: At sockets X1–X4, pin 4 carries DI0–DI3 respectively, while pin 2 carries DI4–DI7. The channel pairs are therefore 0/4, 1/5, 2/6 and 3/7. When selecting ET 200 connection components, verify that splitter cables follow this assignment. Wiring that takes a signal only from pin 4 leaves the second input group unused.

2. Shared sensor supply: Each socket has a 100 mA sensor supply limit. Add the consumption of both sensors connected to the same socket. When planning ET 200 power supply components and ET 200 power distribution, distinguish this limit from the current capacity of the device's main supply path. The four sensor supply outputs listed in the data sheet are not four controllable digital outputs.

3. Sensor and signal compatibility: The inputs accept nominal 24 V DC signals. For two-wire sensors, the permitted quiescent current is 1.5 mA maximum. Also account for the typical 3 ms input delay; sensor switching speed alone is insufficient when assessing short pulses. Consider pulse duration together with the controller's data processing time.

4. Diagnostic settings: The device supports diagnostics for missing 1L+, sensor supply short circuits per channel group and wire breaks per channel. These diagnostic options are disabled by default in the manual's parameter table. Check the required options in the Siemens S7 hardware project; assess wire-break diagnostics against sensor behaviour and any unused inputs.

5. Network and physical connections: Before replacement, record the PROFINET device name, IP settings, input addresses and port connections. When selecting from the ET 200 special-function and expansion module range and accessories, also check connector coding, seals and covers for unused sockets. An IP67 housing does not maintain the same protection with an open or damaged connection.

Distinguishing similar order numbers

6ES7141-6BG00-0AB0 also has eight inputs but uses eight M12 sockets; do not assume that the existing cable arrangement is identical. 6ES7142-6BF00-0AB0 belongs to the ET 200 digital output range. When comparing products through the Siemens main menu, check both 141 / 142 and 6BF / 6BG. Input versus output function and socket arrangement matter as much as channel count.

Editor's note

An easily overlooked detail is that two inputs share one socket and its sensor supply. If two sensors stop working together, inspect their shared cable and supply as well. Recording the socket-to-channel mapping in the machine documentation can help prevent unnecessary module replacement.

Manuals and PDF documentation

Use our Siemens ET 200 PDF and user manuals page to consult the ET 200eco PN Operating Instructions. In edition A5E01250250-AH, 01/2015, section 9.1.1 covers the device and pin assignment, while section 9.1.4 covers input diagnostic parameters. Match the product data sheet to the complete reference 6ES7141-6BF00-0AB0; section numbering may differ between editions.

Related topics and Siemens navigation

Product family: Siemens main menu  |  SIMATIC S7  |  ET 200 family

Station and field devices: Digital input modules  |  Additional modules  |  PROFIBUS and PROFINET

Technical resources: About ET 200  |  Power supply modules  |  ET 200 PDF manuals