6ES7 141-4BF00-0AA0
Siemens main menu › SIMATIC S7 family › ET 200 › Digital input modules
6ES7 141-4BF00-0AA0 — Siemens ET 200pro, 8 DI 24 V DC Digital Input Module
6ES7 141-4BF00-0AA0 is an ET 200pro 8 DI 24 V DC digital input module in the Siemens SIMATIC product family. It collects on/off signals from switches, limit switches and compatible proximity sensors. Within the ET 200 distributed I/O family, it is the standard version with module-level diagnostics; distinguish it from the 6ES7141-4BF00-0AB0 High Feature model.
Six checks before selection
1. Input count and sensor type: The module provides 8 digital inputs and occupies 1 byte of input address space. When selecting ET 200 digital input modules, check the sensor output type and compatibility with 24 V DC signals. Two-wire sensors are supported with a maximum permissible off-state current of 1.5 mA. In the Siemens S7 hardware configuration, map sockets, channels and PLC addresses in one signal list.
2. Input delay: Input delay is 1.2–4.8 ms for both signal transitions and cannot be adjusted through parameters. For short-pulse counting, assess pulse duration together with the communication and PLC program cycles. Do not assume that standard digital inputs and ET 200 counter modules are interchangeable for the same task.
3. Connection module selection: The product includes the bus module; the CM IO connection module is ordered separately. Compatible options include 6ES7194-4CA00-0AA0, CM IO 4 × M12, and 6ES7194-4CB00-0AA0, CM IO 8 × M12. Select ET 200 connection modules to match the installed sensor cables. When planning ET 200 station expansion, include the required connection components alongside the electronic module in the bill of materials.
4. Eight inputs through four sockets: On CM IO 4 × M12, pin 4 of sockets X1–X4 carries DI0–DI3, while pin 2 carries DI4–DI7. For example, X1 serves DI0 and DI4. Pin 1 supplies the sensors, pin 3 is supply return 1M, and pin 5 is functional earth (FE). With CM IO 8 × M12, each socket carries one input on pin 4; pin 2 is unused. Select cables or Y splitters for the chosen CM IO arrangement.
5. Total sensor supply current: The sensor supply is rated for a maximum total current of 1 A up to 55 °C; this is not a separate allowance for each sensor. Calculate combined sensor consumption when assessing ET 200 power supply modules. Check power distribution within the station against cable losses and simultaneous sensor operation. The input channels are not galvanically isolated from one another.
6. Diagnostic coverage: A sensor supply short circuit to M is monitored at module level. Green LEDs indicate channel states, and a red SF LED indicates a group fault. Do not assume that this standard version provides the HF model’s channel-specific diagnostics. For safety functions, assess ET 200 safety modules separately; this product is a standard digital input module.
Editor’s note
Four M12 sockets do not mean that the module has only four inputs. With CM IO 4 × M12, the second group of inputs is accessed through pin 2. Cables carrying only the pin 4 signal will leave DI4–DI7 inaccessible. If four channels appear to be missing, check the connection module and cable wiring before replacing the electronic module.
PDF and technical documentation
Visit the Siemens ET 200 PDF and user manual library for the documentation guide. Use the 6ES7141-4BF00-0AA0 datasheet and section 14.1, pages 333–338, of the ET 200pro system manual, 09/2015, A5E00335544-AJ. M12 pin assignments appear on page 334; the CM IO 4 × M12 and 8 × M12 connection modules are described on pages 264 and 270 respectively.
Related topics
Terminal bases • Connection modules • Digital inputs • Digital outputs • Power distribution • Additional modules
Otomasyon AVM • Siemens guide
Siemens main menu | SIMATIC S7 family | ET 200 module categories | ET 200 PDF archive