6ES7 138-4CB11-0AB0

Siemens 6ES7 138-4CB11-0AB0 – ET 200S PM-E Power Module

Siemens 6ES7 138-4CB11-0AB0 is a PM-E DC24..48V/AC24..230V power module for SIMATIC ET 200S stations. It provides load supply distribution and monitoring for the associated electronic modules, with diagnostic functions and a replaceable fuse. This component belongs to the ET 200S platform within the Siemens ET 200 family and is part of its power module range.

What does the PM-E module do?

Electronic modules sharing a load supply form a potential group within an ET 200S station. The PM-E and its suitable TM-P terminal module provide the supply point for that group. The electronic modules to the right use this arrangement until the next supply group begins. This allows the station’s power distribution to follow the machine’s electrical design.

The digital input modules and digital output modules in each group must suit the applied voltage. The PM-E’s broad voltage specification does not mean that every connected electronic module accepts the same voltages. Clear group boundaries on the electrical drawings are particularly useful in cabinets containing several supply levels.

Supply voltage and the role of an external power supply

The product is specified for 24–48 V DC and 24–230 V AC supply applications. It distributes an externally supplied load voltage; it does not convert 230 V AC into 24 V DC. A group operating at 24 V DC therefore requires an appropriate external DC power supply.

When selecting a rail-mounted power supply, calculate the combined demand of the electronic modules, sensors and loads. Available source current and the PM-E group’s permitted current are separate design checks. Installing a larger power supply does not increase the current rating of the module group.

Current capacity and fuse protection

For the manual’s temperature limits of 30 / 40 / 60 °C, maximum group currents are respectively 10 / 9 / 7 A with DC and 8 / 7 / 5 A with AC. The module should therefore not be treated as having an unconditional 10 A rating.

The replaceable fuse is specified as 5 × 20 mm, 10 A, 250 V, fast-acting. It supplements the required external supply-circuit protection. If the fuse opens, investigate the connected loads and wiring for overloads or short circuits before replacing it.

Terminal module and wiring arrangement

The PM-E plugs into a suitable TM-P terminal module. Supply wiring connects to this base, so the electronic module and terminal base must be identified separately when ordering replacements. Examples within the ET 200 terminal module range include TM-P15S23-A0 with screw terminals and TM-P15C23-A0 with spring terminals.

Terminal selection also determines how the AUX1 potential bus continues between groups. The A0 version interrupts AUX1 from the group on its left. Where different potentials are used, check the connection modules and terminal variants against the electrical drawings. Matching the physical width alone is insufficient.

Diagnostics and AC/DC configuration

SF indicates group faults, PWR monitors load voltage and FSG indicates fuse status. The voltage type parameter selects AC or DC; DC is the default. Missing-load-voltage and blown-fuse diagnostics can be enabled in the project.

These settings help distinguish a supply problem from an individual electronic module fault. If several channels stop working together, checking their common supply group can be more informative than replacing channels individually. Review the PLC diagnostic information alongside the station’s communication configuration.

Dimensions and installation planning

The electronic module measures 15 × 81 × 52 mm (width × height × depth), with a maximum power loss of 5 W. These dimensions describe the electronic module itself. Cabinet planning must also allow for the terminal base, cable routing and maintenance access.

Clear labels for sensor supplies and output load groups can make troubleshooting easier. Cable routing and grounding should follow the installation’s electromagnetic compatibility requirements. For wiring and commissioning details, consult the relevant ET 200S documents through the Siemens ET 200 manuals and PDF documents page.

Editor’s note: When selecting a replacement, compare the complete 6ES7 138-4CB11-0AB0 order number with the installed terminal base, actual group supply voltage and configured AC/DC setting. Similar-looking PM-E modules can differ in voltage range and fuse provision. The existing wiring diagram is just as important as the product label.