6ES7 138-4CA50-0AB0
Siemens 6ES7 138-4CA50-0AB0 – ET 200S PM-E 24–48 V DC Power Module
Siemens 6ES7 138-4CA50-0AB0 is a PM-E DC24..48V power module used to monitor the load supply for electronic modules in SIMATIC ET 200S stations. It belongs to the ET 200S system within the Siemens ET200 family. In machines where distributed inputs and outputs work with a PLC, it forms part of the supply arrangement for the associated module group.
What does the PM-E module do?
The module allows an external DC supply to feed the load group through its terminal module and provides supply monitoring. It is not a standalone power supply or voltage converter. For example, it does not convert a 48 V DC input into a 24 V DC output. The cabinet's DIN rail power supply must be selected separately to suit the voltage and current requirements of the loads.
Supply selection should consider every module in the group. The PM-E's 24–48 V DC designation does not mean that every connected module can operate at 48 V. Check the permitted supply ratings of the ET200 digital input modules and digital output modules individually. This model requires a DC load supply; it does not accept AC.
Electrical ratings and current capacity
The rated load supply is 24–48 V DC, with a maximum current-carrying capacity of 10 A up to 60 °C. The module itself draws a maximum of 12 mA without load; typical power loss is 0.5 W. The 10 A rating applies to the total group supply, not to each output channel.
Reverse-polarity protection is provided; internal short-circuit protection is not. Suitable external protection is required. Select the protective device with reference to the wiring, connected loads and starting currents, rather than using the module's 10 A rating alone. Supply diagnostics do not replace short-circuit protection.
Terminal module and potential group
The PM-E plugs into a compatible TM-P terminal module. Siemens lists options including the screw-terminal TM-P15S23-A1 / 6ES7 193-4CC20-0AA0 and spring-terminal TM-P15C23-A1 / 6ES7 193-4CC30-0AA0. Compare the complete order numbers when selecting ET200 terminal blocks and reviewing the station's connection modules.
The TM-P starts a new load potential group extending to the next TM-P terminal module. AUX1 continuity depends on the terminal version; the A1 type, for example, maintains this connection to the group on its left. Adding a power module therefore does not automatically separate every auxiliary potential.
Supply diagnostics and indicators
The front indicators are green PWR and red SF. Missing load voltage can be diagnosed. The manual specifies “Diagnostics: No load voltage” as disabled by default, so its setting should be checked against the project's diagnostic requirements.
For maintenance, identifying the affected supply group is more useful than displaying only a general station fault. Depending on the application, the diagnostic information can be presented as a clear maintenance message on an HMI operator panel or within a SCADA system.
Communication and system selection
Selecting 6ES7 138-4CA50-0AB0 addresses the load supply arrangement. When reviewing the station's PROFIBUS or PROFINET connection, also identify the installed interface module. Checking the supply group and the industrial communication arrangement separately helps clarify which component is needed.
Dimensions and replacement selection
The module body measures 15 × 81 × 52 mm and weighs approximately 35 g. Cabinet planning should also allow for the terminal base and access to the wiring.
For a replacement, compare the complete 6ES7 138-4CA50-0AB0 order number on the existing label. Similar-looking PM-E modules should not be assumed to share the same supply range, protection features or hardware configuration entry. Providing the module label, terminal order number and project configuration together makes identification more reliable.
Technical documentation and related topics
For connection details and parameter information, consult the relevant ET 200S documents through the Siemens ET200 PDF manuals page. Further background is available in the Siemens ET200 overview, the sensors section and the PROFIBUS frequently asked questions.
Editor's note: The main selection point is agreement between the supply voltage accepted by the PM-E and the operating voltage of the connected electronic modules. Check the terminal base and existing supply group alongside the module's order number.
More Siemens products: Siemens products | Siemens S7 PLC | SIMATIC S7 | ET200 products