6ES7 141-1BF30-0XA0
Siemens main menu › SIMATIC S7 › SIMATIC ET 200
Siemens 6ES7 141-1BF30-0XA0 — ET 200X EM 141, 8 DI 24 V DC
6ES7 141-1BF30-0XA0 is an ET 200X EM 141 digital input expansion module in the Siemens ET 200 distributed I/O family. Its eight 24 V DC inputs bring suitable sensor and contact signals into the station. This earlier model in the ET 200 digital input range uses 5-pole M12 connections with dual channel assignment. Selection requires checking the basic module's complete reference as well as the input count.
Order number: 6ES7141-1BF30-0XA0
Series / module: SIMATIC ET 200X / EM 141
Inputs: 8 DI
Rated input voltage: 24 V DC
Signal “1” range: 13–30 V DC
Signal “0” range: −3 to +5 V DC
Input characteristic: IEC 61131 Type 2
Protection rating: IP65 in the product data sheet
Dimensions: 87 × 110 × 55 mm; module body width 60 mm
Basic module and expansion module
Within the ET 200 system architecture, the BM basic module and EM expansion module perform different tasks. This product adds inputs to an existing ET 200X station; it is not an independent networked field block. Assess ET 200 communication options through the station's basic module. Recording the BM label and module sequence alongside the EM 141 label helps prevent an incorrect combination.
Check the documented ECOFAST restriction
Siemens product information A5E00125915-05, dated 01/2005, restricts use of this module with ECOFAST basic modules 6ES7141-1BF00-0AB0, 6ES7141-1BF01-0AB0, 6ES7141-1BF40-0AB0, 6ES7143-1BF00-0AB0 and 6ES7143-1BF00-0XB0. A sensor-line short circuit can interrupt the shared 24 V supply. Resolve this dated restriction against manufacturer documentation covering the actual hardware revision before relying on the general catalogue wording “for all basic modules.”
Five checks before selection or replacement
1. Complete reference and revision: Record the installed component's 1BF30-0XA0 reference and revision markings. Do not directly apply a description for 1BF31-0XA0 or 1BF30-0XB0 to this model. Matching channel counts do not establish identical protection circuits or diagnostic capabilities.
2. M12 wiring arrangement: With dual channel assignment, the pins carried by the cable matter. When selecting ET 200 connection components and splitter cables, record the existing socket-to-sensor mapping. Do not use a pin table from another ET 200 subfamily; a connector fitting mechanically does not establish a correct electrical match.
3. Sensor electrical characteristics: The permitted quiescent current for two-wire sensors is 1.5 mA maximum, and the maximum unshielded signal cable length is 30 m. When checking ET 200 power supply components, also measure voltage at the sensor terminals. Review voltage drop, the common return connection and station fusing together when assessing ET 200 power distribution.
4. Diagnostic requirements and project: Do not assume that the 0XA0 version provides the short-circuit and wire-break functions of the channel-diagnostic 0XB0 version. Compare the selected module, input addresses and existing parameters in the Siemens S7 hardware project. If an input does not change state, examine the sensor signal, cable and supply separately; this symptom alone does not establish a failed module.
5. Mechanical condition and sealing: Inspect side connection contacts, locking parts, socket threads and seals. When reviewing the ET 200 special-function and expansion module range and accessories, also check covers on unused connections. The IP65 product description does not establish continued protection with a missing cover or damaged seal.
Input versus output in similar references
6ES7142-1BF30-0XA0 is an EM 142 output module in the ET 200 digital output range, despite its similar suffix. 6ES7141-1BF30-0XA0 is the EM 141 input module described here. When comparing products through the Siemens main menu, check more than the 1BF30 segment: 141 / 142 changes the component's function.
Editor's note
Select a replacement by checking the expansion module label together with the basic module label. “ET 200X, eight inputs” is not a complete identification. Keeping both labels, the wiring arrangement and the relevant manufacturer supplement in one maintenance record makes ordering easier.
Manuals and PDF documentation
Consult the ET 200X documents on our Siemens ET 200 PDF and user manuals page. Alongside the main manual, review the compatibility note in A5E00125915-05, 01/2005, page 6. Match technical values to the 6ES7141-1BF30-0XA0 product data sheet; do not treat a manual section for 1BF31 as an identical description of the earlier 1BF30 model.
Related topics and Siemens navigation
Product family: Siemens main menu | SIMATIC S7 | ET 200 family
Station and field devices: Digital input modules | Additional modules | PROFIBUS and PROFINET
Technical resources: About ET 200 | Power supply modules | ET 200 PDF manuals