6ES7 141-1BF11-0XB0

Siemens main menu › SIMATIC S7 family › ET 200 › Digital input modules

6ES7 141-1BF11-0XB0 — Siemens ET 200X BM141, 8 DI 24 V DC Basic Module

6ES7 141-1BF11-0XB0 is an ET 200X BM141 basic module in the Siemens SIMATIC product family. It combines 8 digital inputs at 24 V DC, an integrated PROFIBUS DP interface and power connections. In ET 200 distributed I/O systems, it collects machine-mounted switch and proximity sensor signals while handling station communication.

Five checks before selection

1. Basic module and network compatibility: The device operates as a PROFIBUS DP slave at up to 12 Mbit/s. Establish the station network type when comparing PROFIBUS and PROFINET options. In the Siemens S7 control project, verify the device definition for the complete order number, PROFIBUS address and expansion sequence. Direct data exchange is supported in the sender role; assess this feature separately from normal DP communication.

2. Sensor compatibility and pulse duration: Among ET 200 digital input modules, this model has IEC 61131 Type 2 input characteristics. The specified signal “1” range is 13–30 V, and signal “0” is −3 to +5 V. Two-wire sensors must have an off-state current no higher than 1.5 mA. Input delay is 1.2–4.8 ms for both transitions. For short-pulse counting, also consider ET 200 counter modules; delivery of a detected pulse to the PLC program also depends on communication and program cycle times.

3. Eight channels through four M12 sockets: On X1–X4, pin 4 carries channels 0–3, and pin 2 carries channels 4–7. X1 therefore carries channels 0 and 4. Pin 1 is sensor supply L+, pin 3 is supply return, and pin 5 is PE. When selecting ET 200 connection components and Y splitters, check that both input signals are carried by the wiring. For IP66/IP67 protection, install connections correctly and seal unused sockets with suitable caps.

4. Expansion capacity: The BM141 supports up to 7 expansion modules; additional subgroup limits apply to motor starters/frequency converters and pneumatic interfaces. Select ET 200 expansion modules by complete model number, power requirements and project support as well as module count. For example, the EM142 6ES7142-1BD40-0XB0 compatibility list includes this basic module from product version 01. Record the version together with the order number.

5. Distinguish the supply circuits: 1L+ supplies electronics and sensors, while 2L+ is the load supply; both use nominal 24 V DC. In the ET 200 power supply arrangement, the permissible current for the 1L+ electronics/sensor circuit is 1 A up to 40 °C and 0.8 A up to 55 °C. This is not a separate current allowance for each sensor. Calculate power distribution within the station with all connected modules included. 2L+ has no reverse-polarity protection; verify polarity before connection.

Editor’s note

Having only inputs on the BM141 does not rule out a load-supply diagnostic. This basic module allows missing load voltage diagnostics to be configured. When troubleshooting, read the ON, BF, SF and DC24V indicators together, then compare 1L+/2L+ measurements, project settings and expansion modules. Establish which supplies the station requires before changing diagnostic settings.

PDF and technical documentation

Visit the Siemens ET 200 PDF and user manual library for the documentation guide. Use the product datasheet dated 27 February 2020 and ET 200X documentation that lists the complete order number. The Italian A5E00158282-05 system manual, 05/2001, section 7.1, printed pages 7-2–7-4, covers this model. The English EWA 4NEB 780601602-06 manual provides Table 5-22 for diagnostics and compatibility lists for expansion modules.

Related topics

Terminal bases • Connection modules • Digital inputs • Digital outputs • Power distribution • Additional modules

Otomasyon AVM • Siemens guide

Siemens main menu  |  SIMATIC S7 family  |  ET 200 module categories  |  ET 200 PDF archive