6ES7 141-1BD30-0XA0

Siemens main menu › SIMATIC S7 family › ET 200 › Digital input modules

6ES7 141-1BD30-0XA0 — Siemens ET 200X EM141, 4 DI 24 V DC Digital Input Expansion Module

6ES7 141-1BD30-0XA0 is an ET 200X EM141 digital input expansion module in the Siemens SIMATIC product family. It adds 4 digital inputs at 24 V DC to an existing station. Within ET 200 distributed I/O systems, it collects signals from switches and compatible proximity sensors. Selection requires particular attention to basic module compatibility as well as input count.

Five checks before selection

1. Role within the station: EM141 is an expansion module and does not operate as an independent PROFIBUS station. Assess the basic module when reviewing ET 200 communication options. In the Siemens S7 hardware configuration, compare module order, device definition and input addresses with the installed equipment. Before replacement, confirm that the project backup and field labels identify the same module.

2. Sensor and signal compatibility: Among ET 200 digital input modules, this model has a nominal input voltage of 24 V DC. The Siemens ST40 catalog specifies 13–30 V for signal “1”, −3 to +5 V for signal “0”, and an input delay of 1.2–4.8 ms. Two-wire sensors must have a permissible off-state current no higher than 1.5 mA. For fast pulse counting, assess ET 200 counter modules separately; consider input delay together with PLC and communication cycle times.

3. M12 connections: Field wiring uses 5-pin M12 sockets. Pin 4 of X1–X4 carries channels 0–3 respectively. Pin 1 is L+, pin 3 is supply return, and pin 5 is PE. When selecting ET 200 connection components, check pin numbers before relying on wire colors. Labeling each cable with both its socket and PLC address reduces channel mix-ups during maintenance. Seal unused connections with suitable caps.

4. Supply and cable checks: Assess the ET 200 power supply arrangement together with the basic module and connected sensors. When reviewing power distribution within the station, establish which modules could be affected by a faulty sensor cable. The catalog specifies a maximum unshielded sensor cable length of 30 m. An illuminated sensor indicator does not prove that the correct voltage reaches the module input; measure at the input using the correct reference.

5. ECOFAST/DESINA compatibility restriction: Siemens product information A5E00125916-04, dated 03/2003, restricts use of this expansion module with basic modules 6ES7141-1BF00-0AB0, 6ES7141-1BF01-0AB0, 6ES7141-1BF40-0AB0, 6ES7143-1BF00-0AB0 and 6ES7143-1BF00-0XB0. In these combinations, a sensor-line short circuit may not be contained by the modules and can affect the 24 V supply line. Account for this note when selecting ET 200 expansion modules. The document lists 6ES7141-1BD31-0XA0 among the alternatives; separately verify project and wiring compatibility before replacement.

Editor’s note

The ET 200X family name alone does not establish compatibility. The distinction between 1BD30 and 1BD31 matters in the manufacturer’s compatibility supplement. Read later product information alongside the original catalog description. A general compatibility statement is insufficient without the complete basic module order number.

PDF and technical documentation

Visit the Siemens ET 200 PDF and user manual library for the documentation guide. For this order number, consult Siemens ST40 catalog page 4/33 for technical specifications and page 4/38 for ordering data, followed by page 1 of compatibility supplement A5E00125916-04, 03/2003. Use the ET 200X system manual for general installation and station architecture. Do not treat a 1BD31 section in a later edition as an unconditional datasheet for 1BD30.

Related topics

Terminal bases • Connection modules • Digital inputs • Digital outputs • Power distribution • Additional modules

Otomasyon AVM • Siemens guide

Siemens main menu  |  SIMATIC S7 family  |  ET 200 module categories  |  ET 200 PDF archive