6ES7 138-7EA00-0AA0
Siemens Automation Main Page › Siemens SIMATIC S7 PLC › Siemens ET 200 Modules › ET 200 Manuals and PDF Archive
6ES7 138-7EA00-0AA0 – Siemens SIMATIC ET 200iSP PS 24 V DC Power Supply
6ES7 138-7EA00-0AA0 is an ET 200iSP Power Supply PS module designed for Siemens SIMATIC ET 200 distributed I/O systems. It converts the incoming 24 V DC supply into the galvanically isolated and intrinsically safe internal voltages required by the ET 200iSP station. It should therefore be regarded as the station power-entry module, not as a general-purpose DIN-rail power supply.
The module belongs to the ET 200iSP architecture used with Siemens SIMATIC S7 automation systems. Selection must be based on the complete 7EA00 article number, terminal module, mechanical coding and approved station configuration. General information about the product family is available on the Siemens ET 200 system overview page.
Function Within the ET 200iSP Station
6ES7138-7EA00-0AA0 provides the output voltages required by the ET 200iSP station. Potential isolation is provided between the incoming supply and the power bus, backplane bus and interface-module supply. This gives the product a specialised role among ET 200 power supply modules intended for hazardous-area applications.
The external 24 V DC source is connected through the correct ET 200 terminal module. The station load calculation must consider the complete ET 200 power-distribution arrangement, electronic-module population and connected field loads rather than the PS input rating alone.
Principal Technical Data
Product type: ET 200iSP Power Supply PS
Article number: 6ES7 138-7EA00-0AA0
Supply voltage: 24 V DC
Current consumption from the 24 V DC supply: Maximum 4 A
Maximum permissible input power: 78.6 W
Module power loss: 20 W
Reverse-polarity protection: Yes
Insulation test voltage: 600 V DC between the supply and all output voltages
Terminal module: Version-compatible TM-PS-A or TM-PS-B
Approximate dimensions: 60 × 190 × 136.5 mm
Approximate weight: 2.7 kg
Maintenance: Described by the manufacturer as maintenance-free
Operation with ET 200 communication and interface modules depends on the approved station configuration. The presence of a compatible PROFIBUS or communication interface does not remove the need to verify the power-supply and terminal-module combination.
Important Difference Between 7EA00, 7EA01 and 7EC00
6ES7138-7EA00-0AA0 and 6ES7138-7EA01-0AA0 are different article numbers. The existence of a later version does not establish drop-in compatibility with the older module. Siemens uses mechanical coding to prevent unsuitable power-supply and terminal-module combinations. The AC-powered 7EC00 version must likewise not be confused with the 24 V DC 7EA00 module.
Before replacement, verify the PS article number, TM-PS terminal-module article number, ET 200 connection modules, coding elements and configured station hardware together. Similar appearance is not evidence of electrical or hazardous-area compatibility.
Hazardous-Area Installation and Wiring
This module was developed for the ET 200iSP hazardous-area system. This does not mean that it may be installed unconditionally in every enclosure or hazardous zone. The nameplate, hardware version, certificate, zone classification, enclosure, ambient conditions and national regulations must be checked. Safety-related applications also require the correct ET 200 safety and PROFIsafe modules.
The 24 V DC supply is connected to the L+ and M terminals, while equipotential bonding is connected to the PA terminal. Intrinsically safe and non-intrinsically-safe wiring must be separated and must not share the same cable duct. In Zone 1, supply conductors may only be disconnected while de-energised. Installation and replacement must be performed by qualified personnel according to the applicable certificate and the plant explosion-protection documentation.
Commissioning Checklist
1. Confirm that the complete nameplate number is 6ES7138-7EA00-0AA0.
2. Check the complete TM-PS-A or TM-PS-B article number and mechanical coding.
3. Verify 24 V DC polarity, voltage stability, protection and conductor size.
4. Inspect the PA bonding connection and the Ex enclosure protection rating.
5. Calculate the complete station demand, module population and field loads.
6. Check the housing, contacts, terminals and coding components before energising.
Additional ET 200 auxiliary and additional modules can alter the station power budget. Loads connected to ET 200 digital output modules must also be checked against their individual channel and total-current limits.
Inspection of a Used Module
A basic power-on test is not sufficient for a used module. Confirm the full article number and inspect the terminal contacts for discoloration, overheating, oxidation and mechanical stress. Missing or altered coding components increase the risk of installation on an unsuitable terminal module. Where possible, document the Ex marking, product version, enclosure history and previous operating environment.
For a compatibility review, use the Siemens automation contact page and provide both the PS and TM-PS article numbers. These two numbers are more useful than a general photograph of the station.
Manuals and PDF Documents
For ET 200iSP system manuals, wiring documents and related technical publications, visit the Siemens ET 200 manuals and PDF archive.
Siemens ET 200iSP Power Supply PS product information – multilingual PDF
The document includes the installation, safety and technical information for the 6ES7138-7EA00-0AA0 version.
Reminder: The technical information on this page is intended to assist product identification. Hazardous-area installation, terminal-module selection, wiring, commissioning and replacement must be based on the product nameplate, plant classification and the manufacturer’s documentation for the exact hardware version.