6ES7 138-7BB00-0AB0
Siemens main menu › SIMATIC S7 › SIMATIC ET 200
Siemens 6ES7 138-7BB00-0AB0 — ET 200iSP WATCHDOG
6ES7 138-7BB00-0AB0 is the ET 200iSP WATCHDOG module in the Siemens ET 200 distributed I/O family. It supports checks of station data exchange and provides an intrinsically safe 11 V supply for external disconnection of digital outputs. Selecting this product from the ET 200 special-function and expansion module range requires separate consideration of the monitoring program and the shutdown circuit.
Order number: 6ES7138-7BB00-0AB0
System: SIMATIC ET 200iSP
Function: WATCHDOG / station functional check
Physical digital inputs: None
Terminal families: TM-IM/EM and TM-EM/EM
Dimensions, W × H × D: 30 × 129 × 136.5 mm
Shutdown signal supply: 11 V, within the same station only
Shutdown signal cable: 20 m maximum
How does it check station operation?
Within the ET 200 system architecture, WATCHDOG allows a value written to the output data to be read back through the input data. This check requires no field wiring; its result must be evaluated by the user program. When reviewing ET 200 communication options, distinguish this module from a standalone network tester. Its check uses the station's process data.
In write/read mode, the written byte is returned; write/read neg. returns its bitwise inverse. The toggle settings change input byte bit 0 at 0.1 / 0.5 / 1 / 2 Hz. For example, writing 55H gives an expected result of 55H in normal mode and AAH in inverted mode. This illustrates the difference between the modes; test timing must be defined in the application.
Five checks before selection and commissioning
1. Terminal module and mechanical coding: Select the appropriate base from the ET 200 terminal modules for the existing station arrangement. WATCHDOG uses the TM-IM/EM or TM-EM/EM family. When inspecting ET 200 connection components, check the socket and coding element too; do not alter mechanical coding to fit an incorrect component.
2. Addresses and monitoring logic: Record input/output addresses, operating mode and evaluation logic together in the Siemens S7 hardware project. The program should define what is sent, what response is expected and what happens if the response is missing. A match against one unchanging value alone is a weak basis for continuous monitoring.
3. Purpose of the shutdown circuit: The module's 11 V connection supplies the shutdown signal on suitable modules in the ET 200 digital output range. Do not use it as a general sensor supply. When comparing ET 200 power supply components, distinguish the station's main power supply from WATCHDOG's supply for the shutdown signal.
4. STOP response and power budget: CPU/master STOP settings include retaining the last value, 00H or FFH. Do not assume that this setting automatically puts physical outputs into a safe state. For ET 200 power distribution calculations, use the manufacturer's consumption relationship of 2 mA × the number of connected digital output modules; check connection limits against the relevant output module manual.
5. Hazardous-area application: The device label, certificate, terminal type and enclosure conditions must suit the same application. Separate intrinsically safe wiring from other circuits as instructed by the manufacturer. Ex suitability alone does not establish a SIL/PL-rated safety function. When comparing replacements through the Siemens main menu, check the complete suffixes of similar references.
Editor's note
The useful question goes beyond “Is the LED on?”: What response does the program expect, and what does it do when that response stops? Include the operating mode, addresses and fault response in the maintenance record. A successful write/read check alone does not establish that every field sensor and actuator is working.
Manuals and PDF documentation
Use the ET 200iSP documents on our Siemens ET 200 PDF and user manuals page. Product information for this model is A5E00807410-03; function and parameter descriptions appear in A5E00247483-AI, 12/2020, section 14.2. In the newer 03/2025, A5E00247483-AL edition, WATCHDOG is covered in section 17.2. Match documentation by product reference and edition as well as section number.