6ES7 138-4FB02-0AB0

Siemens Main Menu  |  SIMATIC S7  |  Siemens ET 200  |  PDF Manuals

6ES7 138-4FB02-0AB0 — Siemens ET 200S PROFIsafe Fail-Safe Output Module

6ES7 138-4FB02-0AB0 is the 4 F-DO DC24V/2A PROFIsafe electronic module for the ET 200S series within the Siemens ET 200 distributed I/O family. Among ET 200 safety modules, it provides four digital outputs for safety-related control tasks.

Module function

This model is a fail-safe member of the ET 200 digital output module range. It uses P/M switching, controlling both the positive and negative sides of the load. Typical suitable loads include solenoid valves, DC contactors and indicator lamps.

In ET 200 PROFIsafe applications, assess the module together with the safety program and a suitable F-CPU. A SIMATIC S7 control system requires matching CPU, software and hardware versions. The station’s network connection depends on its ET 200 communication interface.

Key technical details

Order number: 6ES7138-4FB02-0AB0.
Module designation: 4 F-DO DC24V/2A PROFIsafe.
Outputs: 4 fail-safe digital outputs.
Rated load voltage: 24 V DC.
Rated output current: 2 A per channel.
Dimensions: 30 × 81 × 52 mm (width × height × depth).
Indicators: Red SF group-fault LED and green output-status LEDs.

A 2 A channel rating does not mean that 8 A total is available under every installation condition. Check the aggregate load limit against temperature and mounting orientation. The catalogue does not permit paralleling outputs to increase current capacity.

Terminal and power module selection

The electronic module plugs into a suitable terminal base. When selecting ET 200 terminal blocks, a matching 30 mm width is insufficient: verify the terminal assignment for the 4FB02 version. Do not automatically apply information for later 4FB03 or 4FB04 versions to this model.

The choice of ET 200 power supply modules affects the achievable safety level. Siemens product information A5E36397089-AB classifies this module’s use with PM-E DC24V versions up to 6ES7138-4CA01-0AA0 as SIL2 / Category 3 / PL d. An unconditional SIL3 claim is therefore inappropriate without checking the ET 200 power distribution arrangement.

Maintenance and commissioning approach

Before replacement, compare the full order number, hardware version, terminal base and project hardware list. Review the ET 200 system architecture to distinguish the station components and their functions. Commissioning checks should cover the F-address, safety parameters and diagnostic records; qualified personnel must validate the safety function for the application.

Editor’s note

Record the complete module code and its supply group together. “ET 200S, four outputs, 24 V” is insufficient for selection. For an enquiry, prepare photographs of the module label, terminal base and power module and share them through the Otomasyon AVM Siemens contact page. For used equipment, also establish the unit’s condition and exactly which components are included.

PDF catalogue and operating manuals

Use the Siemens ET 200 operating manuals and PDF archive to locate the relevant ET 200S documentation. The technical description for this model appears in A5E00103686-04, 07/2005, section 7.6. Also consult the A5E36397089-AB, 08/2015 update for power-module assignments.

The Siemens ET 200 catalogue PDF — IK PI 2007 includes this product’s technical and ordering information on printed pages 5/52–5/53. This is a catalogue, not a dedicated operating manual. Wiring and commissioning must follow manufacturer instructions covering the complete order number.