6ES7 138-4DL00-0AB0 is a 1PosUniversal (1PosU) positioning module in the Siemens ET 200S family. It uses encoder position feedback and digital outputs to control rapid/creep movement. Within the ET 200 positioning module range, it serves single-axis applications using this control method.
Key specifications
Supply: 24 V DC, permitted range 20.4–28.8 V DC. Electronics module dimensions: 30 × 81 × 52 mm. Encoder options: 5 V differential or 24 V incremental encoders; Gray-coded SSI encoders. Maximum incremental input frequency is 500 kHz at 5 V and 100 kHz at 24 V.
The module has three digital outputs and three digital inputs assigned to positioning functions. Unlike a selection based only on the channel count of standard digital input modules or standard digital output modules, selection must account for these functions.
Five checks before selection
1. Drive command method: Examine the drive’s command inputs. A rapid/creep and direction arrangement differs from a pulse/direction arrangement. Before choosing among ET 200 function modules, identify how the existing machine commands motion.
2. Encoder electrical requirements: Check signal type, resolution and supply voltage separately. As with ET 200 counter modules, an “encoder input” description alone is insufficient. Accepting 5 V signals does not mean supplying 5 V to the encoder. This module has no 5 V encoder supply output; it provides a 24 V encoder supply.
3. Terminal base: The Siemens manual specifies a TM-E30x44-01 base. Check the complete order number and terminal assignment when selecting ET 200S terminal bases. When replacing field connection components, do not transfer wires solely by their physical positions.
4. Supply arrangement: Assess the ET 200S power supply modules together with the encoder and output loads. The 24 V encoder supply is rated for a maximum of 500 mA; this is not a motor power rating.
5. Project and mechanical settings: Check the ET 200 station communication interface, encoder selection in the hardware catalogue and existing program. Record encoder scaling, reference position and stopping distances, then perform a controlled motion test after replacement.
Editor’s note
A positioning error does not automatically indicate a faulty module. Inspect the encoder coupling, mechanical backlash, brake condition and drive deceleration as well. Compare commanded movement with measured movement before deciding to replace the module.
PDF documentation and wiring references
Use the Siemens ET 200 PDF and user manual page alongside ET 200S Positioning, A5E00124872-05, 06/2010, specifically Chapter 3 — 1PosUniversal. The product overview starts on page 61, terminal assignments on page 70 and technical specifications on page 134. The 1STEP 5V chapter in the same manual covers a different module.
Related topics
Terminal bases • Connection modules • Digital inputs • Digital outputs • Power distribution • Additional modules
Otomasyon AVM • Siemens guide
Siemens main menu | SIMATIC S7 family | ET 200 module categories | ET 200 PDF archive