6ES7 138-4DE02-0AB0

Siemens main menu › SIMATIC S7 › SIMATIC ET 200

Siemens 6ES7 138-4DE02-0AB0 — ET 200S 1Count5V/500kHz High-Speed Counter Module

6ES7 138-4DE02-0AB0 is the 1Count5V/500kHz single-channel high-speed counter module for the ET 200S series within the Siemens ET 200 distributed I/O family. It processes incremental encoder signals for counting and measurement. Among ET 200 special-function and additional modules, it is a candidate for applications requiring encoder feedback.

Order number: 6ES7138-4DE02-0AB0
Encoder interface: 5 V differential signals, RS-422
Counter: 1 channel, 32 bit
Supply: 24 V DC
Module width: 30 mm

Where does it fit?

Within the ET 200 system architecture, this module supports pulse counting, frequency, rotational speed and period measurement, and position feedback. When describing your application, specify whether the PLC program needs a count value, speed information or position feedback. This gives hardware selection and software checks a clear, shared starting point.

Five checks before ordering or replacement

1. Signals and supply: The 5 V designation refers to the encoder signal interface. The encoder supply output is specified as 24 V class, L+ − 0.8 V, with a maximum of 500 mA. Check the encoder's supply requirement separately. When reviewing ET 200 power supply modules and the ET 200 power distribution arrangement, keep signal levels and supply voltages clearly distinguished.

2. Operating mode and project: Record the configured module, parameters and I/O addresses. Review the complete codes of the Siemens S7 control system and ET 200 communication interface together. If the application uses isochronous operation, verify the station and project configuration as well as the module label.

3. Auxiliary inputs and outputs: The module has one digital input and two digital outputs. The input supports gating, synchronization or latching. Trace these connections separately from the station's other ET 200 digital input modules and ET 200 digital output modules. Check that terminal labels match the addresses used in the program.

4. Terminal base: The relevant Siemens manual specifies the TM-E30S44-01 terminal module. When selecting from ET 200 terminal blocks, compare this type with the installed base label. While reviewing ET 200 connection modules and field wiring, distinguish the electronic module's order number from the base code. Record contact condition and terminal numbering as well.

5. Frequency and cable length: The data sheet lists a maximum encoder input frequency of 650 kHz and a frequency measurement limit of 500 kHz. The shielded encoder cable limit is 50 m, reduced to 30 m above 500 kHz. These figures describe different limits. Assess encoder pulse count, maximum operating speed and the actual cable route together.

Checks after replacement

Preserve the existing project and parameter backup first. Then use a known movement or pulse sequence to compare counting direction and measured values. Mechanical transmission ratio, encoder pulse count and program scaling should agree. Successful communication alone does not establish that the measurement is scaled correctly.

Editor's note

Include the module and encoder labels, terminal base details and configured operating mode in a spare-part enquiry. State whether “5 V encoder” refers to its signals or its power supply. Clarifying this detail can save considerable time during ordering and commissioning.

Manuals and PDF documentation

On our Siemens ET 200 PDF and user manuals page, refer to ET 200S Technological Functions, A5E00124867-06, chapter 3 — 1Count5V/500kHz. Use section 3.4 for terminal assignments and 3.5 for operating mode selection. Check electrical limits against the data sheet for the complete order number.

Related topics and Siemens navigation

Product family: Siemens main menu  |  SIMATIC S7  |  ET 200 family

Station and connections: Special and additional modules  |  Terminal blocks  |  PROFIBUS and PROFINET

Technical resources: About ET 200  |  Power supply modules  |  ET 200 PDF manuals