6ES7 138-4CF03-0AB0 — Siemens ET 200S PM-E F pm PROFIsafe Power Module

6ES7 138-4CF03-0AB0 is a PM-E F pm DC24V PROFIsafe fail-safe power module in the Siemens ET 200 distributed I/O family. It combines power-group switching with two fail-safe digital outputs in an ET 200S station. When selecting ET 200 safety modules, assess these functions separately.

Function and output arrangement

The module switches an externally supplied 24 V DC supply; it does not convert mains voltage into 24 V. Review ET 200 power supply modules alongside the ET 200 power distribution arrangement. DO0 and DO1 are semiconductor outputs. DO2 is the relay output switching both L+ and M for P1/P2; it must not be counted as two independent 10 A outputs.

Key technical details

Order number: 6ES7138-4CF03-0AB0.
Designation: PM-E F pm DC24V PROFIsafe.
Rated supply: 24 V DC.
Semiconductor outputs: 2, P/M switching, rated 2 A per channel.
Dimensions: 30 × 81 × 52 mm (W × H × D).
Total current limit, horizontal mounting: 10 A up to 40 °C; 7 A up to 55 °C; 6 A up to 60 °C.
Total current limit, vertical mounting: 6 A up to 40 °C.

Interpreting the safety ratings

Fail-safe group shutdown of suitable ET 200 standard digital output modules is rated up to SIL2 / Category 3 / PLd; suitable DO0/DO1 applications can reach SIL3 / Category 4 / PLe. Siemens manual Table 7-1 additionally conditions the P1/P2 relay-output rating on switching frequency: SIL3 with signal changes monthly or more often, SIL2 with less frequent changes. This does not raise the standard DO group’s limit.

Five selection and commissioning checks

1. Read the complete terminal-base code. Suitable bases are TM-P30S44-A0 / 6ES7193-4CK20-0AA0 with screw terminals and TM-P30C44-A0 / 6ES7193-4CK30-0AA0 with spring terminals. Do not select ET 200 terminal blocks by width alone; compare the ET 200 connection arrangement with the project drawing.

2. Check the safety project. For ET 200 PROFIsafe communication, verify the F-CPU, safety program, F-address and hardware selection together. Record whether the addresses in the SIMATIC S7 control project match the device setting.

3. Verify the station interface. Siemens specifies PROFINET operation with the IM151-3 HF. Check the complete order number and version of the installed ET 200 PROFIBUS or PROFINET interface; a matching network name alone does not establish compatibility.

4. Match the current calculation to mounting conditions. Consider the load list, cabinet temperature and mounting orientation together. Do not add the two 2 A output ratings to the 10 A figure and assume a 14 A total capacity. Assess load pickup behaviour as well as continuous current.

5. Do not select replacements by similar codes alone. The “pm” and “pp” designations identify different switching arrangements. When reviewing the ET 200 system architecture, compare the existing wiring drawing, load M connections and project parameters. Include verification of the safety functions in the maintenance record after replacement.

Editor’s note

When investigating a fault, first record whether it affects one load or the entire supply group. The module label, terminal-base code, LED status and project diagnostic message are most useful together. Share these details through the Otomasyon AVM Siemens contact page. A green LED alone does not demonstrate that the safety function has been validated.

PDF manuals and documentation

Use the Siemens ET 200 PDF manuals page to access safety-module and terminal-module documentation. For this product, start with A5E00103686-08, section 7.2, and A5E01120034-01, section 1.5. For wiring and parameter selection, check the complete device code, document scope and applicable product-information supplements together.