6ES7 132-7RD00-0AB0
Siemens main menu › Siemens S7 family › ET 200 › Digital output modules
6ES7 132-7RD00-0AB0 — Siemens ET 200iSP 4 DO, 23.1 V DC / 20 mA Digital Output Module
6ES7 132-7RD00-0AB0 is an electronic output module in the Siemens SIMATIC product family, designated 4 DO, 23.1 V DC / 20 mA. It belongs to the ET 200iSP distributed I/O system. Retain the exact 7RD00 identifier when selecting a replacement.
What does it do?
It switches suitable Ex i field loads. When selecting a solenoid valve or relay, compare its load characteristic as well as its nameplate voltage. This product belongs to the ET 200 digital output range; 20 mA in its designation does not mean an analog 4–20 mA command. Match the field connections and terminal arrangement to the diagram for the exact model.
Five checks before selection
1. Exact order number: 6ES7132-7RD00-0AB0 and 6ES7132-7RD01-0AB0 are different order numbers. Siemens explicitly identifies RD01 as SHUT DOWN “H”. Do not assume this feature for RD00; review the hardware configuration and field circuit together before changing variants.
2. Voltage and load: The datasheet specifies 23.1 V at no load and 17.1 V / 20 mA at characteristic point E. Do not select a load on the assumption that 23.1 V remains available under all operating conditions. Include the ET 200 power supply arrangement and cable voltage drop in the assessment.
3. Terminal module: Siemens lists the TM-IM/EM and TM-EM/EM families in its control drawing. When choosing ET 200 terminal modules, verify ET 200iSP compatibility, the complete base order number and connection type. ET 200S and ET 200SP bases are not equivalent mounting options.
4. Station and diagnostics: Match the module to its configured slot. Check the ET 200 communication interface alongside the module entry in the engineering project. Wire-break and short-circuit diagnostics, the red SF indicator and channel status LEDs help with troubleshooting. Include the digital input feedback channels associated with the actuator when checking the control sequence.
5. Complete Ex i circuit: Assess the applicable certificate limits for the module, field device and cable together. Operating voltage and certified safety limits serve different purposes. Selecting ET 200 safety modules requires a separate assessment; intrinsic safety alone does not establish fail-safe or PROFIsafe functionality.
Editor’s note
Record the complete module number, terminal base and connected load together, rather than describing the part simply as an “ET 200 output card”. For Siemens S7 system maintenance, these details help prevent the selection of a similar-looking but unsuitable module.
PDF and technical documentation
Visit the Siemens ET 200 PDF and user manual library for relevant documentation. Use the 6ES7132-7RD00-0AB0 datasheet and ET 200iSP documents for this model. Pages 11–12 of control drawing A5E00455287-AG identify RD00 and its Ex i output limits. Do not transfer RD01 specifications from newer manuals directly to the earlier RD00 version.
Related topics
Terminal bases • Connection modules • Digital inputs • Digital outputs • Power distribution • Additional modules
Otomasyon AVM • Siemens guide
Siemens main menu | Siemens S7 family | ET 200 module categories | ET 200 PDF archive