6ES7 132-4FB01-0AB0
Siemens main menu › Siemens S7 family › ET 200 › Digital output modules
6ES7 132-4FB01-0AB0 — Siemens ET 200S 2 DO, 24–230 V AC Digital Output Module
6ES7 132-4FB01-0AB0 is a two-channel AC digital output module for ET 200S in the Siemens SIMATIC product family. It operates with 24–230 V AC load circuits and is 15 mm wide. When comparing ET 200 digital output modules, check the AC output requirement before choosing a replacement.
Where is it used?
Typical loads include suitable solenoid valves, AC contactors and indicator lamps. When reviewing the ET 200S station arrangement, assess load voltage, pickup current and operating frequency together. Base the field wiring arrangement on the diagram for the exact order number rather than the appearance of the existing module.
Five checks before selection
1. AC load and supply: The specified load supply is 24–230 V AC at 47–63 Hz. Do not assume equivalent operation with 24 V DC loads. Match the ET 200S power module to the actual load voltage and check the power distribution arrangement separating the station’s potential groups.
2. Channel rating and total current: Although the nominal channel rating is 2 A, total module output current is limited to 2 A up to 40 °C and 1 A at 60 °C. Use the manual’s curve for intermediate temperatures. Do not load both channels at 2 A simultaneously. Base the calculation on the module’s operating temperature, not simply the temperature outside the cabinet.
3. Terminal base and connections: Compatible ET 200S terminal bases include TM-E15S26-A1 / 6ES7193-4CA40-0AA0 with screw terminals and TM-E15C26-A1 / 6ES7193-4CA50-0AA0 with spring terminals. Outputs use terminals 1 and 5; neutral uses 3 and 7. Check the diagram for the selected base because terminal availability and AUX1 connections vary across compatible versions.
4. STOP response and indication: CPU/master STOP can trigger a substitute value or retention of the last value. Green LEDs indicate channel status; the module has no diagnostic function. Distinguish the state observed through the ET 200 communication interface from actual actuator movement. Where required, monitor an auxiliary contact through digital input feedback channels.
5. Off-state current and small loads: Specified leakage current at output state “0” is up to 3 mA. If a low-power lamp glows faintly or a sensitive load fails to release, compare this value with the load specifications. An OFF command does not provide electrical isolation. Isolate the circuit at the appropriate point before measurement or maintenance.
Editor’s note
The Siemens catalogue statement “5 units per packing unit” describes factory packaging. It does not describe the channel count of one module or the quantity supplied in a used-equipment listing. When selecting Siemens S7 replacement parts, record the exact model, required module quantity and whether the terminal base is included.
PDF and wiring documentation
Visit the Siemens ET 200 PDF and user manual library. The dedicated manual is 2DO AC24..230V — 6ES7132-4FB01-0AB0, A5E01077264-01. Wiring and terminal options appear on pages 7–8, technical limits and current derating on pages 9–10, parameters on page 11 and LED indications on page 13.