6ES7 132-4BD32-0AA0

Siemens Main Menu  |  SIMATIC S7  |  Siemens ET 200  |  PDF Manuals

6ES7 132-4BD32-0AA0 — Siemens ET 200S 4 DO 24 V DC/2 A ST Digital Output Module

6ES7 132-4BD32-0AA0 is a four-channel standard digital output module for the ET 200S series in the Siemens ET 200 distributed I/O family. It operates 24 V DC solenoid valves, DC contactors and indicator lamps from a SIMATIC S7 control system.

Output arrangement and current limit

Each of the four outputs has a nominal rating of 2 A, while the permitted total current for all outputs of the module is limited to 4 A. The rating cannot be interpreted as “4 channels × 2 A = 8 A”. When comparing ET 200 digital output modules, distribute loads between channels and calculate the total current in the power group separately.

Key technical details

Order number: 6ES7132-4BD32-0AA0.
Designation: 4 DO DC24V/2A ST.
Output type: PNP current-sourcing output.
Outputs: 4.
Rated current per channel: 2 A.
Total module current: 4 A maximum.
Load voltage: 24 V DC from the power module.
Width: 15 mm.
Address space: 4 bits when packed; 1 byte when unpacked.
Typical power loss: 1.6 W.
Factory package: 5 electronic modules per packing unit.

The outputs are short-circuit protected. Siemens specifies a signal-1 output voltage of at least L+ minus 1 V, a permissible current range of 7 mA to 2.4 A and one green status LED per channel. This ST version has no channel diagnostic function; detailed channel fault information should not be expected through the ET 200 PROFIBUS or PROFINET interface.

Five selection and commissioning checks

1. Calculate the total load current. The sum of the four continuous load currents must remain within the 4 A limit. Include pickup current for solenoids and contactors. Check the capacity of the ET 200 power supply module and ET 200 power distribution arrangement together with the other modules in the same potential group.

2. Identify the correct terminal base. The Siemens manual lists twelve spring, screw and Fast Connect terminal modules. Spring examples include 6ES7193-4CA50/30 and 4CB30/10; screw examples include 4CA40/20 and 4CB20/00; Fast Connect examples include 4CA80/70 and 4CB70/60. Select ET 200 terminal modules by AUX1 arrangement, terminal count and wiring method.

3. Do not parallel outputs to increase current. Two channels may control one load redundantly, but the Siemens data sheet does not permit parallel connection for uprating. If more current is required, use the ET 200 connection arrangement to assess a suitable interposing relay, contactor or another output module.

4. Match the load type and switching rate. Maximum switching frequency is 1 kHz with a resistive load, 2 Hz with a 0.5 H inductive load and 10 Hz with a lamp load. Lamp load is limited to 10 W per channel. The stated cable-length limit does not replace conductor-sizing and voltage-drop calculations at a 2 A load.

5. Verify replacements against the hardware project. Siemens identifies the 4BD32 as the successor to 6ES7132-4BD30-0AA0. Within the ET 200 system architecture, still compare hardware-catalogue selection, address packing, terminal code and power group. The order number represents a five-unit factory package; this must not be confused with the actual quantity in a field stock or used-equipment listing.

A short pulse that can be missed during commissioning

According to the Siemens manual, when the 24 V DC load voltage is applied to the power module through a mechanical contact, the digital outputs can carry a “1” signal for approximately 25 µs due to switching. Account for this behaviour when the module is used with fast digital inputs, counters or circuits sensitive to short pulses.

Editor’s note

If an output does not operate, the channel LED alone is insufficient because the ST version provides no detailed channel diagnostics. Measure L+ and M with the load connected, channel current, the common power group and terminal tightness. Share the module label, terminal-base code and load data together through the Otomasyon AVM Siemens contact page to make the product assessment more reliable.

PDF manuals and documentation

Consult A5E01001711-AB — 4DO DC24V/2A ST on the Siemens ET 200 PDF manuals page. The manual documents terminal assignments, compatible terminal bases, the 4 A total-current limit and switching behaviour specifically for the 6ES7132-4BD32-0AA0. Use it alongside the station manual when selecting ET 200 accessories and separation components.