6ES7 132-4BB01-0AB0 — Siemens ET 200S 2 DO 24 V DC/0.5 A HF Digital Output Module
6ES7 132-4BB01-0AB0 is a two-channel High Feature digital output module for the ET 200S series in the Siemens ET 200 distributed I/O family. It operates 24 V DC solenoid valves, DC contactors and indicator lamps from a SIMATIC S7 control system while providing channel diagnostics and configurable STOP behaviour.
What the High Feature version adds
This module is defined by more than its two outputs. Short-circuit and wire-break diagnostics are readable by channel; a red SF LED reports a group fault and green LEDs indicate output status. On CPU or master STOP, each channel can output a substitute value or retain its last value. These functions must be considered when comparing ET 200 digital output modules, rather than selecting by current rating alone.
6ES7132-4BB01-0AA0 is the Standard version with the same channel count and 0.5 A class. The -0AB0 High Feature module described here provides diagnostic and parameter functions. Always check whether the final characters are AA0 or AB0 before ordering.
Key technical details
Order number: 6ES7132-4BB01-0AB0.
Designation: 2 DO DC24V/0.5A HF.
Outputs: 2.
Rated current per channel: 0.5 A.
Permissible channel current: 7 mA to 0.6 A.
Total output current: 1 A maximum per module.
Load voltage: 24 V DC from the power module.
Dimensions: 15 × 81 × 52 mm.
Weight: approximately 40 g.
Address space: 2 bits when packed; 1 byte when unpacked.
Parameter length: 3 bytes.
Typical power loss: 0.4 W.
Factory package: 5 electronic modules per packing unit.
The outputs are short-circuit protected, with a typical response threshold of 1.5 A. Siemens specifies maximum delays of 100 µs for turn-on and 400 µs for turn-off, plus switching limits of 100 Hz for resistive loads, 2 Hz for inductive loads and 10 Hz for lamp loads. Detailed diagnostic availability also depends on the ET 200 PROFIBUS or PROFINET interface and its hardware configuration.
Six selection and commissioning checks
1. Calculate channel and total current separately. Continuous load must remain within the nominal 0.5 A rating per channel and the two-channel sum must remain within 1 A. Include pickup current for solenoids and contactors. Check the ET 200 power supply module and ET 200 power distribution arrangement together with other loads in the same potential group.
2. Distinguish HF from ST by the order number. -0AB0 is the diagnostic and parameter-capable HF version; -0AA0 is the Standard version. Do not substitute by appearance alone without comparing the STEP 7 hardware project, station interface and ET 200 system architecture.
3. Configure STOP behaviour deliberately. CPU/master STOP allows “substitute a value” or “keep last value”; the substitute can be set to 0 or 1 per channel. If the interface or COMPACT module loses power, however, the output module cannot provide substitute values and the output value becomes 0. Machine-safe stopping must not depend on this parameter alone.
4. Understand the diagnostic condition. Wire break is detected only while the output is switched on. An illuminated SF LED does not by itself prove a broken load wire; incorrect parameter assignment, an incompatible module or another pending diagnostic must also be checked. Feedback through ET 200 digital inputs provides stronger confirmation of actual movement for critical actuators.
5. Select the correct terminal base. The Siemens manual lists spring types 6ES7193-4CA50/30 and 4CB30/10, screw types 4CA40/20 and 4CB20/00, and Fast Connect types 4CA80/70 and 4CB70/60. Select ET 200 terminal modules by AUX1 arrangement, terminal count and wiring method. Channel 0 uses terminals 1-2-3, while channel 1 uses 5-6-7.
6. Verify the load type and protection arrangement. Lamp load is limited to 2.5 W per channel. Two outputs may control one load redundantly, but cannot be paralleled to increase current. For larger loads, use a suitable interposing relay or contactor in the ET 200 connection arrangement. Because reverse polarity can cause outputs to switch through, verify L+ and M before applying power.
A 50 µs pulse that can be missed during commissioning
When the 24 V DC load voltage is applied to the power module through a mechanical contact, the outputs can carry a “1” signal for approximately 50 µs, depending on the circuit. Account for this behaviour with fast counters and circuits sensitive to short pulses. The stated cable limits of 600 m unshielded and 1000 m shielded do not replace conductor-sizing and voltage-drop calculations.
Editor’s note
The most common mistakes are treating the SF LED as proof of an output-stage failure or assuming that AA0 and AB0 versions are identical because both contain 4BB01. First verify the complete order number, then inspect STEP 7 parameters, L+ and M voltage, load current and terminal-base code. Share the module label, SF condition, channel LEDs and load information through the Otomasyon AVM Siemens contact page for a more reliable assessment.
PDF manuals and documentation
Consult A5E01077220-01 — 2DO DC24V/0.5A HF on the Siemens ET 200 PDF manuals page. The manual documents terminal assignments, compatible terminal bases, STOP behaviour, channel diagnostics and the 50 µs switching pulse specifically for 6ES7132-4BB01-0AB0. Use it alongside the ET 200S station manual when selecting ET 200 accessories and separation components.
Related topics and Siemens navigation
Digital output modules | Terminal modules | Power supply modules
Power distribution modules | Communication interfaces | ET 200 system architecture
Siemens Main Menu | SIMATIC S7 | Siemens ET 200 | PDF Manuals