6ES7 132-4BB00-0AB0
Siemens main menu › Siemens S7 family › ET 200 › Digital output modules
6ES7 132-4BB00-0AB0 — Siemens ET 200S 2 DO, 24 V DC / 0.5 A High Feature Digital Output Module
6ES7 132-4BB00-0AB0 is a 2DO 24 V DC / 0.5 A High Feature electronic output module in the Siemens SIMATIC product family. It controls two field loads in the ET 200S distributed I/O system. Wire-break and short-circuit diagnostics are key maintenance features of this HF version.
Five checks before selection
1. Exact model and version: Do not confuse 4BB00-0AB0 with the Standard version or 2 A output models. Siemens lists 6ES7132-4BB01-0AB0 as its successor in the SIMOTION compatibility document. Before changing ET 200 digital output modules, compare the project configuration, interface version and load requirements. A successor listing does not guarantee a configuration-free replacement in every installation.
2. Load current and supply: The nominal rating is 0.5 A per channel, with a 1 A total for both outputs. Outputs must not be paralleled to increase current capacity. When selecting the ET 200S power module, account for coil pickup current and other loads in the group. Assess the potential distribution arrangement and conductor sizes against the combined load.
3. Terminal base: The legacy system manual shows this module with TM-E15S24-A1, TM-E15S24-01, TM-E15S23-01 and TM-E15S26-A1 bases. Selection between ET 200S terminal bases depends on the required connections and AUX1 use. Match the field wiring diagram to the complete base designation; mechanical fit alone does not establish compatibility.
4. Diagnostics and LEDs: Wire-break and short-circuit information can be read for each channel; diagnostics can be enabled or disabled through parameters. The red SF LED indicates a group fault, while green LEDs indicate output status. Read fault details through the ET 200 communication interface. Check the load, wiring and supply before treating an SF indication as proof of a defective module.
5. CPU/master STOP response: Configure substitute values or retention of the last value according to the machine’s stopping requirements. Retaining an output command does not confirm actuator movement; monitor digital input feedback signals where required. Include STOP and restart behaviour in commissioning checks as well as normal operation.
Editor’s note
The legacy Siemens manual notes that applying the power module’s 24 V supply through a mechanical contact can produce an approximately 50 µs HIGH pulse at the output. Account for this when connecting to high-speed counter inputs. When investigating an unexpected count at startup, also examine how the load supply is switched.
PDF and technical documentation
Visit the Siemens ET 200 PDF and user manual library. Use the 6ES7132-4BB00-0AB0 datasheet and section 11.13, printed pages 11-56–11-59, of ET 200S Distributed I/O System, 12/2004, EWA-4NEB 780602402-12. The catalogue’s five units per pack describes packaging; each module has two outputs.
Related topics
Terminal bases • Connection modules • Digital inputs • Digital outputs • Power distribution • Additional modules
Otomasyon AVM • Siemens guide
Siemens main menu | Siemens S7 family | ET 200 module categories | ET 200 PDF archive