6ES7 152-1AA00-0AB0
Siemens 6ES7 152-1AA00-0AB0 – ET 200iSP IM 152 Interface Module
6ES7 152-1AA00-0AB0 is the IM 152 interface module for the Siemens SIMATIC ET 200iSP distributed I/O system. Its order number is also written without spaces as 6ES7152-1AA00-0AB0. Within the ET 200 family, this model connects the station to a higher-level control system through PROFIBUS DP / RS 485-IS.
The IM 152 transfers I/O data for the electronic modules and handles station communication. It is not a PLC CPU executing an independent user control program. Field signals connect to suitable ET 200iSP I/O modules; the IM 152 handles data exchange between those modules and the PROFIBUS DP master.
Communication and station capacity
This model uses an intrinsically safe RS 485-IS physical interface. Its highest supported PROFIBUS transmission rate is 1.5 Mbit/s. The station address is set using switches on the module. The IM 152 supports an address space of 244 input bytes and 244 output bytes; the usable space also depends on the DP master and project configuration.
An ET 200iSP station can contain up to 32 electronic modules. Module count alone does not establish a valid configuration: total functional current consumption, power supply capacity and configuration limits must also be checked. Products listed under digital inputs, digital outputs and analog inputs are not universally compatible with this station. ET 200iSP compatibility must be confirmed using the complete order number.
Terminal module and hazardous-area use
The IM 152 plugs into a suitable TM-IM/EM or TM-IM/IM terminal module. Select terminal blocks, connection modules and power supply modules for the intended station arrangement. PROFIBUS RS 485-IS connects through the terminal module; it must not be treated as electrically interchangeable with an ordinary RS 485 connection.
Siemens product information specifies Ex ib IIC T4 Gb marking and permits Zone 1 use under the stated conditions. Suitability depends on the enclosure, RS 485-IS coupler, connection components and the complete Ex installation. Installation and servicing must follow the device label, applicable certificates and the relevant Siemens manual.
Configuration, redundancy and diagnostics
Match the IM 152 version, PROFIBUS address and physical module sequence to the project. Configure the station through the engineering tool’s hardware catalog or the appropriate GSD file. Siemens documents IM 152 redundancy from V2.0; this requires the appropriate terminal arrangement, a second interface module and a compatible control system.
BF indicates bus-related faults, while SF provides group-error indication. If the station is missing, investigate power, addressing, the coupler and bus termination. If it is accessible but reports module errors, compare the module sequence and parameters. Interpret LEDs together with controller diagnostics; a single indication does not establish that the interface module is defective.
Editor’s note: ET 200iSP and ET 200SP are different systems. This order number identifies a PROFIBUS interface; it does not provide PROFINET connectivity. For replacement or used-equipment assessment, check the complete code, hardware/firmware version, terminal compatibility and Ex markings together. This page provides technical information and does not establish the test status, stock availability or warranty of an individual unit.
User manuals and PDF documentation
For IM 152 product information, ET 200iSP system manuals and related documentation, visit the Siemens ET 200 user manuals and PDF documentation page. Match the document to 6ES7152-1AA00-0AB0 and the version of the installed device.
Related topics
ET 200 PROFIBUS and PROFINET interfaces · Other network interface modules · Power distribution modules.
Functional modules · Safety modules · PROFIsafe. These links explain different functions within the ET 200 family; the listed products should not be assumed to be direct replacements or compatible accessories for the IM 152.
Navigation: Siemens automation · SIMATIC S7 · About ET 200.
Technical sources: Siemens, Interface Submodule IM 152 – 6ES7152-1AA00-0AB0 product information (A5E00308225-06); ET 200iSP Operating Instructions (A5E00247483-AI), station configuration, commissioning and IM 152 sections; Siemens technical data sheet for this order number.