6ES5 101-8UB13

Siemens SIMATIC S5-101U 6ES5 101-8UB13 Central Controller

The 6ES5 101-8UB13 is a compact PLC in the Siemens SIMATIC S5 family with 10 digital inputs and 6 relay outputs. In existing machinery, it reads sensor signals, handles timing and counting, and switches its relay contacts according to the control program.

Mains and sensor supplies

The built-in power supply operates at 220/240 V AC, 48–63 Hz. Typical power dissipation at full load is 22 W. Siemens shows separate mains and sensor fuses for this model, both rated 500 mA, slow-blow.

When using the built-in 24 V DC / 300 mA sensor supply, check the total current drawn by connected devices, including inductive proximity sensors. The enclosure measures 285 × 167 × 114 mm, weighs approximately 2.7 kg and is rated IP20.

Input, output and terminal addresses

The ten digital inputs are rated 24 V DC. Siemens specifies +13 to +35 V DC for logic 1. The physical input addresses are I0.0, I0.2, I0.4, I0.6, I1.0, I1.2, I1.4, I1.6, I2.0 and I2.2.

The six digital outputs are addressed Q0.0, Q0.2, Q0.4, Q0.6, Q1.0 and Q1.2. When comparing other S5 I/O layouts, use the even-numbered bits wired to terminals on this model. Figure 11 of the Siemens manual shows the complete terminal layout.

Each relay contact has two separate terminals. Check the applicable contact rating when connecting a contactor or an interposing relay coil. Siemens lists 1.5 A at 250 V AC for AC-11 and 0.5 A at 30 V DC for DC-11.

STEP 5, program memory and PG connection

Use STEP 5 and the front PU/PG interface for programming. The internal RAM holds 1,024 statements and supports battery backup. A compatible EPROM or EEPROM memory submodule can retain the program for long-term storage. Siemens lists 6ES5 731-1BD20 as the programming cable for the PG 670 and PG 675.

Expansion and related order numbers

The EU/EG port connects to an S5-101U expansion unit using a short ribbon cable. The 6ES5 101-8UC11 expansion unit has relay outputs, while the 6ES5 101-8UC31 has transistor outputs. Check the expansion unit’s own supply and equipotential bonding against the Siemens drawing.

Compare the full order number when selecting a replacement central controller. The 6ES5 101-8UA13 has 20 inputs and 12 relay outputs. The 6ES5 101-8UA23 has triac outputs, and the 6ES5 101-8UA33 has a 24 V DC supply and transistor outputs.

Editor’s Note

On a used 8UB13, test all six relays individually with a suitable test load. The green output LED is wired in parallel with the relay coil. Confirm that the load switches when the LED comes on to catch a burnt or intermittent contact. The varistor across each contact can pass up to 1 mA when the output is off. For a unit removed from a machine, make a STEP 5 backup and check the battery compartment before resetting the controller or changing the memory submodule.

To sell a used 6ES5 101-8UB13, send the quantity, working condition or fault details, a label photo and your asking price to otomasyonavm@gmail.com.

Related topics

SIMATIC S5-90U | S5-100U CPU 102 | S5-100U CPU 103

Navigation

Shared SIMATIC S5 PDF archive | S5 CPU 90U–115U | Used SIMATIC S5 | Siemens second-hand main page | Second-hand automation

References

Siemens SIMATIC S5-101U Operating Instructions (PDF, EN) · Document EWA 4NEB 810 2119-02c. Terminal assignments in Figure 11, p. 2-5. Technical specifications on pp. 5-1–5-3. PG cable on p. 6-1.