6EW1380-1AB

Siemens 6EW1380-1AB SIPAC Power Supply — 24 V DC, 4 A

Siemens 6EW1380-1AB, identified as SIPAC 380-1AB in legacy Siemens documentation, is a regulated 24 V DC / 4 A power supply. It accepts a single-phase 93–264 V AC input. Nominal output power is 96 W, calculated as 24 V × 4 A. It supplies control electronics and suitable 24 V loads in Siemens automation installations.

Siemens lists this exact part number as a 4 A load supply in SIMATIC S5 documentation. The catalogue includes its use with S5-95U and S5-100U systems. Our site lists it under SITOP power supplies and Siemens 6EV / 6EW models. Read the general information in About Siemens SITOP alongside the ratings specific to this legacy SIPAC unit.

Input and regulated output

Input: nominal 115/230 V AC, non-selectable 93–264 V AC range; nominal frequency 50/60 Hz, permissible range 47–63 Hz. Output: 24 V DC with a catalogue tolerance of 23.7–24.3 V and a load current range of 0–4 A. This voltage tolerance should not be interpreted as an adjustment range.

Protection: electronic short-circuit protection, galvanic isolation between input and output, and Class I construction are specified. Protective grounding is part of the installation. Electronic protection does not require prolonged shorting of the output as a test method.

Mounting and distribution of 24 V loads

The catalogue shows direct DIN-rail mounting without a separate bus unit. Approximate width is 80 mm, weight 0.7 kg and typical power loss 17 W. Preserve cooling space in the enclosure and select wiring, connectors and power supply accessories for the required current.

When PLCs, sensors and relay loads share the supply, assess both their continuous consumption and startup currents. Long cables or loose terminals can reduce voltage at the load even when the supply output is correct. The 4 A figure applies to the total output, not to each outgoing branch.

Measurements and controlled load testing

Begin with a suitable multimeter at the output terminals, then measure at the load. For intermittent PLC resets, also examine voltage fluctuations and brief dips. If using an oscilloscope, verify the reference connection and probe rating; do not connect a conventional grounded probe indiscriminately to the mains side.

After verifying the connections, a suitable electronic load can be stepped through values such as 1 A, 2 A and 4 A. For a resistive load, Ohm’s law gives a 6 Ω resistance at 24 V / 4 A, dissipating 96 W. Use a resistor with an appropriate continuous rating above this dissipation and adequate cooling. This is a test-fixture calculation, not a substitute for a manufacturer acceptance test.

When comparing the similar part number 6EW1380-1AA, check the nameplate, input range, connections and revision. Matching 24 V / 4 A output ratings alone do not establish mechanical and electrical suitability for every installation.

Editor’s Note

A no-load reading of 24 V is a useful start, but do not stop there. If voltage falls when the PLC starts, measure at both the supply and the PLC power connection. A growing difference points towards terminals, cabling or the return path; do not replace a healthy supply to compensate for a wiring loss.

On a unit that starts poorly when cold or becomes unstable when warm, electrolytic capacitors are inspection candidates. Look beyond swelling and assess capacitance, ESR and leakage. Preserve the required voltage, temperature and ripple-current ratings when replacing components. These are workshop inspection suggestions, not confirmed recurring faults for this model.

If an input fuse has opened, do not simply replace it and reapply power. After isolation and measurement confirming discharged capacitors, inspect rectifier diodes, power semiconductors and damaged areas. Do not increase the fuse rating. Mains-side repair requires a qualified technician with suitable equipment.

A few seconds at full load is not enough evidence. During a controlled test, record output voltage, heating and any drift over time; compare cold startup with restart after warming. Do not treat the factory insulation test voltage as an instruction to apply that voltage during maintenance with the PLC connected.

When buying a used power supply, request a clear 6EW1380-1AB nameplate, revision and terminal photographs. Ask for the input voltage, load current and test duration rather than accepting “working.” If the existing load is already close to 4 A, reassess distribution and capacity instead of raising the output adjustment.

OtomasyonAVM Resources and PDFs

Siemens SITOP files is the reference page for manufacturer documents collected for this series. The following English archive documents support the model ratings and its use in S5 systems.

+ Siemens ST 50 — SIMATIC S5 catalogue archive copy, English PDF; 1998, 500 PDF pages. Printed page 2/78, PDF page 86: SIPAC 380-1AB specification column and 6EW1 380-1AB ordering entry.

+ SIMATIC S5-90U / S5-95U System Manual — English PDF; Edition 03, 620 PDF pages. Printed page E-1, PDF page 597: exact 24 V / 4 A part-number entry. This is not a board-level repair schematic.

Related Topics

Multimeter measurements + Capacitors + Grounding + Ohm’s law

Browse Categories

Siemens 6EV / 6EW models + SITOP power supplies + Siemens S5 PLC + Siemens second-hand equipment + Used power supplies

Siemens and External References

+ Siemens ST 50, 1998 — Siemens catalogue hosted in a distributor archive

+ Siemens S5-90U / S5-95U — original manufacturer system manual