6EW1380-1AA
Siemens 6EW1380-1AA Power Supply — 24 V DC / 4 A
Siemens 6EW1380-1AA is a power supply whose manufacturer label specifies 93–265 V AC input and 24 V DC / 4 A output. Multiplying the rated voltage and current gives a nominal output power of 96 W. This calculation does not state the mains input power or efficiency.
It is listed within the OtomasyonAVM Siemens SITOP power supply and Siemens 6EV / 6EW model sections. It can be assessed for suitable 24 V DC control electronics and loads. Preserve the 1AA suffix; the detailed table for the similar 1AB model must not be presented as this unit’s own data sheet.
Input, output and connection markings
The inspected manufacturer label clearly shows AC 93–265 V. The front input connections are marked L1, N and protective earth. Check the actual unit’s nameplate and terminal markings. Protective grounding and the DC output M reference have different functions.
The DC connections are marked L+ and M: L+ is the positive output and M the DC return reference. The 4 A rating applies to the combined output load. Assess the continuous demand and startup current of the PLC, sensors and relay loads together.
Installation and cabinet wiring
Inspect the mounting, terminal cover, ventilation openings and cable entries. Preserve the intended installation arrangement. A conversion using another DIN rail power supply requires checking mechanical fit, output capability and cable placement; a similar metal housing does not establish identical connections.
24 V measurements and controlled load testing
A qualified technician can use a suitable multimeter to measure L+ against M, then check the voltage at the receiving equipment. If the supply reading is correct but the load voltage is low, inspect terminals, cables and the return path. Intermittent resets also warrant investigation of brief voltage fluctuations, rather than relying solely on an average DC reading.
Once the connections are established, a suitable electronic load can be stepped through controlled values such as 1 A, 2 A and 4 A. Ohm’s law gives a 6 Ω resistance for a 24 V / 4 A test, dissipating approximately 96 W. Select sufficient continuous power margin and meet the load component manufacturer’s cooling requirements. This is a workshop test-fixture calculation, not a Siemens acceptance test.
If the output collapses under load, investigate a downstream short circuit or excessive demand as well as a supply fault. If the input fuse opens, do not continue testing with a higher rating. Establish the correct protection details for this exact unit rather than copying another model.
Repair and thermal checks
After isolating power and verifying by measurement that stored voltage has discharged, assess electrolytic capacitors for capacitance and ESR, and check diodes using methods appropriate to the circuit. Inspect discoloured connectors, loose contacts and heat-stressed solder joints. These are general service inspection points, not a confirmed list of recurring faults for this model.
For an output deviation, consider voltage regulation, the actual load and connection losses together. Linear and switching regulators require different diagnostic approaches. Confirm the circuit before changing adjustments or component types. After repair, record cold startup, stability after warming and controlled load testing separately.
Distinguishing 1AA, 1AB and related models
6EW1380-0AA and 6EW1380-1AB have separate model records. The input limits, output tolerance, short-circuit protection and mounting specifications for 1AB must not be transferred automatically to 1AA. Compare the full model, nameplate, dimensions and connections when assessing a replacement.
When selecting a used power supply, request a clear 6EW1380-1AA nameplate, terminal photographs and repair history. Obtain the input voltage, load current and duration used during testing. A no-load voltage reading provides different evidence from operation under load.
Editor’s Note
If the nameplate says 1AA, keep that suffix in the service record. Finding a 1AB data sheet does not establish every rating for this unit. Input range, output tolerance and protection behaviour require particular care.
Do not stop at a no-load 24 V reading. If a fault appears when the PLC or relays start, assess both the supply output and the voltage reaching the load. A poor M return connection can make a healthy supply look defective.
Control the 4 A load test and account for approximately 96 W of heat in a resistive fixture. Provide sufficient power margin and cooling; a small resistor is unsuitable. Record current, voltage and test duration.
Capacitors are inspection candidates when cold starting or warm operation is unreliable. Assess capacitance and ESR as well as appearance. Replacing components indiscriminately is not a substitute for diagnosis.
If the fuse opens, avoid repeatedly replacing it and reapplying mains. Isolate power and verify discharge before inspecting the input and power circuits. Increasing the fuse rating does not resolve the fault.
For a used unit, inspect darkened terminals, cracks, loose contacts and repair work before judging the clean cover. Ask what input voltage, current and duration were used for testing. The actual test scope determines the evidence available.
OtomasyonAVM Resources and PDFs
Browse the Siemens 6EV / 6EW model pages and the Siemens SITOP files document index.
+ SIMATIC S5-90U / S5-95U System Manual — English PDF. Edition 03, 1994; 620 pages, 5.88 MiB. Document number: EWA 4NEB 812 6115-02b. This is supplementary material for general S5 supply and wiring requirements. It is not a dedicated 6EW1380-1AA service manual; the 4 A model listed on accessories page E-1 is 1AB.
Related Topics
Ohm’s law + Multimeter measurements + Protective grounding + Capacitors
Used equipment enquiries: Provide the model, quantity, working/faulty condition, nameplate photographs and price. Sales require an invoice; returns are not accepted for used products. Workshop testing can be arranged with an agreed scope. To offer equipment for sale, send details and photographs to otomasyonavm@gmail.com.
Browse Siemens Power Supplies
Siemens second-hand equipment + SITOP power supplies + 6EV / 6EW models + Used power supplies
Siemens and External References
+ Siemens 6EW1380-1AA manufacturer label and connection markings — photograph. The manufacturer label was inspected on an example photographed by Classic Automation.
+ Original Siemens S5-90U / S5-95U System Manual — general system reference