6EW1380-0AA

Siemens 6EW1380-0AA External Power Supply — 220 V AC / 24 V DC, 2 A

Siemens 6EW1380-0AA is identified in product records as an external power supply with a single-phase 220 V AC input and a 24 V DC / 2 A output. The calculation 24 V × 2 A = 48 W describes nominal output power, not input consumption or power loss. When assessing a power supply for older Siemens automation equipment, check the complete order number against the original nameplate.

This unit appears in our Siemens 6EV / 6EW model directory. Its position alongside SITOP power supplies does not establish interchangeability with a current supply. Match the mounting arrangement, connections and electrical requirements of the intended load separately.

Input and output ratings

The catalogue description specifies a single-phase 220 V AC input and a 24 V DC / 2 A output. Establish the permissible input voltage range, frequency, output tolerance and protection behaviour from the exact unit’s nameplate or manufacturer documentation. 2 A is the listed nominal output capacity, not a current that the load must continuously draw.

Total current for 24 V loads

If a PLC, sensors and relay coils share the supply, verify each load’s suitability for 24 V DC and its steady and startup currents. For example, a total continuous load of 1.5 A leaves an arithmetic difference of 0.5 A relative to the 2 A class. Whether that is sufficient for startup transients and operating conditions requires a separate assessment. This calculation alone does not establish application suitability.

Difference from 6EW1380-1AA and 1AB

6EW1380-1AA and 6EW1380-1AB are listed as 24 V / 4 A models. 6EW1380-0AA is the 24 V / 2 A unit. In particular, do not transfer the wide input range or other specifications of 1AB to 0AA. Check every connection and loading requirement before substituting a similar order number.

Load-test calculation examples

By Ohm’s law, a 24 Ω load at 24 V draws approximately 1 A and dissipates 24 W. A 12 Ω load corresponds to approximately 2 A / 48 W if the nominal 24 V is maintained. Select load resistors against their manufacturer’s continuous power and cooling requirements. These are calculations, not recorded test results for a unit. Begin with a low load and verified connections; establish full-load conditions from service information.

Use a multimeter to measure the output and then the powered device’s input under the same load conditions. A correct no-load 24 V reading can fall when a load is applied. Investigate the mains supply, contact resistance and connected loads together when examining voltage fluctuations. Before using an oscilloscope, establish the measurement reference and suitable probe voltage ratings.

Connection and repair checks

Identify AC input and DC output from the original markings rather than wire colours alone. Preserve the original protective earthing arrangement and any PE connection. Select wiring, terminals and power supply accessories for the actual current. No verified terminal table for this complete order number was obtained, so no terminal numbers or jumper arrangements are stated here.

If protection operates or the output collapses, investigate possible short circuits in the connected equipment. Do not conceal a fault by increasing the fuse rating; replacements must preserve the specified type, current, voltage and breaking capacity. Mains-side work requires qualified technical personnel, isolation and safe discharge of stored energy.

During repair, inspect any rectifier diodes, electrolytic capacitors, output connections and power-carrying solder joints identified in the actual circuit. Parallel paths can affect in-circuit measurements. These are general inspection candidates, not a model-specific recurring-fault list or a verified circuit diagram.

When buying a used power supply, request the complete 6EW1380-0AA label, revision, connector photographs and load-test details. A statement that it produces 24 V should include the measured load current and test duration. Consider mechanical damage, overheating marks and previous repairs as well.

Editor’s Note

Start with what the loads actually need. A 24 V marking does not imply the same current demand for every device. Add relay coils, controllers and sensors individually. If steady consumption approaches the limit, assess startup behaviour as well as whether the equipment currently runs.

A no-load 24 V reading is only an initial check. Use a suitable fixture for partial loading and then the documented operating conditions. Record voltage, current, heating and test duration. Include any temperature-related voltage change in the fault report.

An output collapse does not automatically condemn the supply. A shorted load, crushed cable or incorrect connection can produce a similar symptom. Separate circuits with power isolated and assess them in a controlled manner. Repeatedly reconnecting the same faulty load does not help diagnosis.

Base capacitor replacement on measurements. Swelling and leakage are useful clues, but a normal-looking component can also be defective. Check capacitance and ESR. Preserve temperature, voltage and ripple-current ratings; matching capacitance alone is insufficient.

Keep the 0AA specifications separate from 1AA and 1AB. Similar enclosures and order numbers do not prove identical input ranges or connections. Read the actual mains-input marking. Wire colours and previous wiring are not substitutes for manufacturer identification.

Ask for the test record when buying used. Identify the complete label, revision and repair history, and check both cold starting and warm operation. To offer a unit for sale, send its full code, quantity, label photograph and known condition to otomasyonavm@gmail.com.

OtomasyonAVM Resources and PDFs

Browse our Siemens 6EV / 6EW model pages and Siemens SITOP guide for related records.

Siemens SITOP files is the common document page for this project.

TPCOVN — Siemens parts list, English PDF (94 pages, approximately 2.2 MiB). PDF page 41 lists 6EW1380-0AA as 24 V DC / 2 A, single-phase 220 V. This is a supplier parts list, not a Siemens manufacturer manual, wiring diagram or service instruction.

Documentation scope: A verified manufacturer datasheet for this complete order number was not obtained. Establish input tolerance, frequency range, IP rating, terminal numbers and protection thresholds from the original nameplate or model-specific manufacturer documentation.

Related Topics

Ohm’s law, multimeter measurements, short circuits and capacitors are useful background topics for maintenance preparation.

Browse Siemens Power Supplies

+ Siemens 6EV / 6EW models

+ Siemens SITOP power supplies

+ Siemens second-hand catalogue

+ Used power supplies

External References

TPCOVN / Thinh Phat — Siemens parts list, original source PDF — exact-code product description record.

6EW1380-0AA — product identification comparison — single-phase 220 V / 24 V DC, 2 A description; not manufacturer service documentation.