6EW1110-5AC
Siemens 6EW1110-5AC S5-150A Power Supply — 24 V DC / 5 V
Siemens 6EW1110-5AC is a power supply unit for the SIMATIC S5-150A central controller, converting a 24 V DC input into the 5 V system supply. The operating manual lists the exact part number as 18 A. It powers the CPU and associated central-controller electronics in the Siemens automation system.
This unit belongs to the legacy 150A arrangement of the SIMATIC S5 family. Our site lists it under 6EV / 6EW models and SITOP power supplies. The general information in About Siemens SITOP should be read alongside this model’s input rating and central-controller connections.
24 V input and 5 V system output
Input: 24 V DC, with a 20–30 V DC permissible range in the 6EW1110-5 family table. Output: the 5 V system rail, with a documented standard setting of 5.1 V. Input/output galvanic isolation is specified. Assess measured voltage together with load current.
Current rating record: manual C79000-B8500-C227-2 lists 18 A for 6EW1110-5AC. Some archive text records also show 16 A. Before purchase or full-load testing, match the unit nameplate, revision and applicable document edition; do not apply conflicting archive ratings indiscriminately to every unit.
Distinguish the 5 V system rail from the external 24 V supply for machine relay and field loads. Preserve input polarity, system references and protective grounding according to the manufacturer diagram. Do not improvise connectors or power supply accessories.
Front-panel voltage and current measurements
The family manual identifies UAN test sockets for output voltage and IAN test sockets for monitoring output current. The IAN scale is 10 mV = 1 A. Use a suitable multimeter on its DC millivolt range; for example, 50 mV corresponds to 5 A on this scale. Do not draw load current through the test sockets or short them with an ammeter.
The green Stromversorgung klar indicator signals the presence of input and output power. Yellow Pufferung gestört concerns the backup battery. The manual also describes red Lastspannung fehlt for missing field-load voltage. Some 150A delivery options are listed without load-voltage monitoring, so confirm this function against the actual front panel and wiring diagram.
Load testing, connection losses and backup
For intermittent CPU stops, go beyond a no-load voltage reading. Measure at the supply and central-controller power connection under a controlled load, and examine voltage fluctuations. By Ohm’s law, 10 mΩ contact resistance at 10 A produces a 0.1 V drop. This calculation illustrates why small connection losses matter on a low-voltage system rail.
The manual includes a NiCd battery backup arrangement. Before battery work, obtain program and data backups and use the specified battery module and replacement procedure. Do not remove or insert the power supply unit while energized.
The similar-looking part numbers 6EW1110-5AB and 6EW1110-5AE identify separate products. Compare the full code, mechanical connections, backup arrangement and machine diagram before deciding on interchangeability.
Editor’s Note
If the CPU stops intermittently, give the power path a proper check before blaming the processor. Measure the 5 V rail at both the supply and central controller, preferably as the load changes. If it is stable at the source but falls at the cards, investigate connectors, bus connections and the return path. Do not raise the output adjustment to disguise a poor contact.
On a supply that starts slowly when cold or oscillates under load, do not judge electrolytic capacitors by appearance alone. Check capacitance, ESR and leakage, and inspect heat-stressed solder joints. These are troubleshooting candidates, not confirmed recurring faults for this model.
If an input fuse opens, investigate the short-circuit cause first. After isolation and measurement confirming discharged capacitors, inspect rectifier diodes and power semiconductors. A 24 V input does not remove high-current and stored-energy hazards. Do not increase the fuse rating.
For a yellow backup warning, secure the program backup first. If an old NiCd module has leaked or its contacts are corroded, inspect nearby board tracks as well. Do not substitute lithium cells without verifying compatibility with the charging circuit. Operating an acknowledgement button, where fitted, does not repair a weak battery or damaged charging path.
When buying a used power supply, request the complete 6EW1110-5AC nameplate, revision and connector photographs. Record input voltage, test current and duration. Compare the IAN indication with the load instrument, and check cold startup and stability after warming. Do not proceed to the highest test current before confirming the nameplate rating.
OtomasyonAVM Resources and PDFs
Siemens SITOP files is the common document reference page for this series. Both documents below are in German. The S5-150A operating manual is the main technical source; the System 8 document provides supplementary historical system and spare-parts context.
+ SIMATIC S5-150A Central Controller Operating Instructions — German PDF; C79000-B8500-C227-2, 25-page archive file. Specifications: PDF 8 / printed 6; connections: PDF 9 / printed 7; indicators: PDF 11 / printed 9; exact 5AC entry: PDF 24 / printed 22.
+ SINUMERIK System 8 — Startup Checklist, Part 2 — German PDF; June 1984 compilation, 188 pages. PDF 22 / printed 4-7 contains the 150A supply and spare-parts list. Compare values against the scanned page image rather than relying solely on extracted text.
Related Topics
Siemens S5 PLC + Multimeter measurements + Capacitors + Ohm’s law