Siemens 6EW1110-5AA belongs to the 6EW1110-5 power supply family used with legacy SIMATIC S5 systems. The Siemens S5-150A central-unit manual lists 24 V DC input, 5.1 V DC output and 18 A nominal output current for this family. These are family reference values and must be matched to the nameplate and hardware revision of the particular 5AA unit.
Assess this supply as part of the controller’s internal electronics. Replacing it with a general industrial power supply or a current SITOP model requires more than a matching voltage. Our Siemens 6EV / 6EW model group and SITOP selection guide help place the products in their respective application contexts.
DC input and electronic system supply
The family table specifies a 20–30 V DC input range and 5.1 V DC ±1% output. Assess voltage requirements separately from current capacity. Keep the 24 V input distinct from the lower-voltage system output; do not connect mains voltage or reverse the input polarity.
Identify the correct output reference before using a multimeter. Protective earth, chassis and circuit common must not be treated as interchangeable without the wiring information. Losses through connectors and other power supply accessories can reduce the voltage reaching the boards even when the supply itself is functioning correctly.
Front-panel voltage and current test sockets
In the documented front-panel arrangement, U_AN is used for voltage checks and I_AN provides a current measurement signal. The stated scale is 10 mV = 1 A; for example, 60 mV represents 6 A. This is neither a load output nor a socket for directly inserting an ammeter in series. Confirm that the markings on the actual unit match this arrangement first.
Status indications and memory backup
The family’s front-panel description identifies green “Stromversorgung klar” with input/output voltage present, and red “Lastspannung fehlt” with missing external 24 V load supply. Yellow “Pufferung gestört” is associated with battery voltage below 2.7 V. Check which monitoring functions and indicators are fitted to the particular revision.
NiCd backup modules such as 6EW1000-4AB require a separate assessment. The manual’s spare-parts table associates this battery module with the 5AC version; compatibility with 5AA must not be assumed. A battery warning in a PLC system is different from failure of the main supply output.
Distinguishing 5AA, 5AB, 5AC and 5AE
6EW1110-5AB, 6EW1110-5AC and 6EW1110-5AE are nearby family references. Similar construction or common nominal ratings do not establish complete interchangeability. Compare the full suffix, monitoring functions, battery arrangement and connections together. Our Siemens S5 PLC overview provides further system context.
Editor’s note
Before working on an older S5, secure a usable program and machine-data backup. Avoid casual power cycling when the battery condition is unknown. Repairing a power supply is one task; recovering a missing program can be a much larger one.
If investigating low voltage, leave the adjustment potentiometer alone initially. Check the 24 V input under load, then compare the supply output with the board supply points. A shorted board or poor connector can make a functioning supply appear defective.
Where I_AN sockets are fitted, read the millivolt measurement signal. Do not short the sockets by placing the meter in its current range. A properly obtained current reading makes voltage-drop and load-regulation checks more useful.
If a NiCd battery has leaked, inspect the contacts and nearby tracks as well as replacing the battery. Do not connect an arbitrary lithium cell or a different battery chemistry to the charging circuit. Establish the correct battery and replacement procedure for the unit’s revision.
Before internal repairs, isolate power and verify that capacitor voltage has discharged. Investigate rectifier and power-semiconductor shorts, capacitor capacitance/ESR, cracked joints and overheated connections. Replacement parts must match voltage, temperature and operating requirements as well as capacitance.
Do not declare used Siemens equipment healthy after a no-load check alone. Once the nameplate and connections are confirmed, record cold startup and stability after warming up under an appropriate load. A green LED alone does not establish battery health or prove that every monitoring function has been tested.
OtomasyonAVM resources and PDFs
Start with our SIMATIC S5 main page and Siemens 6EV / 6EW model archive. The documentation hub selected for this work is the Siemens SITOP files page.
+ SIMATIC S5-150A Central Unit manual – C79000-B8500-C227-2, German, 25-page archive copy. The family technical table is on printed page 6, front-panel/test sockets on page 9, and spare parts on page 22. The first two PDF pages are a different binder cover/contents section; the S5-150A document starts on PDF page 3.
Document scope: The technical table uses the 6EW1 110-5 family designation; the spare-parts table explicitly names 5AC. The complete 5AA code was not verified in a separate technical-data row. Family information therefore does not replace nameplate and revision checks, and this manual is not presented as a component-level repair schematic dedicated to 5AA.
Related topics
+ SIMATIC S5 system overview + Multimeter checks + NiCd backup battery module + Voltage fluctuations
Used-equipment enquiries: Provide the brand, complete model, quantity, working/faulty condition, nameplate photographs and asking price. Sales are invoiced; returns are not accepted for used equipment. Workshop testing is possible where suitable conditions are available. To offer equipment for sale, send its details to otomasyonavm@gmail.com.
Browse categories
+ Siemens SIMATIC S5 + Siemens 6EV / 6EW models + SITOP power supplies + Used Siemens equipment + SITOP PDF archive
Siemens and external references
+ Archive copy of the original Siemens S5-150A central-unit publication. Publisher: Siemens; archive host: SPS-Service.