6EV1322-7AK00

Siemens 6EV1322-7AK00 – Unregulated 24 V DC / 5 A Power Supply

Siemens 6EV1322-7AK00 is an unregulated industrial power supply with 110 / 120 / 220 V AC single-phase input options and a nominal +24 V DC / 5 A output. Check the permitted voltage range of connected control and field loads when using this power supply.

It appears in the Siemens SITOP power supply and 6EV / 6EW model sections on OtomasyonAVM. An unregulated output does not maintain the tight output control of a precision voltage regulator as mains and load conditions change. Account for this characteristic during maintenance and replacement selection.

Manufacturer catalogue ratings

Input voltage tolerance is −15% / +10%, with 50/60 Hz frequency. These ratings do not establish automatic wide-range input operation. Verify the actual nameplate and input configuration before applying power; do not use jumper numbers without a matching wiring diagram.

The output range is 20–30 V including ripple, with a ripple limit of ≤10%. Multiplying nominal output current by voltage gives 24 × 5 = 120 W, not input consumption. Do not assess the unit by expecting exactly 24.0 V under every condition.

The catalogue specifies IP00 protection. Use the open-construction unit within a suitable cabinet or enclosure; check ventilation, terminal access and protective grounding. Assess the condition of the actual legacy unit separately.

Measurements and testing under load

Use a suitable multimeter for DC voltage measurement, recording mains voltage and connected load as well. Observe unloaded behaviour first, then apply controlled load within the unit’s limits. Output variation with load is not by itself evidence of a fault in an unregulated supply; also check the voltage limits of the connected equipment.

When investigating voltage fluctuations or excessive ripple, general inspection points include filter capacitors, rectifier diodes and power connections. These are not verified recurring faults specific to this model. Use differential or isolated equipment suitable for the circuit when taking oscilloscope measurements.

Compare voltage at the supply and at the load. Investigate wiring and terminals when a voltage drop occurs. At 5 A, a connection resistance of 0.1 Ω causes a 0.5 V drop and 2.5 W of local heating under Ohm’s law. This illustrates connection losses; it is not a proposed test connection.

Fusing and short-circuit protection

The manufacturer’s table describes the output as not fused. A 5 A nominal rating does not guarantee electronic current limiting or short-circuit protection. Verify input and load-circuit fusing against the machine drawings; do not perform a deliberate short-circuit test.

If a fuse opens, do not increase its rating; investigate why it failed. Disconnect power and verify that stored voltage has been safely removed before internal inspection. Repeated energization can increase damage when a failed connection, rectifier fault or overload remains present.

Used-unit selection and related models

When selecting a used power supply, request clear nameplate, input-connection and output-polarity information plus a load-test record. 6EV1320-4AC, 6EV1334-4AK00 and 6EV1352-5BK00 are separate models. Compare suffix, phase count, current rating and mounting arrangements before considering interchangeability.

Editor’s Note

Start by remembering that this supply is unregulated. A reading other than exactly 24.0 V does not by itself establish a fault. Assess mains conditions, load and the connected equipment’s voltage limits together.

Do not mistake the input options for automatic selection. Confirm the required 110, 120 or 220 V configuration from the unit’s own wiring information. Do not borrow jumper arrangements from another 6EV model.

Investigate voltage collapse under load with measurements. The upstream source, rectifier, filter and connections are separate inspection candidates. A capacitor’s normal appearance does not prove that it is serviceable.

Do not short the output to see whether protection operates. The 5 A nameplate rating does not establish safe current limiting. Find the load fault rather than increasing the fuse rating.

Respect exposed connections and stored energy. Use suitable equipment around mains voltage; disconnecting power does not prove that capacitors have discharged.

Record current and test duration. Check cold start, controlled loading and warm operation before calling the unit serviceable. These are general service suggestions, not claims of recurring model-specific faults.

Documents and PDF Resources

Browse our Siemens SITOP files document index and the Siemens 6EV / 6EW model pages.

Siemens ST 11 – Manufacturer Catalogue. German, 1981/02.1984, 108 PDF pages, 17.79 MiB. Exact-model specifications: PDF page 100, printed 7/10; ordering list: PDF page 107, printed 9/6. The catalogue refers to ET 1 for further diagrams and dimensions.

Related Topics

6EV1320-4AC + 6EV1334-4AK00 + 6EV1352-5BK00 + 6EW1380-1AB. These are different power-supply records; the links are not direct replacement recommendations.

Used equipment enquiries: Provide the brand, full model, quantity, working/faulty condition, nameplate photographs and price. Sales require an invoice; returns are not accepted for used products. Workshop testing can be arranged with an agreed scope. To offer equipment for sale, send details to otomasyonavm@gmail.com.

Browse Siemens Power Supplies