6ES5 482-8MA12

Siemens 6ES5 482-8MA12 – 16-Input / 16-Output 24 V DC Digital I/O Module

Siemens 6ES5 482-8MA12 is a 24 V DC digital I/O module with 16 inputs and 16 transistor outputs for S5-100U and relevant ET 100U/ET 200U peripheral applications in the SIMATIC S5 family. Among combined S5 input/output modules, its defining feature is the split between eight 0.1 A outputs and eight 0.5 A outputs. The Siemens table for the exact −8MA12 version specifies no galvanic isolation on either the input or output side.

The module reads signals from inductive sensors, photoelectric sensors and limit switches while driving suitable DC loads. It therefore combines 32 digital channels in one module. However, not all sixteen outputs are rated at 0.5 A, and the specified total output current limit is 4 A.

Input levels and common reference

The inputs are rated for 24 V DC, with 0–5 V for logic 0 and 13–30 V for logic 1. Typical input current at logic 1 is 4.5 mA. Check the difference between PNP and NPN sensors together with the M connection of the field power supply. Without galvanic isolation, signals with different reference potentials must not be assumed directly compatible.

Typical input delays are 4 ms for OFF-to-ON and 3 ms for ON-to-OFF. Two-wire BERO sensors may be connected, provided their OFF-state residual current does not exceed 1.5 mA. The red input fault indicator reports an L+ or M interruption; that indication alone does not establish that the entire module has failed.

Output groups: 0.1 A, 0.5 A and the 4 A total limit

On the OUT side, terminals 2–9 form the 0.1 A group and terminals 12–19 form the 0.5 A group. Specified load-current ranges are 5–100 mA and 5–500 mA, respectively. When selecting separate S5 digital output modules, compare the channel ratings of types such as 441-8MA11 and 453-8MA11 against their own specifications; channel count alone is insufficient.

8 × 0.5 A + 8 × 0.1 A = 4.8 A, which exceeds the module’s 4 A total limit. Do not assume that every output can carry its nominal channel current simultaneously. The rated load supply is 24 V DC, with a continuous operating range of 20–30 V. Both output groups have short-circuit protection and a red short-circuit indicator.

Maximum OFF-state residual current is 0.6 mA for the 0.1 A group and 1 mA for the 0.5 A group. A very low-current indicator or measuring instrument may therefore show voltage while an output is OFF. The manufacturer specifies switching frequencies of 100 Hz with resistive loads and 2 Hz with inductive loads; these ratings must not be interchanged.

40-pole front connector and IN/OUT terminal assignment

The Siemens drawing lists the 40-pole crimp 6ES5 490-8MA12 or screw-terminal 6ES5 490-8MB11 front connector. Read the IN and OUT sections separately; each section has its own terminals numbered 1–20. The same terminal number can have a different function on the input and output sides.

IN section: 1 = L+, 20 = M; 2–9 = (n+1).0–(n+1).7; 12–19 = n.0–n.7; 10 and 11 = NC. OUT section: 1 = L+ for the 0.1 A group, 10 = M; 2–9 = (n+1).0–(n+1).7. For the second output group, 11 = L+, 20 = M; 12–19 = n.0–n.7, rated at 0.5 A per channel. Confirm the IN/OUT markings before transferring wires by terminal number.

Field wiring connects at the front connector, while the system bus connects through the appropriate bus unit. Check parts such as the 700-8MA11 screw-terminal bus unit and 700-8MA21 crimp-terminal bus unit against the installed arrangement. Typical module power loss is 4.5 W and approximate weight is 190 g.

Addressing and the −8MA13 revision distinction

The sixteen inputs occupy two input bytes, and the sixteen outputs occupy two output bytes. Match the front-panel n and n+1 markings to the S5 addressing arrangement. In an example with start address n = 64, the inputs use I64/I65 and the outputs Q64/Q65: the 0.5 A output group uses Q64 and the 0.1 A group uses Q65. Verify actual start addresses in the installation. ET 200U permits separate input and output start addresses.

The 6ES5 482-8MA13 has a different output-current arrangement; its sixteen 0.5 A outputs must not be attributed to the −8MA12. Nor should the 6ES5 482-8MA11 be treated as equivalent merely by comparing the final digit. Check CPU version, front connections, addressing and load distribution together.

For input-only applications, assess the S5 input module range separately. This device performs both acquisition and load switching in a SIMATIC S5 system. Extend the checks normally applied to a used input module to cover all sixteen inputs and sixteen outputs, both output-current classes and the fault indicators.

Editor’s note

Identify the two output groups first. The upper n+1 group is rated at 0.1 A, while the lower n group is rated at 0.5 A. Do not apply the same load indiscriminately to all sixteen outputs, and keep the 4 A total limit in the load calculation.

Follow the IN and OUT markings. Terminals 10 and 11 do not perform the same functions on both sides. Photograph the existing wiring before removal and compare every connection with the front-panel legend and diagram.

A lit LED does not replace a load test. Use a suitable test load within the channel rating. If an output shows voltage unloaded but collapses under load, measure the load supply and group M connection before approving the module.

Inspect the field circuit when a red fault indicator appears. A shorted coil, damaged cable or incorrectly connected load can operate the protection. Record which group of eight is affected and remove the cause before re-energising.

Keep −8MA12 explicit in the records. A −8MA13 description or an old stock-list entry can obscure the current limits of this version. Request separate loaded tests of both output groups and establish test conditions that prevent machine movement.

OtomasyonAVM resources and PDFs

+ S5 digital input/output modules

+ Siemens S5 PLC main page

+ S5 PDF files — shared manual archive

Related topics

+ 482-8MA13 and its different output-current arrangement

+ 490-8MB11 screw-terminal front connector

+ PNP and NPN sensor comparison

Browse SIMATIC S5

+ S5 digital input/output modules

+ SIMATIC S5

+ Siemens second-hand main page

Siemens and external references

+ Siemens S5-100U Gerätehandbuch — German; exact 482-8MA12 wiring and specification extract, 14-32–14-33

+ Siemens ET 200U Manual — English; 482-8MA12 addressing and diagnostic applications

+ Siemens S5-100U System Manual — English; addressing for the combined 16-input/16-output family, section 6.4.2