Siemens 6ES5 436-4UA12 – 16-Channel 115/230 V AC Digital Input Module

6ES5 436-4UA12 is a 16-channel, 115/230 V AC, 47–63 Hz Siemens SIMATIC S5 input card for S5-135U/155U systems. This member of the S5 digital input range has two isolated groups of eight inputs.

The card transfers on/off information from AC control circuits to the SIMATIC S5 system. Use the appropriate rack and front-connector arrangement, and match input voltage, group commons and address switches to the existing project when replacing it.

Signal levels and input current

Logic 0 is 0–60 V AC; logic 1 is 90–264 V AC. Voltages between 60 and 90 V should not be used as a defined logic state. Typical input current is 15 mA at 115 V and 25 mA at 230 V. The manual permits two-wire BERO connection; check sensor voltage and leakage-current characteristics together.

The digital section draws typically 100 mA at 5 V from the system bus. Assess bus consumption and the AC field circuit separately when checking the power supply. Permitted signal cable lengths are 600 m unshielded and 1000 m shielded; also assess routing and interference conditions.

Response time and pulse limit

Positive-edge delay is typically 5 ms, with a 2–15 ms range. Negative-edge delay is typically 20 ms, with a 10–25 ms range. Maximum pulse-train input frequency is 20 Hz. Distinguish this limit from the 47–63 Hz frequency of the AC signal itself.

Connecting the two groups

The first group uses 1N: pin 4, with inputs on pins 6, 8, 10, 12, 14, 16, 18 and 20. The second group uses 2N: pin 25, with inputs on pins 27, 29, 31, 33, 35, 37, 39 and 41. Preserve group isolation and maintain the specified neutral connections separately from protective grounding.

Selecting the front connector

Catalog ST 50 specifies a double-width, 20-pole front connector for this card. The 6ES5 497-4UB42 provides screw terminals; the crimp-terminal option is 6ES5 497-4UA42. Twenty poles does not mean that the drawing uses pin numbers 1–20. Follow the Siemens terminal numbering given above.

F+/F− enable circuit and jumper X20

F+ pin 1 and F− pin 2 are bridged in the front connector. With X20 fitted, enable monitoring is active; this is the factory setting. With X20 open, monitoring is disabled. Do not apply AC field voltage to F+/F−. Preserve the bridge and X20 arrangement required by the system’s interlocking and module-removal design.

Address switches and two-byte allocation

The module uses two consecutive input bytes. Its switches set the starting address independently of the slot. If the input/output address plan assigns decimal 20 = 14H, select weights 16 and 4; the card then occupies IB 20 and IB 21. In English STEP 5 notation, channels are I 20.0–I 21.7. A 16-channel card requires an even starting address, and its second byte must remain reserved.

Ventilation, simultaneous loading and EMC

Power dissipation is 3.5 W at 115 V and 17 W at 230 V. The manual gives 100% simultaneous loading with ventilation. Without ventilation, it lists 75% at 230 V, 100% at 35 °C and 100% at 115 V. Assess continuously active inputs against these conditions in the central rack or expansion rack.

Siemens EMC notes require a SIFI C or equivalent filter in the module’s 230 V AC field supply. Assess the filter and cable shielding together with the cabinet arrangement and manufacturer’s installation instructions.

Differences from similar codes

The 6ES5 436-4UB12 has 8 individually isolated inputs. The 6ES5 435-4UA12 is for 24–60 V AC, while the 6ES5 431-4UA12 is for 24–60 V DC. Their voltage ratings and isolation arrangements differ.

The 6ES5 434-4UA12 is a separate TTL/CMOS/NAMUR input card. The 6ES5 436-4UA11 is an earlier order revision; confirm its own specifications and wiring before applying details from the 4UA12.

Replacement preparation and used-module checks

Back up the program and memory unit. Record the programmer interface connection, address switches and X20 position, and photograph channel labels on the connector.

During S5 maintenance, test all 16 inputs in their two groups using a suitable AC test source. For used Siemens modules, state label details, included connectors, physical condition and completed tests for the individual item.

Editor’s note

Check the common connection if eight inputs disappear together. A loose group neutral can make sound channels appear faulty. Check 1N and 2N against their respective groups before setting the card aside.

Keep track of the small bridge when changing connectors. Photograph F+/F− and the original X20 position. A missing enable connection can otherwise lead to a long search around a healthy card.

Check airflow when operating at 230 V. A turning fan needs a clear air path as well. Look at cabinet temperature and the number of continuously active inputs together.

Photograph the address switches before touching them. This card occupies two bytes. Check both the starting byte and the following byte when fitting the replacement to avoid an address conflict.

Finish by checking every channel. Use a suitable AC source and protected test arrangement to verify both switching states. Record the group and readings so that the card’s condition remains clear afterwards.

OtomasyonAVM resources and PDFs

+ Shared SIMATIC S5 manuals and PDF archive

+ S5 digital input modules and model pages

Related topics

+ 6ES5 436-4UB12 – 8-channel AC input

+ 6ES5 435-4UA12 – 24–60 V AC input

+ 6ES5 431-4UA12 – 24–60 V DC input

+ 6ES5 434-4UA12 – TTL/CMOS/NAMUR input

+ 6ES5 497-4UB42 – 20-pole front connector

Browse SIMATIC S5

+ Back to S5 digital input modules

+ SIMATIC S5 system pages

+ Siemens S5 PLC main page

+ Used Siemens products and models

Siemens and external references

+ Siemens S5-135U/155U – 436-4UA12 specifications, 8-44 (English)

+ Siemens – pin assignments and X20, 8-45 (English)

+ Siemens – starting address and two-byte allocation, 8-15 (English)

+ Siemens – 230 V AC supply filter, 1-5 (English)

+ Siemens ST 50 – input ratings and connector options, 4/35–4/36 (English)