6ES5 420-3BA11
Siemens 6ES5 420-3BA11 – Compact K Digital Input Module, 32 × 24 V DC
Siemens 6ES5 420-3BA11 is a non-isolated digital input module with 32 inputs at 24 V DC, used in S5-130K, S5-130W and S5-150K systems within the SIMATIC S5 family. This compact K module converts field signals into logic states for the CPU. Its distinguishing features include an on-board address-coding socket, a four-byte input area and a typical input delay of 3 ms.
Typical field devices include pushbuttons, mechanical switches, inductive sensors and photoelectric sensors. Check the PNP or NPN connection type against the positive-voltage input arrangement shown in the wiring diagram. Dry relay contacts can switch a suitable DC source to an input. Keep the complete 3BA11 suffix when identifying the mechanical family and connection arrangement.
Input voltage and response time
The nominal input is 24 V DC. Siemens specifies −33 to +4.5 V, or an open input, for logic 0 and +13 to +33 V for logic 1. These recognition thresholds are separate from the nominal supply voltage. Measure DC voltage against the input's reference, and do not treat a signal between 4.5 and 13 V as a defined logic state.
Input current is typically 8.5 mA, with a typical delay of 3 ms. The C233-3 operating instructions specify a delay range of 1.4–5 ms and a maximum input frequency of 100 Hz. CPU scanning also affects the complete detection time. Do not confuse this card's digital state detection with analog measurement or a dedicated high-speed counting function.
Non-isolated design and field wiring
Potentialgebunden / non-isolated means that the inputs are not galvanically separated from the control electronics. Check the power supply reference, grounding connections and PELV supply arrangement against the existing panel design. The ST 53 wiring diagram specifies the L− connection to the module carrier, making the carrier and reference connections relevant to fault finding.
The ST 53 diagram identifies the inputs as Byte 0, Byte 1, Byte 2 and Byte 3. Use the compact K drawing when selecting the front connector and wiring. Check the mechanical match with the S5 rack; do not transfer the 7LA11 model's 46-pole connector or M-terminal numbering to this card. Photograph the original connector with all wire labels readable before removing it.
Address-coding socket and four input bytes
The byte address is set by the coding plug / addressing socket on the module. A 32-input module starts on a byte address divisible by four: 0, 4, 8…252. The hardware coding must match the PLC program. Do not assume that a coding plug supplied with a replacement card is already configured for the existing machine.
For an example starting byte of 32 = 20h, the four bytes cover I32.0–I35.7. This is an addressing example, not a fixed factory address. Watch the online inputs in the PLC while applying test signals; if the expected local LED lights but a different byte is being read, inspect the address coding again.
Cable limits and comparison with similar codes
The ST 53 catalogue lists maximum input cable lengths of 600 m unshielded and 1000 m shielded, a requirement for one mounting position and an approximate weight of 0.3 kg. Assess cable routing and interference sources separately. Consider the complete Siemens S5 system arrangement during fault finding; changing a card may leave a supply or carrier-contact fault unresolved.
6ES5 430-3BA11 has the same nominal voltage and channel count but provides galvanic isolation. 6ES5 420-7LA11 and 6ES5 420-4UA11 belong to different mechanical and system arrangements. Do not select an equivalent from the S5 digital input range using only “32 inputs” or “24 V”. For a used input module, inspect the complete order number, address-coding socket and front connection together.
Editor’s Note
Start by confirming the 3BA11 code and compact K construction. “420 series” alone is not enough. Put clear photographs of the original and replacement labels side by side and check every suffix.
Give the address-coding socket some attention. A broken, missing or incorrectly coded plug can make a sound replacement look faulty. Photograph the socket and its coding before moving anything.
If several inputs become unstable together, inspect the reference connection and carrier contacts first. This card is non-isolated; a loose connection can make several sensors appear faulty at once. Measure as close to the module connection as practical.
Do not finish the test after lighting two LEDs: try all 32 channels in sequence. Watch the local indication and the program bit together. For a long field cable, record the input voltage with the sensor both on and off.
For a used unit, specify the complete model, quantity, label photograph, working/faulty condition and price. Sales require an invoice; returns are not accepted, and workshop testing is available. To offer a card for sale, send its details to otomasyonavm@gmail.com.
OtomasyonAVM resources and PDFs
+ 6ES5 420-3BA11 model page and SIMATIC S5 main range.
+ Shared Siemens S5 PDF archive. Select documents covering S5-130K/130W/150K and compact K for this module.
+ About Siemens S5 PLCs and S5 cables and connectors.
Related topics
+ 6ES5 430-3BA11 isolated 32-input module and 6ES5 420-7LA11 S5-115U input module.
+ S5 digital output modules and S5 digital input/output modules.
Browse SIMATIC S5
+ S5 digital input modules · SIMATIC S5 · S5 racks and carriers.
+ Siemens second-hand range · Used digital input modules.
Siemens and external references
+ Siemens C79000-B8500-C233-3 operating instructions – German: exact 420-3BA11 data on page 6; system scope on page 2; address coding on pages 3–4.
+ Siemens SIMATIC S5 ST 53 catalogue, 1985 – German: technical data 8/11, wiring diagram 8/24 and complete order number 9/6.
+ Siemens Interface Module Adapter, Version 5.1, August 2019 – English: classification of older S5-130/150K inputs for S7 migration. An adapter table does not establish direct plug-in interchangeability between modules.