6ES5 498-1AA71

Siemens 6ES5 498-1AA71 SIMATIC S5 4–20 mA Measuring Range Submodule

The Siemens 6ES5 498-1AA71 is a four-channel measuring range submodule for 460 and 465 analog input modules in SIMATIC S5 systems. It accepts 4–20 mA from separately powered four-wire transmitters and uses a 31.25 Ω shunt per channel with the host module’s 500 mV setting. Siemens documents this setup for the S5-115U and S5-135U/S5-155U.

A pressure, flow or temperature transmitter uses one pair for its own power supply and a second pair for the current signal at the channel’s M+ and M− terminals. The 498-1AA51 covers the same current range for loop-powered two-wire transmitters. Check the transmitter’s power arrangement as well as its output range when selecting a spare.

Compatible 460 and 465 input modules

The 460-4UA11, 460-4UA12 and 460-4UA13 have eight current or voltage inputs. Each of their two range submodule slots serves four channels.

The 465-4UA11, 465-4UA12 and 465-4UA13 support up to 16 current or voltage inputs. Each of the four range submodule slots configures four channels. The 460 and 465 have different isolation arrangements. Check the allowable potential difference between transmitter references in the specifications for the exact host module.

500 mV setting and field wiring

Set the host analog input module to its 500 mV range. For 460 versions with a gain switch, Siemens shows the ×1 setting. Use the host wiring diagram to identify the channel’s M+ and M− pins. The 497-4UA12 crimp and 497-4UB31 screw-terminal front connectors are single-width, 42-way wiring options.

Different four-channel groups can share the same input module when the settings allow it. In 500 mV mode, examples include 498-1AA11 for ±500 mV, 498-1AA21 for ±1 V, 498-1AA31 for ±10 V, 498-1AA41 for ±20 mA and 498-1AA61 for ±5 V. The fitted range submodule sets the range for its group.

PLC raw values and open-circuit diagnostics

In the Siemens 460/465 tables, 4 mA → 512, 12 mA → 1536 and 20 mA → 2560 raw counts in the measured-value field. Separate the status bits from the measurement before scaling. Subtract 512 from the measured value if the PLC program expects a 0–2048 scale. The Siemens S5 manual index and S5-115 PDF archive lead to the manuals covering measured values and status bits.

The 1AA71 shunt prevents the hardware wire-break bit from being set. Use a low-current threshold in the PLC program that matches the transmitter and the existing alarm logic. If the reading drops, check the transmitter’s separate power supply and current output first.

Editor’s note

Check both labels. When ordering a spare, provide the 498-1AA71 code and the full order number of the 460 or 465 host module.

Record the four-channel group. Photograph the range submodule slot and the host module’s range switches before removal.

Label the two pairs separately. Mark the transmitter supply and the M+/M− signal pair on the terminal diagram.

Test at three points. During maintenance, use a calibrated current source to apply 4, 12 and 20 mA and compare the raw PLC readings.

Check the spare under load. When buying a used Siemens part, ask for results from all four channels. To sell a module, email its full code, quantity, working condition, label photo and price to otomasyonavm@gmail.com.

OtomasyonAVM resources and PDFs

SIMATIC S5 analog and range modules · 460-4UA13 analog input module · 465-4UA12 analog input module

OtomasyonAVM S5-115 PDF archive · SIMATIC S5 system manuals · SIMATIC S5-115H system manual, four-wire transmitter wiring

Related topics

498-1AA51, two-wire 4–20 mA · 498-1AA41, ±20 mA · 497-4UB31, 42-way screw-terminal front connector

Browse the S5 range

Siemens SIMATIC S5 › S5 analog modules

External references

Siemens 6ES5 498-1AA71 data sheet · Siemens S5 U peripherals manual, compatible 460 and 465 modules

Siemens S5-135U/155U system manual, four-wire connection diagram · Siemens S5-115U system manual, raw values and wire-break diagnostics